{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APM9B0CTLY6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APM9B0CTLY6","canonicalUrl":"https://aoctrl.com/schneider/APM9B0CTLY6","factsUrl":"https://aoctrl.com/api/mcp/products/APM9B0CTLY6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process Modular APM9B0CTLY6 control module, 500-690 V, STO SIL 3, dual Ethernet/Modbus serial.","salesMarkdown":"APM9B0CTLY6 is the control module for the Altivar Process Modular range, designed to pair with an ATV900 regen drive in the 500-690 V class. It runs the drive logic, fieldbus, and safety functions — separate from the power section, so you can swap a control board without pulling line power. Supply for the digital inputs is 24 V DC (19-30 V), and the STO circuit gets its own 24 V DC rail (21-27 V) with SIL 3 rating. The module also provides a 10.5 V DC reference for a 1-10 kΩ potentiometer. ## Fieldbus & I/O Communication is dual-stack: Ethernet/Modbus TCP at 10/100 Mbit/s (RJ45 on the remote terminal) and a separate RS-485 serial link at 4.8-38.4 kbit/s, RTU framing, slave addresses 1-247. The Ethernet port handles both IP and TCP frames, autonegotiating half/full duplex. Sixteen preset speeds are selectable via discrete inputs — useful for multi-speed applications without reconfiguring the bus. ## Environmental & Mounting IP00 open-frame, rated for pollution degree 2. Ambient operating range is -10 to 40 °C without derating, 40-50 °C with derating. Storage from -40 to 70 °C. Vibration resistance: 1.5 mm peak-to-peak at 2-13 Hz, 0.5 gn at 13-200 Hz. Shock rated at 7 gn for 11 ms. Altitude derating starts at 1000 m — 1 % per 100 m above that. Humidity 5-95 % non-condensing.","metaTitle":"Schneider APM9B0CTLY6 Altivar Process Control Module, 500-69","metaDescription":"APM9B0CTLY6 control module for ATV900 regen drive, 500-690 V AC supply, STO SIL 3, dual Ethernet/Modbus serial. Active production. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"APM9B0CTLY6","Supply":"External supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm 500 V DC for 1 minute to earth","Marking":"CE","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","Data format":"8 bits, configurable odd, even or no parity for Modbus serial","Noise level":"69 dB conforming to 86/188/EEC","description":"LH/regen ATV900 control unit, APM, single drive, 500...690V","Maximum THDI":"<48 % full load conforming to IEC 61000-3-12","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Connector type":"RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial","Kit composition":"control unit graphical display terminal Digi-Link cable cable 24 V cable for voltage measurement","Safety function":"STO (safe torque off) SIL 3","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process Modular","Shock resistance":"7 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"APM","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Transmission rate":"10/100 Mbit/s for Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Physical interface":"2-wire RS 485 for Modbus serial","Transmission frame":"RTU for Modbus serial","Number of addresses":"1...247 for Modbus serial","Discrete input logic":"16 preset speeds","Frequency resolution":"Display unit: 0.1 Hz Analog input: 0.012/50 Hz","Type of polarization":"No impedance for Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Power dissipation in W":"Forced convection: 2980 W, switching frequency 2.5 kHz","IP degree of protection":"IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529","Product or component type":"Control module","[Us] rated supply voltage":"500...690 V","Communication port protocol":"Modbus serial Ethernet Modbus TCP","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-10...40 °C (without derating) 40...50 °C (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b0601bc93a02c825843a4e21781ab27b.pdf","sourceUrl":"https://www.se.com/th/en/product/APM9B0CTLY6/lh-regen-atv900-control-unit-apm-single-drive-500690v/"},"ai":{"faq":[{"question":"What supply voltages does APM9B0CTLY6 require?","answer":"The module needs three separate supplies: 24 V DC (19-30 V) for digital inputs, 24 V DC (21-27 V) for digital inputs and STO, and 10.5 V DC ±5 % for an external reference potentiometer (1-10 kΩ). Insulation test at 500 V DC, 1 MΩ minimum to earth."},{"question":"What communication protocols are available?","answer":"Ethernet/Modbus TCP at 10/100 Mbit/s (autonegotiation, half/full duplex) and Modbus serial RS-485 at 4.8-38.4 kbit/s, RTU framing, slave addresses 1-247."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APM9B0CTLY6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APM9B0CTLY6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}