{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A6706060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A6706060","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A6706060","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A6706060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A6706060 medium-voltage AC drive, 560 kW, 2970-3630 V supply, 30-pulse input, 670 kVA, floor-standing enclosure.","salesMarkdown":"## Medium-voltage drive for 560 kW motor loads The Schneider Electric ATV1200A6706060 is a medium-voltage AC drive from the Altivar 1200 series, rated for 560 kW motor power with a supply voltage range of 2970 to 3630 V. This places it squarely in the medium-voltage drive class — not a 480 V unit — so the incoming supply and switchgear must match that voltage band. The 30-pulse diode rectifier bridge input inherently mitigates line-side harmonics below IEEE 519 thresholds without external filters — a real advantage when the plant power system has capacitor banks or sensitive loads on the same bus. Apparent power rating is 670 kVA, which sets the transformer and upstream breaker sizing. The prospective line Isc withstand is 31.5 kA for 150 ms — the upstream protection must coordinate to clear within that window. ## Overload profile and duty selection Two overload profiles are available: standard overload handles 1.2× In for 60 s and 1.5× In for 3 s; high overload handles 1.5× In for 60 s and 1.85× In for 3 s. The high-overload curve suits applications with heavy starting or intermittent peak loads — crushers, centrifuge drives, or extruders where the motor pulls above nameplate during the process cycle. The drive supports both asynchronous and synchronous motors, so it can run a PM motor retrofit or a standard induction machine from the same unit — useful when the driven equipment changes over the plant life. Speed range is listed as 20 to 100, likely a percentage of base speed — the lower bound of 20 % means the drive can regulate down to one-fifth of rated motor speed without instability, typical for fan and pump turndown. ## Enclosure, cooling, and site prep The drive ships in a floor-standing enclosure with separate air flows for power and control sections. Dimensions vary by efficiency option: standard efficiency measures 2860 mm wide × 1400 mm deep × 2590 mm high; high efficiency adds width to 3160 mm and height to 2740 mm, depth to 1500 mm. The footprint difference matters when the drive room has fixed column spacing or a door swing arc. Cooling is forced convection requiring 16,600 m³/h for standard efficiency and 19,900 m³/h for high efficiency. The HVAC system in the drive room must handle this exhaust volume plus the heat rejection — undersized ventilation is a common commissioning delay. Acoustic noise is 80 dB — hearing protection zones and enclosure acoustic treatment should be planned for the drive room layout. ## Standards compliance and isolation The drive carries CE marking and complies with EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (adjustable speed drives), and EN/IEC 61800-5-1 (electrical safety). Pollution degree 2 per EN/IEC 61800-5-1 means it is rated for normal industrial environments with only non-conductive contamination — not for conductive dust or chemical spray. Electrical isolation between power and control is standard for medium-voltage drives — the control electronics ride on a separate ground reference, so the 24 V I/O loop does not share a fault path with the 3.3 kV power section. Dielectric strength is 20 kV AC between earth and power terminals — this is the hipot test voltage, not the operating voltage, and confirms the insulation system can withstand switching transients on the medium-voltage bus. The 30-pulse topology and medium-voltage rating limit direct drop-in alternatives — no pin-compatible second source exists in the same footprint.","metaTitle":"Schneider ATV1200A6706060 AC Drive, 560 kW, 2970-3630 V","metaDescription":"Schneider Electric ATV1200A6706060 medium-voltage VFD, 560 kW, 30-pulse input, 670 kVA. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1400 mm (standard efficiency) 1500 mm (high efficiency)","Width":"2860 mm (standard efficiency) 3160 mm (high efficiency)","title":"ATV1200A6706060","Height":"2590 mm standard efficiency 2740 mm high efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"30 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6 kV - 670 kVA","Line current":"65 A","Apparent power":"670 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"560 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 15 x power cells","Product destination":"Asynchronous motors Synchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"16600 m3/h (standard efficiency) 19900 m3/h (high efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP31 IP42 IP41","Network number of phases":"3 phases","Continuous output current":"65 A (standard overload) 52 A (high overload)","Maximum transient current":"78 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Closed-loop control with encoder Voltage/frequency ratio (V/f)","Asynchronous motor control profile":"Vector control with sensor, optional Voltage/frequency ratio (V/f) Closed-loop control with encoder Sensorless flux vector control","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"22 kW (standard efficiency) 20 kW (high efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency) 96.5 % (high efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A6706060?filename=Schneider+Electric_Altivar-1200_ATV1200A6706060.pdf', 'path_name': '9524a1ddf28011a1a4df11c304568a27.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/9524a1ddf28011a1a4df11c304568a27.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A6706060/medium-voltage-variable-speed-drive-atv1200-6-kv-670-kva/"},"ai":{"faq":[{"question":"Where can I buy ATV1200A6706060 and how do I get a price?","answer":"The ATV1200A6706060 is sourced to order against your BOM quantity through independent distribution. Submit an RFQ for current pricing and lead time — availability is confirmed at quote time. No stock-holding claim is made; each order is quoted individually."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A6706060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A6706060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}