{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATS480D22Y","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATS480D22Y","canonicalUrl":"https://aoctrl.com/schneider/ATS480D22Y","factsUrl":"https://aoctrl.com/api/mcp/products/ATS480D22Y","rawCanonicalId":null},"summary":{"shortDescription":"Soft starter, Altistart 480, 22A, 208 to 690V AC, control supply 110 to 230V AC","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Phase":"3 phase","Marking":"CE CCC UKCA EAC RCM CULus","Category":"US1CP1G22588","Standards":"IEC 60947-4-2 UL 60947-4-2 IEC 60664-1","Option card":"Communication module Profibus DP V1 Communication module Modbus TCP/EtherNet/IP Communication module CANopen daisy chain Communication module CANopen Sub-D Communication module CANopen open style Communication module PROFINET","Apparent power":"0.06 kVA","Motor power kW":"5.5 kW 230 V in the motor supply line normal duty 4.0 kW 230 V in the motor supply line heavy duty 11.0 kW 400 V in the motor supply line normal duty 7.5 kW 400 V in the motor supply line heavy duty 11.0 kW 440 V in the motor supply line normal duty 7.5 kW 440 V in the motor supply line heavy duty 11.0 kW 500 V in the motor supply line normal duty 9.0 kW 500 V in the motor supply line heavy duty 11.0 kW 525 V in the motor supply line normal duty 9.0 kW 525 V in the motor supply line heavy duty 15.0 kW 660 V in the motor supply line normal duty 11.0 kW 660 V in the motor supply line heavy duty 18.5 kW 690 V in the motor supply line normal duty 15.0 kW 690 V in the motor supply line heavy duty 9.0 kW 230 V to the motor delta terminals normal duty 7.5 kW 230 V to the motor delta terminals heavy duty 18.5 kW 400 V to the motor delta terminals normal duty 15.0 kW 400 V to the motor delta terminals heavy duty","Protection type":"Phase failure line Integrated thermal protection motor Thermal protection starter Current overload motor Underload motor Excessive starting time, locked rotor motor Motor phase loss motor Line supply phase loss line Line supply phase loss motor Thermal protection motor","lifecycle_stage":"current","Range of Product":"Altivar Soft Starter ATS480","Device connection":"In the motor supply line To the motor delta terminals","Device short name":"ATS480","Relay output type":"Relay outputs R1A 1 NO Relay outputs R1B 1 NO Relay outputs RIC NO/NC programmable","Discrete input type":"STOP) logic inputs, 3500 Ohm RUN) logic inputs, 3500 Ohm DI3) programmable as logic input, 3500 Ohm DI4) programmable as logic input, 3500 Ohm","Input compatibility":"STOP discrete input level 1 PLC IEC 61131-2 RUN discrete input level 1 PLC IEC 61131-2 DI3 discrete input level 1 PLC IEC 61131-2 DI4 discrete input level 1 PLC IEC 61131-2","Product destination":"Asynchronous motors","Relay output number":"3","Discrete input logic":"Programmable digital input < 5 V","Discrete output type":"DQ1) programmable digital output DQ2) programmable digital output 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m","Utilisation category":"AC-3A AC-53A","Discrete input number":"4","Nbr. of units in pkg.":"1","Discrete output number":"2","Power Supply Frequency":"50...60 Hz - 20...20 %","IP Degree of Protection":"IP20","Ue power supply voltage":"208...690 V - 15...10 %","Maximum switching current":"Relay outputs 2 A 250 V AC Relay outputs 2 A 30 V DC","Minimum switching current":"100 mA 12 V DC relay outputs","Product or Component Type":"Soft starter","Maximum Horse Power Rating":"5.0 hp 208 V normal duty 3.0 hp 208 V heavy duty 7.5 hp 230 V normal duty 5.0 hp 230 V heavy duty 15.0 hp 460 V normal duty 10.0 hp 460 V heavy duty 20.0 hp 575 V normal duty 15.0 hp 575 V heavy duty","Rated Current In Heavy Duty":"17.0 A at 104 °F (40 °C) heavy duty","Product Specific Application":"Process and infrastructures","[Uc] control circuit voltage":"24 V DC","[Us] control circuit voltage":"110...230 V AC 50/60 Hz - 15...10 %","Motor Thermal Protection Class":"Class 10E","[Ie] rated operational current":"Normal duty 22.0 A 104 °F (40 °C))","Integrated motor overload protection":"True","Power loss static current independent":"25.0 W","[In] Rated current pwr loss specifctn":"22.0 A","current limiting %In (5 x Ie maximum)":"150...700 %","Power loss per device current dependent":"54.0 W","Maximum acceleration under shock load (during storage)":"100 m/s² at 11 ms","Maximum acceleration under shock load (during transport)":"100 m/s² at 11 ms","Maximum deflection under vibratory load (during storage)":"1.75 mm at 2...9 Hz","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum acceleration under vibratory load (during storage)":"15 m/s² at 200...500 Hz 10 m/s² at 9...200 Hz","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum deflection under vibratory load (during transport)":"1.75 mm at 2...9 Hz","Maximum acceleration under vibratory load (during transport)":"15 m/s² at 200...500 Hz 10 m/s² at 9...200 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ee2a67845230bf6458e4227014e95c0.pdf","sourceUrl":"https://www.se.com/us/en/product/ATS480D22Y/soft-starter-altistart-480-22a-208-to-690v-ac-control-supply-110-to-230v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATS480D22Y/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATS480D22Y","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATS480D22Y when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}