{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATH230D11S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATH230D11S6","canonicalUrl":"https://aoctrl.com/schneider/ATH230D11S6","factsUrl":"https://aoctrl.com/api/mcp/products/ATH230D11S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar HVAC ATH200 series, ATH230D11S6 variable speed drive, 11 kW / 15 hp, 525-600 V, 3-phase, cabinet mount, standard version.","salesMarkdown":"## Drive identity and power rating The ATH230D11S6 is a Schneider Altivar HVAC ATH200 series variable speed drive rated for 11 kW (15 hp) motor output. It accepts 525 V to 600 V three-phase input and delivers output voltage up to the supply level. Line current draw is 15.8 A at 525 V and 14.1 A at 600 V; apparent power is 14.7 kVA at 600 V. This fits HVAC pump, fan, and compressor loads in commercial building and light industrial applications. ## Safety integration and compliance Safety level is SIL 3 per IEC 61508 and PL e per ISO 13849-1, with integrated STO (safe torque off) on discrete inputs. Use this drive in safety circuits up to Cat 4 / PL e without an external safety relay for the stop function. Approvals include CULus, CE, UKCA, RCM, KC, EAC, and ATEX. The drive meets IEC 61800-5-1, IEC 61800-3 (environment 1 category C2 and environment 2 category C3), UL 508C, and IEC 61508. ## Cabinet fit and mounting Cabinet-mount design: 330 mm height, 180 mm width, 198 mm depth. Operating position is vertical ±10°. Allow 100 mm clearance above and below for airflow; noise level is 58 dB. Pollution degree 2 (normally non-conductive, occasional condensation). Altitude derating applies above 1000 m: reduce current 1 % per 100 m up to 3000 m. ## Communication and I/O options Includes a BACnet IP communication module (option card). The drive also supports Modbus serial and BACnet MS/TP via 2-wire RS-485, with configurable baud rates from 4800 bps to 76.8 kbit/s. Three analogue inputs (AI1 voltage 0-10 V, AI2 bipolar ±10 V, AI3 current 0-20 mA), six digital inputs (DI1-DI6 at 24 V DC), and two configurable relay outputs. DI5 can serve as a pulse input up to 30 kHz. ## Application-specific functions Built-in functions include fire mode (override for smoke extraction), run permissive, PID controller, additional PID, damper control, and underload detection for broken belt. These are configured via the drive's parameter set without extra hardware. Protection covers line supply phase loss, motor phase loss, overvoltage/undervoltage, overheating, overload (with PTC probes), short-circuit between motor phases, and earth faults. Output frequency range is 0.599 kHz.","metaTitle":"Schneider ATH230D11S6 Altivar HVAC Drive, 11 kW, 15 hp","metaDescription":"Schneider ATH230D11S6 Altivar HVAC drive, 11 kW / 15 hp, 525-600 V input, SIL 3 STO, BACnet IP option. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Depth":"198 mm","Width":"180 mm","title":"ATH230D11S6","Height":"330 mm","Marking":"CULus CE UKCA RCM KC EAC ATEX","Variant":"Standard version","Standards":"IEC 61800-5-1 IEC 61800-3 UL 508C IEC 61800-3 environment 1 category C2 IEC 61800-3 environments 2 category C3 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Without EMC filter","Data format":"8 bits, configurable odd, even or no parity 1or 2 stop","Noise level":"58 dB","Option card":"Communication module for BACnet IP","description":"Variable speed drive, Altivar HVAC ATH200, ATH230, 11kW, 15hp, 525 to 600V, 3 phase, IP20","Line current":"15.8 A at 525 V 14.1 A at 600 V","Safety level":"SIL 3 conforming to IEC 61508 PL = e conforming to ISO 13849-1","Mounting mode":"Cabinet mount","Apparent power":"14.7 kVA at 600 V","Connector type":"RJ45","Motor power hp":"15 hp","Motor power kW":"11 kW","Output voltage":"<= power supply voltage","Protection type":"Line supply phase loss: drive Motor phase loss: motor Line supply overvoltage and undervoltage: drive Overheating protection: drive Overload: motor With PTC probes: motor Short-circuit between motor phases: drive Overcurrent between output phases and earth: drive","Safety function":"STO (safe torque off)","lifecycle_stage":"current","Method of access":"Server Modbus serial Subordinate BACnet MS/TP","Output frequency":"0.599 kHz","Pollution degree":"2","Range of product":"Altivar HVAC ATH200","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATH230","Relative humidity":"5...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3","Relay output type":"Configurable relay logic R1A 1 NO electrical durability 100000 cycles Configurable relay logic R1B 1 NC electrical durability 100000 cycles Configurable relay logic R1C Configurable relay logic R2A 1 NO electrical durability 100000 cycles Configurable relay logic R2C","Transmission rate":"4800 bps, 9600 bps, 19200 bps, 38.4 Kbps 9.6, 19.2, 38.4, 76.8 kbit/s","Function available":"Fire mode Run permissive PID controller Additional PID Damper control Underload detection for broken belt","Operating altitude":"1000...3000 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Physical interface":"2-wire RS 485","Transmission frame":"RTU MS/TP","Analogue input type":"AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits","Discrete input type":"STO safe torque off, 24 V DC, impedance: 1.5 kOhm DI1...DI6 logic inputs, 24 V DC (30 V) DI5 programmable as pulse input: 0...30 kHz, 24 V DC (30 V)","Number of addresses":"0...247 0...127","Product destination":"Asynchronous motors Synchronous motors","Relay output number":"2","Switching frequency":"2...16 kHz adjustable 4...16 kHz with derating","Analogue output type":"Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits","Discrete input logic":"Positive logic (source) Negative logic (sink)","Discrete output type":"Open collector DQ+ 0...1 kHz 30 V DC 100 mA Open collector DQ- 0...1 kHz 30 V DC 100 mA","Overvoltage category":"III","Prospective line Isc":"22 kA","Type of polarization":"No impedance","Analogue input number":"3","Braking to standstill":"By DC injection","Discrete input number":"7","Volume of cooling air":"156 m3/h","Analogue output number":"1","Discrete output number":"1","Nominal Output Current":"17.0 A","Power dissipation in W":"267 W","IP degree of protection":"IP20","Motor slip compensation":"Automatic whatever the load Adjustable 0...300 % Not available in voltage/frequency ratio (2 or 5 points)","Brake chopper integrated":"True","Network number of phases":"3 phases","Maximum switching current":"Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC","Maximum transient current":"18.7 A","Minimum switching current":"Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC","Product or component type":"Variable speed drive","[Us] rated supply voltage":"525...600 V - 15...10 %","Communication port protocol":"Modbus serial BACnet MS/TP","Nominal Switching Frequency":"4 kHz","Product specific application":"HVAC","4 Quadrant Operation Possible":"True","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11","Ambient air transport temperature":"-25...70 °C","Synchronous motor control profile":"Vector control without sensor","Asynchronous motor control profile":"Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points","Acceleration and deceleration ramps":"Linear U S CUS Ramp switching Acceleration/deceleration ramp adaptation Acceleration/deceleration automatic stop with DC injection","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"-10...50 °C without derating 50...60 °C with derating factor","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3","Complementary/[Us] rated supply voltage":"24 V for DC","Relative symmetric mains voltage tolerance":"10 %","With safety function Safe torque off (STO)":"True","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/ATH230D11S6/variable-speed-drive-altivar-hvac-ath200-ath230-11kw-15hp-525-to-600v-3-phase-ip20/"},"ai":{"faq":[{"question":"What compliance documentation does the ATH230D11S6 carry?","answer":"The drive is marked CULus, CE, UKCA, RCM, KC, EAC, and ATEX. It complies with IEC 61800-5-1, IEC 61800-3, UL 508C, IEC 60721-3, IEC 61508, and ISO 13849-1."},{"question":"What is the closest alternative to the ATH230D11S6 in the Altivar HVAC family?","answer":"The ATH230D11S6 is a standard-version drive with a BACnet IP option card. Other ratings in the ATH200 series share the same cabinet-mount form factor and I/O architecture; the key difference is the power stage (11 kW vs other kW ratings). No direct pin-compatible alternative exists outside the series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATH230D11S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATH230D11S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}