{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"APMCA03LCY6RH","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"APMCA03LCY6RH","canonicalUrl":"https://aoctrl.com/schneider/APMCA03LCY6RH","factsUrl":"https://aoctrl.com/api/mcp/products/APMCA03LCY6RH","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process Modular APM, power filter, 690 V, 200 A, IP00, cabinet mount.","salesMarkdown":"The Schneider Electric APMCA03LCY6RH is a power filter in the Altivar Process Modular (APM) family, designed to sit between the supply and the drive for a cabinet-mounted installation. Heavy-duty rating drops to 163 A at the same voltages, 195 kVA. The integrated EMC filter meets category C3 for 300 m cable runs, which covers most industrial motor cable lengths without an external filter. ## Sizing and fit constraints At 1249 mm high, 269 mm wide, and 506 mm deep, this is a floor-standing cabinet section, not a DIN-rail component. The IP00 enclosure means it expects a clean, dry environment inside the cabinet — no hose-down, no dust ingress protection. Operating altitude is limited to 2000 m with derating above 1000 m; ambient temperature range is -10 to 40 °C without derating, 40 to 50 °C with a derating factor. Mounting is vertical only, integrated into the cabinet structure. ## Compliance and environment The part carries CE marking and complies with a full suite of IEC and UL standards: UL 61800-5-1, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. Pollution degree 2, vibration and shock resistance per IEC 60068-2-6 and 60068-2-27. Chemical and dust pollution resistance class 3C3 / 3S3 per IEC 60721-3-3. The EMC immunity profile includes level 3 for electrostatic discharge, radiated RF, and conducted RF, and level 4 for fast transients. Prospective line short-circuit current rating is 50 kA. Insulation resistance is > 1 MΩ at 500 V between supply and earth.","metaTitle":"Schneider APMCA03LCY6RH Power Filter, 690 V, 200 A, IP00","metaDescription":"Active-production Altivar Process Modular power filter. 690 V, 200 A line current, 239 kVA apparent power. IP00 cabinet mount. UL/IEC compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Depth":"506 mm","Width":"269 mm","title":"APMCA03LCY6RH","Height":"1249 mm","Marking":"CE","Standards":"UL 61800-5-1 IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated with 300 m category C3","description":"electronic filtering power supply, 690V, 200A, IP00, 3 phases","Line current":"200 A at 500 V (normal duty) 200 A at 690 V (normal duty) 163 A at 500 V (heavy duty) 163 A at 690 V (heavy duty)","Maximum THDI":"<48 % full load conforming to IEC 61000-3-12","Mounting mode":"Cabinet mount","Apparent power":"239 kVA normal duty 195 kVA heavy duty","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process Modular","Shock resistance":"4 gn for 11 ms conforming to IEC 60068-2-27","Device short name":"APM","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Operating altitude":"<= 2000 m with current derating above 1000m","Operating position":"Vertical integrated in cabinet","Prospective line Isc":"50 kA","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Insulation resistance":"> 1 MOhm at 500 V, between supply and earth terminals","IP degree of protection":"IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529","Network number of phases":"3 phases","Product or component type":"Power filter","[Us] rated supply voltage":"500...690 V - 10...10 %","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-10...40 °C (without derating) 40...50 °C (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3142c30e0ad10b480b157de9e830228b.pdf","sourceUrl":"https://www.se.com/nl/en/product/APMCA03LCY6RH/electronic-filtering-power-supply-690v-200a-ip00-3-phases/"},"ai":{"faq":[{"question":"What compliance documentation does this part carry?","answer":"CE marking, UL 61800-5-1, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. The EMC filter is integrated to category C3 for 300 m cable runs."},{"question":"What are the key electrical ratings for the APMCA03LCY6RH?","answer":"Line current 200 A at both 500 V and 690 V normal duty (163 A heavy duty). Apparent power 239 kVA normal duty, 195 kVA heavy duty. Supply voltage 500...690 V -10...10 %, three-phase. Prospective line short-circuit current 50 kA."},{"question":"What are the physical dimensions and mounting requirements?","answer":"Height 1249 mm, width 269 mm, depth 506 mm. Cabinet mount, vertical orientation only. IP00 protection. Ambient temperature -10 to 40 °C without derating, up to 50 °C with derating. Altitude up to 2000 m with derating above 1000 m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/APMCA03LCY6RH","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/APMCA03LCY6RH when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}