{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATH630U07N4Z","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATH630U07N4Z","canonicalUrl":"https://aoctrl.com/schneider/ATH630U07N4Z","factsUrl":"https://aoctrl.com/api/mcp/products/ATH630U07N4Z","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar HVAC ATH600, ATH630U07N4Z, 0.75 kW / 1 hp normal duty, 24 V DC control, integrated Class C2 EMC filter.","salesMarkdown":"The Schneider ATH630U07N4Z is an Altivar HVAC ATH600 drive rated for 0.75 kW normal duty (1 hp) and 0.37 kW heavy duty (0.5 hp) on 380–480 V three-phase input. Control circuit runs on 24 V DC external supply; internal 24 V DC bus powers the digital inputs and STO safety function. Integrated Class C2 EMC filter covers most European panel builds without an external filter. ## Safety and compliance STO (Safe Torque Off) is rated SIL 3 per IEC 61508 and PL e per ISO 13849-1, so it slots into a safety loop without an external contactor for the stop function. Markings include CE, UKCA, CULus, EAC, RCM, ATEX, and KCC; standards cover UL 61800-5-1, EN/IEC 61800-3, and IEC 61000-3-12. Pollution degree 2, cabinet mount only. ## Fieldbus and I/O Two-wire RS-485 port supports Modbus RTU and BACnet MS/TP at selectable baud rates up to 76.8 kbit/s. Option card slot accepts PROFINET, Ethernet IP/Modbus TCP, or BACnet IP modules. Listed as current production.","metaTitle":"Schneider ATH630U07N4Z Altivar HVAC Drive, 0.75 kW, 24 V DC","metaDescription":"Schneider ATH630U07N4Z Altivar HVAC ATH600 drive, 0.75 kW normal duty, 24 V DC control, integrated C2 EMC filter, STO SIL 3. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"158 mm","Width":"115 mm","Height":"196 mm","Current":"2.0 A at 380 V (normal duty) 1.6 A at 480 V (normal duty) 1.2 A at 380 V (heavy duty) 1 A at 480 V (heavy duty)","Frequency":"50...60 Hz - 5...5 %","IP Rating":"IP20","Horsepower":"1 hp for normal duty 0.5 hp for heavy duty","Data Format":"8 bits, configurable odd, even or no parity 8 bits, no parity, 1 stop","Connector Type":"RJ45 and open style terminals","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Operating Position":"Vertical position","Temp Operating Max":"60 °C","Temp Operating Min":"-15 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2bee65a676a5d4fb9c987747c853ccc6.pdf","sourceUrl":"https://www.se.com/th/en/product/ATH630U07N4Z/variable-speed-drive-altivar-hvac-ath600-ath630-0-75kw-1hp-380-to-480v-3-phase-ip20/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATH630U07N4Z/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATH630U07N4Z","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATH630U07N4Z when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}