{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A85001010","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A85001010","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A85001010","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A85001010","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A85001010 AC Drive (VFD) 480V, 7106 kW motor power, 8500 kVA apparent power, 48-pulse input, floor-standing enclosure.","salesMarkdown":"## What this VFD is and what it drives The Schneider Electric ATV1200A85001010 is a medium-voltage AC drive from the Altivar 1200 family, designed for large asynchronous motors up to 7106 kW. It delivers 8500 kVA apparent power from a 2970...3630 V supply, using a 48-pulse diode rectifier bridge input topology that keeps line-side harmonics low enough to often skip an external filter. ## Sizing the overload and fault handling The drive handles 1.2× In for 60 s under standard overload, and 1.5× In for 3 s; for high-overload profiles it sustains 1.5× In for 60 s and 1.85× In for 3 s — match the duty cycle to your load profile before freezing the BOM. Prospective line short-circuit current is rated at 31.5 kA for 150 ms, and the drive includes ground-fault protection on the output side. Dielectric strength between earth and power terminals is 28 kV AC — this is a medium-voltage drive, not a 480 V unit; the supply voltage limits (2970...3630 V) confirm the class. ## Physical footprint and installation constraints The drive ships in a floor-standing enclosure measuring 1700 mm deep, 9370 mm wide, and 3040 mm high — this is a multi-cabinet lineup, not a wall-mount unit. Plan for a dedicated electrical room with overhead bus or cable trench access. Cooling is forced convection requiring 110000 m³/h of air volume — the room HVAC must handle this rejection, and the separate air-flow paths keep power-cell heat from recirculating into the control section. Noise level is 80 dB — hearing protection zones apply near the enclosure during operation. Operating altitude derating starts at 1000 m: 0.6 % per 100 m above that. The drive must be mounted vertical ±10° and the ambient relative humidity kept between 0...90 % (0...95 % with optional treatment). ## Control supply and I/O architecture The control section needs an external 220 V AC supply at 3 kVA (or optional 220 V AC/DC); the cooling fans run on a separate 380 V AC supply. Electrical isolation between power and control circuits is maintained. Standard I/O includes 4 software-configurable analogue inputs (0...20 mA / 4...20 mA, 250 Ω impedance), 1 analogue output of the same type, 6 discrete inputs (expandable to 10), and a built-in EMC filter. Main power connection uses M10 screw-type bars accepting up to 6 × 40 mm² cable per phase, entry from top or bottom. ## Standards compliance and lifecycle status The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Lifecycle stage is current production — this is an active catalogue item, not a phase-out or legacy part. The ATV1200 series remains in Schneider's standard portfolio for medium-voltage drives.","metaTitle":"Schneider Electric ATV1200A85001010 AC Drive, 7106 kW","metaDescription":"Schneider Electric ATV1200A85001010 Altivar 1200 AC Drive (VFD) 480V. 7106 kW motor power, 8500 kVA apparent power, 48-pulse input. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"1700 mm (standard efficiency)","Width":"9370 mm (standard efficiency)","Height":"3040 mm standard efficiency","Current":"490 A","IP Rating":"IP42 / IP31 / IP41","Input Type":"48 pulse diode rectifier bridge","Coil Voltage":"220 V","Product Status":"Active","Protection Type":"Ground fault protection: drive","Pollution Degree":"Pollution degree 2","Temp Storage Max":"60 °C","Temp Storage Min":"-10 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"50 °C","Temp Operating Min":"0 °C","Temperature Storage":"-10...60 °C","Ambient Air Temperature Operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A85001010/medium-voltage-variable-speed-drive-atv1200-10-kv-8500-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV1200A85001010/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A85001010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A85001010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}