{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A39406666","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A39406666","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A39406666","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A39406666","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A39406666, medium-voltage variable speed drive, 3294 kW, 3.3 kV, 36-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"The ATV1200A39406666 is a medium-voltage drive rated for 3294 kW motor power at a supply voltage of 2970...3630 V — this is not a 400 V or 690 V unit; it lands in the 3.3 kV class, requiring MV switchgear and transformer coordination upstream. The 36-pulse diode rectifier input delivers low line-current harmonics without an active front end — the line current draws 410 A at an apparent power of 3940 kVA. The prospective short-circuit current withstand is 31.5 kA for 150 ms, which sets the upstream fuse or breaker rating. Overload capability is defined in two profiles: standard overload handles 1.2 In for 60 s and 1.5 In for 3 s; high overload handles 1.5 In for 60 s and 1.85 In for 3 s. This dictates the motor duty cycle the drive can support without tripping. ## Physical footprint and installation constraints The drive ships in a floor-standing enclosure with separate air flows for power and control sections. Dimensions: 1700 mm deep, 6670 mm wide, and either 2670 mm (standard efficiency) or 2970 mm (high efficiency) tall. Cooling is forced convection requiring 33,000 m³/h of cooling air. The operating position is vertical ±10°. Ambient conditions: pollution degree 2 per EN/IEC 61800-5-1, relative humidity 0–90% (0–95% optional), and altitude derating of 0.6% per 100 m above 1000 m. Power connection uses bar-type screw terminals M10, clamping 6 x 40 mm² per phase, with cable entry from top or bottom. The dielectric strength between earth and power terminals is 20 kV AC. ## Compliance and standards coverage CE marked, with design compliance to EN/IEC 60204-11 (safety of machinery), EN/IEC 60529 (enclosure protection), EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (harmonics), and EN/IEC 61800-5-1 (electrical safety). An integrated EMC filter and electrical isolation between power and control reduce external filtering requirements. The drive includes ground fault protection and overvoltage category II per the same standard. ## Sourcing — active production, quoted to order Sourced through authorized distribution channels. Pricing and lead time are confirmed at RFQ against the BOM quantity — no stock-holding claim on a unit of this size and value.","metaTitle":"Schneider Electric ATV1200A39406666 Altivar 1200, 3294 kW","metaDescription":"Schneider Electric ATV1200A39406666 medium-voltage drive, 3294 kW motor power, 36-pulse rectifier, integrated EMC filter.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1700 mm (high efficiency) 1700 mm (standard efficiency)","Width":"6670 mm (standard efficiency) 6670 mm (high efficiency)","title":"ATV1200A39406666","Height":"2670 mm standard efficiency 2970 mm high efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"36 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6.6 kV - 3940 kVA","Line current":"410 A","Apparent power":"3940 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"3294 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 18 x power cells","Product destination":"Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"33000 m3/h (standard efficiency) 33000 m3/h (high efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP31 IP41 IP42","Network number of phases":"3 phases","Continuous output current":"345 A (standard overload) 276 A (high overload)","Maximum transient current":"414 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6.6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Vector control with sensor, optional Sensorless flux vector control Voltage/frequency ratio (V/f) Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"132 kW (standard efficiency) 115 kW (high efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency) 96.5 % (high efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A39406666?filename=Schneider+Electric_Altivar-1200_ATV1200A39406666.pdf', 'path_name': '8f52f112724249bc8f243fd46c53346b.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/8f52f112724249bc8f243fd46c53346b.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A39406666/medium-voltage-variable-speed-drive-atv1200-6-6-kv-3940-kva/"},"ai":{"faq":[{"question":"What is the motor power rating of the ATV1200A39406666?","answer":"The drive is rated for 3294 kW motor power at a supply voltage of 2970...3630 V. This is a medium-voltage drive, not a low-voltage unit."},{"question":"What compliance documentation does the ATV1200A39406666 carry?","answer":"CE marked, designed to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Includes integrated EMC filter and electrical isolation between power and control."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A39406666","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A39406666 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}