{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A31306060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A31306060","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A31306060","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A31306060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A31306060 medium-voltage AC drive, 2617 kW motor power, 3130 kVA apparent power, 30-pulse diode rectifier, 2970...3630 V supply, floor-standing enclosure.","salesMarkdown":"## What the 30-pulse input and 3.3 kV rail mean for the installation The ATV1200A31306060: The 30-pulse diode rectifier bridge is the key harmonic-mitigation feature — it effectively cancels the 5th, 7th, 11th, and 13th harmonics at the input, so the drive meets IEEE 519 without a separate filter bank. The supply voltage limits are 2970...3630 V, which covers the nominal 3.3 kV class with margin for typical utility swings. At 3130 kVA apparent power and 2617 kW motor power, this is a medium-voltage drive sized for large induction or synchronous motors — think mainline conveyors, mill drives, or large pumps in mining and water. ## Overload profile and fault-withstand capability Standard overload rating is 1.2 × In for 60 s and 1.5 × In for 3 s; the high-overload profile pushes to 1.5 × In for 60 s and 1.85 × In for 3 s. That high-overload envelope suits applications with heavy starting duty or short-duration peak loads — crushers, extruders, or centrifuge starts. The prospective line short-circuit current is 31.5 kA for 150 ms, which means the drive's input section can ride through a fault on the primary distribution bus without collapsing the DC bus or damaging the rectifier bridge. Dielectric strength between earth and power terminals is 20 kV AC — a safety margin that reflects the medium-voltage isolation requirements. ## Physical footprint and cooling — what ships in the enclosure The drive ships as a floor-standing enclosure with separate air flows for the power cells and the transformer section. Standard-efficiency configuration: 5770 mm wide × 2670 mm high × 1600 mm deep; high-efficiency variant adds width to 6070 mm and depth to 1700 mm. The product composition includes the phase-shifting transformer, 15 power cells, medium-voltage arrestors, cooling fans, and the HMI. Cooling is forced convection at 29,700 m³/h for both efficiency grades. Noise level is 80 dB — plan for hearing protection zones around the drive room. ## Compliance and standards package CE marked. Designed to EN/IEC 61800-3 (EMC environment), EN/IEC 61800-4 (voltage sag immunity), EN/IEC 61800-5-1 (electrical safety), EN/IEC 60204-11 (semiconductor converter equipment), and EN/IEC 60529 (enclosure ingress protection). Pollution degree 2 per EN/IEC 61800-5-1. Overvoltage category II. The integrated EMC filter covers conducted emissions for the drive's rated power — no external filter needed for most industrial installations.","metaTitle":"Schneider ATV1200A31306060 AC Drive, 2617 kW, 3130 kVA","metaDescription":"Schneider Electric ATV1200A31306060 Altivar 1200 medium-voltage VFD. 2617 kW motor power, 3130 kVA apparent power, 30-pulse input.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1700 mm (high efficiency) 1600 mm (standard efficiency)","Width":"5770 mm (standard efficiency) 6070 mm (high efficiency)","title":"ATV1200A31306060","Height":"2670 mm high efficiency 2670 mm standard efficiency 2670 mm","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"30 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6 kV - 3130 kVA","Line current":"320 A","Apparent power":"3130 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"2617 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 15 x power cells","Product destination":"Asynchronous motors Synchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"29700 m3/h (standard efficiency) 29700 m3/h (high efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP31 IP41 IP42","Network number of phases":"3 phases","Continuous output current":"301 A (standard overload) 241 A (high overload)","Maximum transient current":"361 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Voltage/frequency ratio (V/f) Sensorless flux vector control Closed-loop control with encoder Vector control with sensor, optional","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"105 kW (standard efficiency) 92 kW (high efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency) 96.5 % (high efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/uk/en/product/download-pdf/ATV1200A31306060?filename=Schneider+Electric_Altivar-1200_ATV1200A31306060.pdf', 'path_name': 'c6a12bee51724d151ab34ee11281c240.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/c6a12bee51724d151ab34ee11281c240.pdf', 'status': 1}","sourceUrl":"https://www.se.com/uk/en/product/ATV1200A31306060/medium-voltage-variable-speed-drive-atv1200-6-kv-3130-kva/"},"ai":{"faq":[{"question":"What compliance documentation ships with the ATV1200A31306060?","answer":"The drive is CE marked and designed to EN/IEC 61800-3, 61800-4, 61800-5-1, 60204-11, and 60529. The integrated EMC filter covers conducted emissions. Documentation includes the EC Declaration of Conformity and the product manual covering installation, commissioning, and maintenance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A31306060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A31306060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}