{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATH630C11N4Z","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATH630C11N4Z","canonicalUrl":"https://aoctrl.com/schneider/ATH630C11N4Z","factsUrl":"https://aoctrl.com/api/mcp/products/ATH630C11N4Z","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar HVAC ATH600 series, ATH630C11N4Z AC drive, 150 hp normal duty / 125 hp heavy duty, 480 V, cabinet mount, 82 kg.","salesMarkdown":"## 150 hp VFD for HVAC fan and pump loads The Schneider Electric ATH630C11N4Z is an Altivar HVAC 630 drive rated 150 hp (110 kW) for normal duty and 125 hp (90 kW) for heavy duty, at 480 V input. Line current draws 201 A at 380 V normal duty and 165 A at 480 V normal duty; heavy duty pulls 170 A at 380 V and 143 A at 480 V. Built for variable-torque HVAC loads — fans, pumps, compressors — with a fire mode, forced fire mode, and scroll compressor management function built into the firmware. ## Safety and compliance package Integrated safe torque off (STO) rated SIL 3 per IEC 61508 and PL e per ISO 13849-1 — this covers the safety circuit requirement for a Category 3 / PL e stop function without an external safety relay. Carries CE, UKCA, CULus, EAC, RCM, ATEX, and KCC markings. Listed to UL 61800-5-1 and EN/IEC 61800-5-1 for the drive standard, plus IEC 61508 and ISO 13849-1 for functional safety. A Class C3 EMC filter is integrated — suitable for industrial environments with a dedicated earth connection; no external filter needed for most second-environment installations. ## Cabinet fit and field wiring Control wiring lands on open-style terminals plus one RJ45 for Modbus RTU / BACnet MS/TP. The external 24 V DC control supply (19...30 V) keeps the logic alive if the main power drops. Relay outputs: one changeover (R1) and two form-A (R2, R3), each rated 100,000 cycles. Digital inputs sample at 2 ms + 0.5 ms jitter — fast enough for most HVAC interlocks. Option card slots accept communication modules for BACnet IP, PROFINET, or Ethernet IP/Modbus TCP, plus digital/analog I/O and output relay extension cards.","metaTitle":"Schneider Electric ATH630C11N4Z Altivar HVAC Drive, 150 HP","metaDescription":"Schneider Electric ATH630C11N4Z Altivar HVAC 630 drive, 150 HP normal duty, 110 kW, 480 V, with integrated STO SIL 3. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"390 mm","Width":"316.6 mm","Height":"852 mm","Frequency":"50...60 Hz - 5...5 %","IP Rating":"IP00","Connector Type":"RJ45 and open style terminals","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Operating Position":"Vertical position","Temp Operating Max":"60 °C","Temp Operating Min":"-15 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATH630C11N4Z/variable-speed-drive-altivar-hvac-ath600-ath630-110kw-125hp-380-to-480v-3-phase-ip00/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATH630C11N4Z/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATH630C11N4Z","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATH630C11N4Z when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}