{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A52505555","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A52505555","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A52505555","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A52505555","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A52505555 medium-voltage AC drive, 4389 kW motor power, 2970...3630 V supply, 5250 kVA apparent power, 30-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## Medium-voltage drive for synchronous and asynchronous motors The Schneider Electric ATV1200A52505555 is a medium-voltage AC drive from the Altivar 1200 series, rated for 4389 kW motor power with a supply voltage range of 2970...3630 V and an apparent power of 5250 kVA. It drives both synchronous and asynchronous motors, making it a fit for large pump, fan, compressor, and conveyor applications in heavy industry. The input stage uses a 30-pulse diode rectifier bridge, which significantly reduces line-side harmonics compared to 6- or 12-pulse topologies — a key consideration for installations where IEEE 519 compliance is required without external filters. The drive is assembled in a floor-standing enclosure with separate air flows for power and control sections, rated for forced convection cooling moving 80000 m³/h at standard efficiency. The enclosure measures 3040 mm high by 7770 mm wide by 1800 mm deep — this is a large-format installation that needs a dedicated equipment room or pad. ## Overload profile and protection coordination The overload withstand capability is defined for two duty classes: standard overload allows 1.2× In for 60 s and 1.5× In for 3 s; high overload allows 1.5× In for 60 s and 1.85× In for 3 s. This dual profile lets the drive handle starting surges and short-term process overloads without oversizing the drive for the continuous load. Ground fault protection is built into the drive, and the dielectric strength between earth and power terminals is 20 kV AC. The prospective line short-circuit current rating is 31.5 kA for 150 ms — this sets the upstream breaker and fuse coordination requirements. The drive is designed for pollution degree 2 environments per EN/IEC 61800-5-1, and the overvoltage category is II. Operating altitude derating starts at 1000 m with a 0.6 % reduction per 100 m above that, which matters for installations at higher elevations. ## Control supply and I/O configuration The control section requires an external supply at 220 V AC, 3 kVA, with an optional 220 V AC/DC supply. The cooling fan has its own internal 380 V AC supply, with an optional external 380 V AC feed. Electrical isolation is maintained between power and control circuits. The drive includes 4 software-configurable analogue inputs (0...20 mA / 4...20 mA, 24 V max, 250 Ω impedance) and 2 analogue outputs with the same current ranges. Discrete inputs are 6 standard, expandable to 10 with an option. The I/O complement is sufficient for basic speed reference, feedback, and run/stop control without an external PLC for simple applications. ## Standards compliance and lifecycle status The ATV1200A52505555 carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. An integrated EMC filter is included. The noise level is rated at 80 dB — hearing protection is required within the equipment perimeter.","metaTitle":"Schneider ATV1200A52505555 AC Drive, 4389 kW, 2970-3630 V","metaDescription":"Schneider Electric Altivar 1200 medium-voltage VFD, 4389 kW motor power, 30-pulse input, 5250 kVA. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1800 mm (standard efficiency)","Width":"7770 mm (standard efficiency)","title":"ATV1200A52505555","Height":"3040 mm standard efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"30 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 5.5 kV - 5250 kVA","Line current":"550 A","Apparent power":"5250 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"4389 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 15 x power cells","Product destination":"Synchronous motors Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"80000 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP42 IP41 IP31","Network number of phases":"3 phases","Continuous output current":"550 A (standard overload) 440 A (high overload)","Maximum transient current":"661 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"5.5 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Closed-loop control with encoder Voltage/frequency ratio (V/f)","Asynchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder Sensorless flux vector control Vector control with sensor, optional","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"167 kW (standard efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A52505555?filename=Schneider+Electric_Altivar-1200_ATV1200A52505555.pdf', 'path_name': '26b5b3c81129c67fede00b33b82b4e1f.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/26b5b3c81129c67fede00b33b82b4e1f.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A52505555/medium-voltage-variable-speed-drive-atv1200-5-5-kv-5250-kva/"},"ai":{"faq":[{"question":"What is the motor power rating for the ATV1200A52505555?","answer":"The drive is rated for 4389 kW motor power with an apparent power of 5250 kVA. It can drive both synchronous and asynchronous motors."},{"question":"What input voltage does the ATV1200A52505555 require?","answer":"The supply voltage limits are 2970...3630 V AC. The input stage is a 30-pulse diode rectifier bridge, which reduces line harmonics."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A52505555","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A52505555 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}