{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATH630U15N4Z","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATH630U15N4Z","canonicalUrl":"https://aoctrl.com/schneider/ATH630U15N4Z","factsUrl":"https://aoctrl.com/api/mcp/products/ATH630U15N4Z","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar HVAC ATH600 series, ATH630U15N4Z, 1.5 kW normal duty / 0.75 kW heavy duty, 380-480 V, STO SIL 3, C2 EMC filter, cabinet mount.","salesMarkdown":"The Schneider Electric ATH630U15N4Z is a current-production Altivar HVAC drive from the ATH600 series, sized for a 1.5 kW motor at normal duty or 0.75 kW at heavy duty on a 380-480 V three-phase supply. It carries a Class C2 EMC filter integrated, STO safety function rated SIL 3 / PL e, and the usual HVAC-specific firmware — fire mode, PID, damper control, scroll compressor management. The normal-duty line current is 3.463 A at 380 V and 2.7 A at 480 V; heavy-duty drops to 2 A at 380 V and 1.7 A at 480 V. That 1.5 kW / 0.75 kW split is the key selection gate — if your motor is a constant-torque load (conveyor, positive-displacement pump), you size to the heavy-duty column; for variable-torque HVAC loads (fan, centrifugal pump), normal duty applies. The drive needs a 24 V DC external control supply (19...30 V) and provides internal 24 V for digital inputs and STO. Mounts in a cabinet, vertical position only, with derating above 1000 m altitude.","metaTitle":"Schneider ATH630U15N4Z Altivar HVAC Drive, 1.5 kW Normal Dut","metaDescription":"Schneider Electric ATH630U15N4Z Altivar HVAC drive, 1.5 kW normal duty / 0.75 kW heavy duty, 380-480 V, STO SIL 3, C2 EMC filter, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"158 mm","Width":"115 mm","Height":"196 mm","Frequency":"50...60 Hz - 5...5 %","IP Rating":"IP20","Connector Type":"RJ45 and open style terminals","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Operating Position":"Vertical position","Temp Operating Max":"60 °C","Temp Operating Min":"-15 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec5e6fd5d86f11defedb29b2177a3c05.pdf","sourceUrl":"https://www.se.com/ae/en/product/ATH630U15N4Z/variable-speed-drive-altivar-hvac-ath600-ath630-1-5kw-2hp-380-to-480v-3-phase-ip20/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATH630U15N4Z/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATH630U15N4Z","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATH630U15N4Z when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}