{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A15606060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A15606060","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A15606060","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A15606060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 series, ATV1200A15606060 AC drive, 1304 kW motor power, 1560 kVA apparent power, 30-pulse diode rectifier, 2970-3630 V supply, floor-standing enclosure.","salesMarkdown":"## Active production — what that means for procurement The ATV1200A15606060: No stock-holding claim — quoted per BOM. ## 1304 kW motor drive — load profile and harmonic mitigation Rated for 1304 kW motor power at 1560 kVA apparent power, with a 30-pulse diode rectifier input stage. The 30-pulse topology cancels the 5th, 7th, 11th, 13th, 17th, and 19th harmonics at the input, keeping total harmonic distortion low enough to meet IEEE 519 without a separate active filter in most installations. Supply voltage range is 2970-3630 V — this is a medium-voltage drive, not a 480 V unit. The output voltage tracks the supply (≤ supply voltage), so motor winding insulation must be rated for the full DC bus potential. Line current draw is 150 A at rated load. ## Overload capability and cooling — sizing for the duty cycle Two overload profiles are available: standard overload allows 1.2× In for 60 seconds and 1.5× In for 3 seconds; high overload allows 1.5× In for 60 seconds and 1.85× In for 3 seconds. The high-overload setting is the one to use for heavy-start loads like crushers or extruders — standard overload is adequate for centrifugal pumps and fans. Cooling is forced convection with separate air flows for the transformer and power cells. The standard-efficiency configuration moves 29,900 m³/h of air; the high-efficiency version moves 33,200 m³/h. Ambient temperature and altitude derating apply — above 1000 m, derate current 0.6 % per 100 m. ## Physical footprint and installation constraints Floor-standing enclosure with separate air flows for the transformer and power cells. The standard-efficiency variant measures 3660 mm wide × 2820 mm high × 1500 mm deep; the high-efficiency variant is 3960 mm wide × 2820 mm high × 1600 mm deep. Operating position is vertical ±10 degrees — no side-mount or horizontal installation. ## Compliance and isolation — standards coverage CE marked, with compliance to EN/IEC 60204-11 (electrical equipment of machines), EN/IEC 60529 (enclosure protection), EN/IEC 61800-3 (EMC for drive systems), EN/IEC 61800-4 (drive performance), and EN/IEC 61800-5-1 (electrical safety). Pollution degree 2 per EN/IEC 61800-5-1 — suitable for controlled environments with non-conductive pollution. Electrical isolation between power and control circuits, with a dielectric strength of 20 kV AC between earth and power terminals. Overvoltage category II per EN/IEC 61800-5-1. Ground fault protection is integral to the drive.","metaTitle":"Schneider Electric ATV1200A15606060 AC Drive, 1304 kW","metaDescription":"Schneider Electric ATV1200A15606060 Altivar 1200 AC drive, 1304 kW motor power, 1560 kVA, 30-pulse rectifier, CE marked. Active production — quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"1600 mm (high efficiency) 1500 mm (standard efficiency)","Width":"3960 mm (high efficiency) 3660 mm (standard efficiency)","Height":"2820 mm standard efficiency 2820 mm high efficiency","Current":"150 A","IP Rating":"IP41 / IP42 / IP31","Input Type":"30 pulse diode rectifier bridge","Coil Voltage":"220 V","Product Status":"Active","Protection Type":"Ground fault protection: drive","Pollution Degree":"Pollution degree 2","Temp Storage Max":"60 °C","Temp Storage Min":"-10 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"50 °C","Temp Operating Min":"0 °C","Temperature Storage":"-10...60 °C","Ambient Air Temperature Operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A15606060/medium-voltage-variable-speed-drive-atv1200-6-kv-1560-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV1200A15606060/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A15606060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A15606060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}