{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A57206060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A57206060","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A57206060","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A57206060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A57206060 medium-voltage AC drive, 4782 kW motor power, 2970-3630 V supply, 30-pulse rectifier, floor-standing enclosure.","salesMarkdown":"## What a 4.8 MW drive means on the mill floor The ATV1200A57206060 is a medium-voltage AC drive rated for 4782 kW motor power, supplied from a 2970–3630 V line through a 30-pulse diode rectifier bridge. That 30-pulse front end keeps input harmonics low enough to skip a dedicated harmonic filter on most mill buses — the transformer secondary windings handle the phase shifting. The drive is designed for synchronous and asynchronous motors, so it covers both the main mill stand drives and the larger wound-rotor or PM motors in the line. Overload capability is specified in four bands: 1.2 × In for 60 s and 1.5 × In for 3 s under standard overload, plus 1.5 × In for 60 s and 1.85 × In for 3 s under high overload. On a hot-strip mill where the cobble catch can spike the torque demand for a few seconds, the 1.85 × In / 3 s window is the one that keeps the drive from tripping on a transient overload that the upstream breaker would see as a fault. ## Physical footprint and integration constraints The drive ships as a floor-standing enclosure with separate air flows for the power cells and the control section. Overall dimensions are 3040 mm high × 7770 mm wide × 1800 mm deep. That width is the limiting dimension for most plant-floor layouts — you need a bay wide enough to swing the doors fully open for cell access. The enclosure colour is grey RAL 7032. Cooling is forced convection, moving 80,000 m³/h of air at standard efficiency. That volume drives the HVAC and ducting design — the room's air-handling system must supply clean, filtered air at that rate, or the drive derates. Operating altitude is 1000–2000 m with a 0.6 % current derating per 100 m above 1000 m. Noise level at full load is 80 dB. Power connections are bar-type terminals, M10 screws, clamping capacity 6 × 40 mm² per phase, with cable entry from the bottom or top. The input line prospective short-circuit current rating is 31.5 kA for 150 ms — this sets the upstream breaker's let-through requirement for fault coordination. ## Standards, isolation, and environmental ratings The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1 (safety). Electrical isolation is maintained between power and control circuits. The integrated EMC filter covers the conducted emission limits for the second environment (industrial) per EN/IEC 61800-3. Pollution degree is 2 per EN/IEC 61800-5-1, overvoltage category II. Dielectric strength between earth and power terminals is 20 kV AC. Operating position is vertical ±10°, relative humidity 0–90 % (0–95 % optional). Vibration resistance is 4.9 m/s² from 10–50 Hz. ## Control I/O and auxiliary supplies The drive includes 4 software-configurable analogue inputs (0–20 mA / 4–20 mA, 24 V max, 250 Ω impedance) and 2 analogue outputs (same current ranges, 250 Ω). Discrete inputs are 6 standard, expandable to 10. The control section requires an external 220 V AC supply at 3 kVA; the cooling fans run on 380 V AC. An optional external 220 V AC/DC control supply is available. The product composition includes two plinths, a phase-shifting transformer, medium-voltage arrestors, cooling fans, a human-machine interface, and 15 power cells. The HMI is the primary commissioning interface — all I/O mapping, motor data entry, and parameter tuning happen through it.","metaTitle":"Schneider Electric ATV1200A57206060 AC Drive, 4782 kW","metaDescription":"Schneider Electric ATV1200A57206060 medium-voltage AC drive, 4782 kW motor power, 30-pulse input, CE marked, floor-standing. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1800 mm (standard efficiency)","Width":"7770 mm (standard efficiency)","title":"ATV1200A57206060","Height":"3040 mm standard efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"30 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6 kV - 5720 kVA","Line current":"550 A","Apparent power":"5720 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"4782 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 15 x power cells","Product destination":"Asynchronous motors Synchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"80000 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP41 IP31 IP42","Network number of phases":"3 phases","Continuous output current":"550 A (standard overload) 440 A (high overload)","Maximum transient current":"661 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Closed-loop control with encoder Vector control with sensor, optional Voltage/frequency ratio (V/f) Sensorless flux vector control","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"182 kW (standard efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A57206060?filename=Schneider+Electric_Altivar-1200_ATV1200A57206060.pdf', 'path_name': 'f3033f45297a315874950119e4144bf8.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/f3033f45297a315874950119e4144bf8.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A57206060/medium-voltage-variable-speed-drive-atv1200-6-kv-5720-kva/"},"ai":{"faq":[{"question":"How can I order ATV1200A57206060 or check availability?","answer":"This drive is quoted to order against the BOM quantity. Submit an RFQ with your target quantity and delivery window."},{"question":"What are the key electrical ratings of ATV1200A57206060?","answer":"Motor power is 4782 kW, supply voltage range is 2970–3630 V, input type is a 30-pulse diode rectifier, line current is 550 A, and apparent power is 5720 kVA. Overload capability includes 1.85 × In for 3 s under high overload."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A57206060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A57206060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}