{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A26001010","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A26001010","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A26001010","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A26001010","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A26001010 medium-voltage AC drive, 2174 kW motor power, 2600 kVA apparent power, 48-pulse diode rectifier input, 2970…3630 V supply, floor-standing enclosure.","salesMarkdown":"The ATV1200A26001010 is rated for 2174 kW motor output at the shaft, with an apparent power of 2600 kVA. That apparent power figure drives the upstream transformer and cable sizing — the feeder must support 2600 kVA continuous, not just the motor nameplate kW. Input supply voltage range is 2970…3630 V, placing this drive squarely in the medium-voltage class (typically 3.3 kV nominal grids). The 48-pulse diode rectifier bridge reduces line-side harmonics below IEEE 519 thresholds without external filters — a key advantage for sites with sensitive co-located equipment or utility harmonic limits. Overload capability is specified as 1.2 × In for 60 s (standard duty) and 1.5 × In for 3 s, with a high-overload profile reaching 1.85 × In for 3 s. This lets the drive handle motor starting inrush and short-duration load spikes without tripping, but the 60 s window at 1.2 × In is the practical limit for continuous overload coordination with the upstream breaker. ## Floor-standing enclosure with separate air flows — physical integration constraints The drive ships in a floor-standing enclosure measuring 1500 mm deep, 6060 mm wide, and 2740 mm high. That footprint demands a dedicated electrical room with a reinforced floor — the width alone exceeds a standard shipping container's internal width, so site access and rigging must be planned before delivery. Cooling is forced convection with separate air flows — the enclosure is designed to draw cooling air from the room and exhaust it separately, so the heat load (43,200 m³/h airflow,) must be factored into the room's HVAC capacity. Operating altitude derating starts at 1000 m, with 0.6 % current reduction per 100 m above that. The product composition includes a phase-shifting transformer, 24 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. The transformer is the heaviest single component — verify floor loading before positioning. ## Compliance and lifecycle — current production, CE marked Lifecycle status is listed as current production. The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. These cover electrical safety, EMC, enclosure protection, and adjustable-speed drive performance standards. Dielectric strength is 28 kV AC between earth and power terminals, and the prospective line short-circuit current withstand is 31.5 kA for 150 ms. That SCCR rating means the drive can withstand a bolted fault on its input bus for up to 150 ms without catastrophic failure — coordination with the upstream breaker must clear the fault within that window.","metaTitle":"Schneider Electric ATV1200A26001010 AC Drive, 2174 kW","metaDescription":"Schneider Electric ATV1200A26001010 medium-voltage VFD, 2174 kW motor power, 2600 kVA apparent power, 48-pulse input, CE marked, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"1500 mm (standard efficiency)","Width":"6060 mm (standard efficiency)","Height":"2740 mm standard efficiency","Current":"150 A","IP Rating":"IP42 / IP41 / IP31","Input Type":"48 pulse diode rectifier bridge","Coil Voltage":"220 V","Product Status":"Active","Protection Type":"Ground fault protection: drive","Pollution Degree":"Pollution degree 2","Temp Storage Max":"60 °C","Temp Storage Min":"-10 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"50 °C","Temp Operating Min":"0 °C","Temperature Storage":"-10...60 °C","Ambient Air Temperature Operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A26001010/medium-voltage-variable-speed-drive-atv1200-10-kv-2600-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV1200A26001010/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A26001010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A26001010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}