{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APM9A0CTLY6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APM9A0CTLY6","canonicalUrl":"https://aoctrl.com/schneider/APM9A0CTLY6","factsUrl":"https://aoctrl.com/api/mcp/products/APM9A0CTLY6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process Modular, APM9A0CTLY6, control module, 500-690 V rated supply, STO SIL 3, Modbus TCP/Ethernet.","salesMarkdown":"The Schneider APM9A0CTLY6 is the control unit for the Altivar Process Modular range, designed as the brain of an ATV900 single-drive system rated 500...690 V. It carries the STO safety function at SIL 3, so a machine builder can integrate safe torque off without an external safety relay on the power stage. ## Supply and wiring Digital inputs need 24 V DC (19...30 V). The internal supply for a reference potentiometer (1 to 10 kΩ) is 10.5 V DC ±5 %. STO and digital inputs share a separate 24 V DC rail (21...27 V). Isolation to earth is tested at 1 MΩ, 500 V DC for 1 minute. Keep the STO supply clean — a shared 24 V bus with contactors can dip below the 21 V dropout and nuisance-trip the safe-off circuit. ## Communications and fieldbus Two RJ45 ports on the remote graphic terminal: one for Ethernet/Modbus TCP at 10/100 Mbit/s, one for Modbus serial at 4.8 to 38.4 kbit/s (2-wire RS-485, RTU frame, slave addresses 1...247). The Ethernet port supports half/full duplex and autonegotiation. If you are replacing a legacy Modbus serial drop, the physical interface is 2-wire RS-485 with no impedance polarization — you will need external biasing resistors on the bus. IP00 enclosure — no protection against dust ingress, so it must live inside a panel. Operating temperature is -10 to 40 °C without derating, 40 to 50 °C with derating. Above 1000 m altitude, derate current 1 % per 100 m up to 4800 m. Pollution degree 2 per IEC 61800-5-1. Vibration resistance: 1.5 mm peak-to-peak at 2...13 Hz, 0.5 gn at 13...200 Hz. Shock: 7 gn for 11 ms. The power dissipation is 2980 W at 2.5 kHz switching frequency — forced convection is assumed; plan panel ventilation accordingly.","metaTitle":"Schneider APM9A0CTLY6 Altivar Process Control Module, 500-69","metaDescription":"Active Schneider Altivar Process Modular control unit for ATV900 drives. Rated 500-690V supply, STO SIL 3, Modbus TCP/Ethernet. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Frequency":"50...60 Hz - 5...5 %","IP Rating":"IP00","Product Status":"Active","Pollution Degree":"2 conforming to IEC 61800-5-1","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"50 °C","Temp Operating Min":"-10 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Control module"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad775412c7773d476c95b4b1b22a0e82.pdf","sourceUrl":"https://www.se.com/th/en/product/APM9A0CTLY6/standard-atv900-control-unit-apm-single-drive-500690v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/APM9A0CTLY6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APM9A0CTLY6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APM9A0CTLY6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}