{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A20003333","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A20003333","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A20003333","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A20003333","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A20003333 medium-voltage AC drive, 1672 kW motor power, 2970-3630 V supply, 18-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"The ATV1200A20003333 is a medium-voltage AC drive rated for 1672 kW motor power with a supply voltage range of 2970-3630 V AC. This places it squarely in the MV drive class for large induction or synchronous motors — think mainline conveyors, mine hoists, large pumps, or compressor trains where a 480 V low-voltage drive would require impractical current levels. The 18-pulse diode rectifier input topology delivers significantly lower line current harmonics than a standard 6-pulse drive, often eliminating the need for external harmonic filters in medium-voltage installations. Line current is 410 A with an apparent power rating of 2000 kVA. Overload capability follows a dual profile: 1.2 x In for 60 seconds (standard) or 1.5 x In for 3 seconds, with a high-overload variant offering 1.5 x In for 60 seconds and 1.85 x In for 3 seconds. This matters when sizing for applications with intermittent peak loads — the 60-second window at 1.5x covers most starting and short-term overload events without oversizing the drive. ## Floor-standing construction and cooling demands This drive ships as a floor-standing enclosure with separate airflows for the transformer and power cells. Physical footprint is substantial: 1500 mm depth (standard efficiency) or 1700 mm (high efficiency), 4560 mm or 4860 mm width respectively, and 2670 mm height. Plan the installation bay accordingly — this is not a wall-mount unit. Forced convection cooling moves 19800 m³/h (standard efficiency) or 23100 m³/h (high efficiency) of air. The noise level is 80 dB — ear protection zones around the drive are expected in operation. Operating position is vertical within ±10 degrees. The product composition includes a phase-shifting transformer, 9 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. Power connections use M10 screw-type terminals accepting up to 6 x 40 mm² cable per phase, with entry from bottom or top. ## Compliance, isolation, and fault handling CE marked and designed to EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (adjustable speed drives), and EN/IEC 61800-5-1 (electrical safety). Pollution degree 2 per the safety standard, overvoltage category II. Electrical isolation between power and control circuits is provided. Dielectric strength is 10 kV AC between earth and power terminals. The drive withstands a prospective line fault current of 31.5 kA for 150 ms — this sets the upstream protection coordination requirements. Ground fault protection is integrated into the drive. Altitude derating applies above 1000 m: 0.6 % current reduction per 100 m up to 2000 m. Relative humidity range is 0-90 % standard, 0-95 % optional. Vibration resistance is 4.9 m/s² at 10-50 Hz. ## Control interfaces and I/O Four software-configurable analogue inputs accept 0-20 mA or 4-20 mA signals at 24 V max with 250 Ohm impedance. Two analogue outputs are similarly configurable. Discrete inputs number 6 standard, expandable to 10 optional. External control supply is 220 V AC at 3 kVA; an optional 220 V AC/DC supply is available. The internal cooling fan supply runs at 380 V AC. An integrated EMC filter is included.","metaTitle":"Schneider ATV1200A20003333 AC Drive, 1672 kW, 2970-3630 V","metaDescription":"Schneider Electric ATV1200A20003333 medium-voltage AC drive, 1672 kW motor power, 2970-3630 V input. 18-pulse rectifier, CE marked.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"1500 mm (standard efficiency) 1700 mm (high efficiency)","Width":"4560 mm (standard efficiency) 4860 mm (high efficiency)","Height":"2670 mm high efficiency 2670 mm standard efficiency","Current":"410 A","IP Rating":"IP41 / IP42 / IP31","Input Type":"18 pulse diode rectifier bridge","Coil Voltage":"220 V","Product Status":"Active","Protection Type":"Ground fault protection: drive","Pollution Degree":"Pollution degree 2","Temp Storage Max":"60 °C","Temp Storage Min":"-10 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"50 °C","Temp Operating Min":"0 °C","Temperature Storage":"-10...60 °C","Ambient Air Temperature Operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A20003333/medium-voltage-variable-speed-drive-atv1200-3-3-kv-2000-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV1200A20003333/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A20003333","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A20003333 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}