{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A10706666","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A10706666","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A10706666","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A10706666","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A10706666 medium-voltage AC drive, 895 kW motor power, 1070 kVA apparent power, 36-pulse diode rectifier, 2970...3630 V supply, floor-standing enclosure.","salesMarkdown":"The ATV1200A10706666 is a Schneider Altivar 1200 medium-voltage drive rated for 895 kW motor power at 1070 kVA apparent power, supplied from a 2970...3630 V three-phase input. That 1070 kVA figure tells you the transformer and upstream switchgear need to be sized for the full apparent power, not just the motor kW — the drive's 36-pulse diode front end draws 100 A line current at full load. The 36-pulse rectifier bridge is the key harmonic-mitigation feature: it cancels the 5th, 7th, 11th, and 13th harmonics at the input, so this drive typically meets IEEE 519 without an external filter. That saves floor space and avoids the insertion loss of a line reactor or multi-pulse transformer external to the drive. The overload profile is dual-rated: 1.2 In for 60 s (standard) or 1.5 In for 3 s (standard), and 1.5 In for 60 s or 1.85 In for 3 s under high-overload duty. The high-overload curve suits applications like crushers or extruders that need a short torque spike above rated current — the standard curve is enough for centrifugal pumps and fans. The drive ships as a floor-standing enclosure with separate air flows for the power section and control compartment. The kit includes: 2 x plinth, phase-shifting transformer, medium-voltage arrestors, cooling fans, human-machine interface, and 18 x power cells. That is the complete drive — no external line reactor or multi-pulse transformer to source separately. Dimensions depend on the efficiency variant: standard efficiency is 3360 mm wide × 1400 mm deep × 2520 mm high; high efficiency is 3660 mm wide × 1600 mm deep × 2670 mm high. The high-efficiency variant also moves 19,800 m³/h of cooling air versus 16,500 m³/h for standard — factor that into the room ventilation design. The main power connection uses M10 screw-type bar terminals accepting up to 6 x 40 mm² per phase, with cable entry from the bottom or top. Control supply is 220 V AC at 3 kVA, with an optional 220 V AC/DC control supply; the cooling fan runs on a separate 380 V AC supply. That separate fan supply means the drive can be powered down for maintenance while the cabinet ventilation stays live. ## Active production — sourcing and compliance Dielectric strength is 20 kV AC between earth and power terminals. Prospective line short-circuit current withstand is 31.5 kA for 150 ms — the upstream breaker must be coordinated to clear within that window to protect the drive's input diodes. Operating altitude derating applies above 1000 m: 0.6 % current derating per 100 m up to 2000 m. Pollution degree 2 per EN/IEC 61800-5-1 means the drive is rated for normal industrial atmospheres with only non-conductive dust — not for conductive粉尘 or heavy chemical exposure.","metaTitle":"Schneider ATV1200A10706666 AC Drive, 895 kW, 1070 kVA","metaDescription":"Schneider Electric ATV1200A10706666 Altivar 1200 medium-voltage drive. 895 kW motor power, 1070 kVA apparent power, 36-pulse input. CE marked, active","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1400 mm (standard efficiency) 1600 mm (high efficiency)","Width":"3660 mm (high efficiency) 3360 mm (standard efficiency)","title":"ATV1200A10706666","Height":"2520 mm standard efficiency 2670 mm high efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"36 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6.6 kV - 1070 kVA","Line current":"100 A","Apparent power":"1070 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"895 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 18 x power cells","Product destination":"Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"19800 m3/h (high efficiency) 16500 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP41 IP42 IP31","Network number of phases":"3 phases","Continuous output current":"94 A (standard overload) 75 A (high overload)","Maximum transient current":"112 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6.6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Vector control with sensor, optional Voltage/frequency ratio (V/f) Sensorless flux vector control Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"36 kW (standard efficiency) 31 kW (high efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency) 96.5 % (high efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A10706666/medium-voltage-variable-speed-drive-atv1200-6-6-kv-1070-kva/"},"ai":{"faq":[{"question":"What compliance documentation does Schneider Electric provide for ATV1200A10706666?","answer":"The drive carries CE marking and is designed to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. The integrated EMC filter covers conducted emissions for industrial second-environment installations. Standard documentation includes the EC Declaration of Conformity and the product manual with installation, commissioning, and maintenance sections."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A10706666","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A10706666 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}