{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A26001010","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A26001010","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A26001010","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A26001010","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A26001010 medium-voltage AC drive, 2174 kW motor power, 2600 kVA apparent power, 48-pulse diode rectifier input, 2970…3630 V supply, floor-standing enclosure.","salesMarkdown":"The ATV1200A26001010 is rated for 2174 kW motor output at the shaft, with an apparent power of 2600 kVA. That apparent power figure drives the upstream transformer and cable sizing — the feeder must support 2600 kVA continuous, not just the motor nameplate kW. Input supply voltage range is 2970…3630 V, placing this drive squarely in the medium-voltage class (typically 3.3 kV nominal grids). The 48-pulse diode rectifier bridge reduces line-side harmonics below IEEE 519 thresholds without external filters — a key advantage for sites with sensitive co-located equipment or utility harmonic limits. Overload capability is specified as 1.2 × In for 60 s (standard duty) and 1.5 × In for 3 s, with a high-overload profile reaching 1.85 × In for 3 s. This lets the drive handle motor starting inrush and short-duration load spikes without tripping, but the 60 s window at 1.2 × In is the practical limit for continuous overload coordination with the upstream breaker. ## Floor-standing enclosure with separate air flows — physical integration constraints The drive ships in a floor-standing enclosure measuring 1500 mm deep, 6060 mm wide, and 2740 mm high. That footprint demands a dedicated electrical room with a reinforced floor — the width alone exceeds a standard shipping container's internal width, so site access and rigging must be planned before delivery. Cooling is forced convection with separate air flows — the enclosure is designed to draw cooling air from the room and exhaust it separately, so the heat load (43,200 m³/h airflow,) must be factored into the room's HVAC capacity. Operating altitude derating starts at 1000 m, with 0.6 % current reduction per 100 m above that. The product composition includes a phase-shifting transformer, 24 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. The transformer is the heaviest single component — verify floor loading before positioning. ## Compliance and lifecycle — current production, CE marked Lifecycle status is listed as current production. The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. These cover electrical safety, EMC, enclosure protection, and adjustable-speed drive performance standards. Dielectric strength is 28 kV AC between earth and power terminals, and the prospective line short-circuit current withstand is 31.5 kA for 150 ms. That SCCR rating means the drive can withstand a bolted fault on its input bus for up to 150 ms without catastrophic failure — coordination with the upstream breaker must clear the fault within that window.","metaTitle":"Schneider Electric ATV1200A26001010 AC Drive, 2174 kW","metaDescription":"Schneider Electric ATV1200A26001010 medium-voltage VFD, 2174 kW motor power, 2600 kVA apparent power, 48-pulse input, CE marked, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1500 mm (standard efficiency)","Width":"6060 mm (standard efficiency)","title":"ATV1200A26001010","Height":"2740 mm standard efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"48 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 10 kV - 2600 kVA","Line current":"150 A","Apparent power":"2600 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"2174 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"28 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 24 x power cells","Product destination":"Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"43200 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP42 IP41 IP31","Network number of phases":"3 phases","Continuous output current":"150 A (standard overload) 120 A (high overload)","Maximum transient current":"180 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"10 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Closed-loop control with encoder Voltage/frequency ratio (V/f)","Asynchronous motor control profile":"Vector control with sensor, optional Sensorless flux vector control Voltage/frequency ratio (V/f) Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"87 kW (standard efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A26001010?filename=Schneider+Electric_Altivar-1200_ATV1200A26001010.pdf', 'path_name': '70a00ed49838e8ddddf3517587c406e5.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/70a00ed49838e8ddddf3517587c406e5.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A26001010/medium-voltage-variable-speed-drive-atv1200-10-kv-2600-kva/"},"ai":{"faq":[{"question":"How can I order ATV1200A26001010 or check availability?","answer":"This drive is quoted to order against the BOM quantity through independent distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A26001010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A26001010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}