{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A20001010","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A20001010","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A20001010","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A20001010","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A20001010 medium-voltage AC drive, 1672 kW motor power, 2000 kVA apparent power, 48-pulse diode rectifier, 2970-3630 V supply, floor-standing enclosure.","salesMarkdown":"## 1672 kW motor power — what it means for the load The ATV1200A20001010 is rated for 1672 kW motor output, which places it squarely in the medium-voltage drive class for large asynchronous motors — think mainline pumps, mine conveyors, or large fans where the motor frame size starts above 1 MW. Apparent power is 2000 kVA at the input, so the upstream transformer and switchgear need to be sized for that throughput, not just the motor nameplate. The supply voltage range is 2970-3630 V, meaning this drive connects to a 3.3 kV class MV bus — not a 480 V or 690 V distribution level. ## 48-pulse rectifier — harmonic management built in The 48-pulse diode rectifier bridge is the key harmonic-mitigation feature: it cancels the 5th, 7th, 11th, and 13th harmonics at the input, so the drive meets IEEE 519 without external filters on most installations. That rectifier topology drives the need for the phase-shifting transformer listed in the product composition — the transformer's secondary windings are phased to feed each 6-pulse group. The integrated EMC filter covers conducted emissions per EN/IEC 61800-3, which is the drive-specific EMC standard for adjustable-speed drives. ## Overload profiles and duty cycle Two overload profiles are available: standard overload handles 1.2× rated current for 60 seconds and 1.5× for 3 seconds; high overload handles 1.5× for 60 seconds and 1.85× for 3 seconds. The high-overload profile suits applications with heavy starting torque or intermittent overloads — crushers, extruders, or centrifuge drives where the peak demand exceeds the steady-state rating. ## Physical footprint and installation constraints Cooling is forced convection with 23100 m³/h airflow — the room HVAC must handle that heat rejection, and the intake/exhaust louvres need to be sized for the full air volume. The enclosure has separate air flows for the power cells and the control section, which keeps the electronics compartment cooler and reduces the dust ingress risk on the control board. ## Protection, isolation, and standards compliance Electrical isolation between power and control circuits is standard — the control supply can be fed from an external 220 V AC source (3 kVA) or an optional 220 V AC/DC supply, keeping the control electronics on a clean supply separate from the MV bus. Ground fault protection is integrated at the drive level, so a phase-to-ground fault inside the drive or motor cable is detected and cleared by the drive itself, not by the upstream feeder breaker. The drive is CE marked and complies with EN/IEC 60204-11 (safety of machinery), EN/IEC 60529 (ingress protection), EN/IEC 61800-3 (EMC for drives), EN/IEC 61800-4 (drive ratings), and EN/IEC 61800-5-1 (electrical safety). Dielectric strength is 28 kV AC between earth and power terminals — this is the insulation test voltage, not the operating voltage, and confirms the MV isolation design.","metaTitle":"Schneider ATV1200A20001010 AC Drive, 1672 kW, 2000 kVA","metaDescription":"Schneider Electric ATV1200A20001010 Altivar 1200 medium-voltage AC drive, 1672 kW motor power, 2000 kVA apparent power, 48-pulse rectifier, CE marked.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1700 mm (standard efficiency)","Width":"5160 mm (standard efficiency)","title":"ATV1200A20001010","Height":"2670 mm standard efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"48 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 10 kV - 2000 kVA","Line current":"135 A","Apparent power":"2000 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"1672 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"28 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 24 x power cells","Product destination":"Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"23100 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP31 IP42 IP41","Network number of phases":"3 phases","Continuous output current":"115 A (standard overload) 92 A (high overload)","Maximum transient current":"139 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"10 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Voltage/frequency ratio (V/f) Vector control with sensor, optional Sensorless flux vector control Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"67 kW (standard efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/uk/en/product/download-pdf/ATV1200A20001010?filename=Schneider+Electric_Altivar-1200_ATV1200A20001010.pdf', 'path_name': '215e44ec81700c8f580f4bb4603bf139.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/215e44ec81700c8f580f4bb4603bf139.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A20001010/medium-voltage-variable-speed-drive-atv1200-10-kv-2000-kva/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A20001010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A20001010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}