{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A11301010","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A11301010","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A11301010","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A11301010","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 series, ATV1200A11301010 medium voltage variable speed drive, 945 kW motor power, 2970-3630 V supply, 48-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## Medium voltage drive with 48-pulse rectifier topology The ATV1200A11301010 is a Schneider Electric Altivar 1200 medium voltage variable speed drive rated for 945 kW motor power at a supply voltage of 2970...3630 V. The 48-pulse diode rectifier bridge input topology is the defining architecture here — it cancels the 5th, 7th, 11th, and 13th harmonics at the input without a separate active filter, keeping total harmonic distortion (THD) below 5% across the operating range. That means the upstream transformer and switchgear see near-sinusoidal current draw, which matters when the drive shares a feeder with other sensitive loads in a critical facility. ## Apparent power and line current for feeder coordination Apparent power is 1130 kVA with a line current of 65 A at the rated supply voltage. The prospective short-circuit current withstand is 31.5 kA for 150 ms — this sets the minimum SCCR rating for the upstream protective device and buswork. The 28 kV AC dielectric strength between earth and power terminals confirms the insulation coordination for a 3 kV class system; overvoltage category II per EN/IEC 61800-5-1 means the drive is intended for installation downstream of a transformer or distribution board, not at the service entrance. ## Overload capability and speed range for process duty The overload withstand profile gives two operating modes: standard overload at 1.2 In for 60 s or 1.5 In for 3 s, and high overload at 1.5 In for 60 s or 1.85 In for 3 s. The speed range is 20...100%, meaning the drive can regulate down to 20% base speed continuously without a speed feedback device — adequate for centrifugal pump and fan applications where the torque varies with the square of speed. For constant-torque loads like conveyors or extruders running below 20% speed, an encoder feedback option would be required to maintain torque accuracy, though the base unit is configured for sensorless vector control. ## Physical footprint and site integration The drive ships as a floor-standing enclosure measuring 4260 mm wide by 1600 mm deep by 2670 mm high (standard efficiency variant). The enclosure is grey (RAL 7032) with forced convection cooling requiring 23,100 m³/h of cooling air volume. The noise level is 80 dB — a room with multiple drives at this sound pressure will need acoustic treatment if operators occupy the space. Power connection uses M10 screw-type bars accepting up to 6 x 40 mm² cable per phase, entry from top or bottom. The operating position is vertical ±10 degrees. ## Control power and I/O complement Control power requires an external 220 V AC supply rated at 3 kVA; the cooling fan has a separate internal 380 V AC supply. An optional external 220 V AC/DC control supply is available. Galvanic isolation between power and control circuits means the control electronics reference is separate from the DC bus — this prevents ground loops when the drive communicates with a PLC or DCS over a long fieldbus run. The drive includes 4 software-configurable analogue inputs (0...20 mA / 4...20 mA, 250 Ohm impedance), 4 analogue outputs (same range), 6 discrete inputs (expandable to 10), and an integrated EMC filter. ## Environmental limits and derating Operating altitude is 1000...2000 m with a current derating of 0.6% per 100 m above 1000 m. Relative humidity range is 0...90% non-condensing, with an optional 0...95% range. Pollution degree 2 per EN/IEC 61800-5-1 means the drive is rated for a controlled environment where only non-conductive pollution occurs — no condensation or conductive dust. Vibration resistance is 4.9 m/s² from 10 to 50 Hz, adequate for floor-mounted installations in industrial buildings but not for direct machine mounting without vibration isolation.","metaTitle":"Schneider Electric ATV1200A11301010 Altivar 1200, 945 kW","metaDescription":"Schneider Electric ATV1200A11301010 Altivar 1200 medium voltage drive, 945 kW motor power, 2970-3630 V supply, 48-pulse rectifier, CE marked.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1600 mm (standard efficiency)","Width":"4260 mm (standard efficiency)","title":"ATV1200A11301010","Height":"2670 mm standard efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"48 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 10 kV - 1130 kVA","Line current":"65 A","Apparent power":"1130 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"945 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"28 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 24 x power cells","Product destination":"Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"23100 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP31 IP42 IP41","Network number of phases":"3 phases","Continuous output current":"65 A (standard overload) 52 A (high overload)","Maximum transient current":"78 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"10 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Sensorless flux vector control Voltage/frequency ratio (V/f) Vector control with sensor, optional Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"38 kW (standard efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A11301010/medium-voltage-variable-speed-drive-atv1200-10-kv-1130-kva/"},"ai":{"faq":[{"question":"What is ATV1200A11301010's motor power rating and supply voltage?","answer":"The drive is rated for 945 kW motor power with a supply voltage range of 2970...3630 V AC. The 48-pulse diode rectifier input cancels low-order harmonics without an external filter."},{"question":"What compliance documentation does ATV1200A11301010 carry?","answer":"The drive is CE marked and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. The enclosure rating and dielectric strength are per these standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A11301010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A11301010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}