{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A8603333","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A8603333","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A8603333","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A8603333","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A8603333 medium-voltage AC drive, 860 kVA apparent power, 719 kW motor power, 3.3 kV supply, 18-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## 860 kVA, 719 kW medium-voltage drive — active production The ATV1200A8603333: The 18-pulse diode rectifier input stage draws 150 A line current and delivers a clean input waveform that meets EN/IEC 61800-3 EMC limits with the integrated filter. Prospective line short-circuit current is 31.5 kA for 150 ms — the drive's internal protection and upstream coordination must handle that fault level. ## Overload profile and motor compatibility Standard overload capability is 1.2× rated current for 60 seconds and 1.5× for 3 seconds; the high-overload profile steps to 1.5× for 60 seconds and 1.85× for 3 seconds. This dual rating lets the drive handle both constant-torque conveyors and variable-torque pumps without oversizing the drive frame. The drive is designed for both synchronous and asynchronous motors, with a speed range of 20–100 %. Output voltage is limited to the supply voltage level, so motor winding insulation must be rated for the full 3.3 kV bus. ## Physical footprint and installation constraints The floor-standing enclosure measures 2760 mm wide × 2590 mm high × 1400 mm deep in the standard-efficiency configuration; the high-efficiency variant adds width to 3360 mm and height to 2740 mm, with depth increasing to 1500 mm. Cooling air volume is 16,600 m³/h (standard) or 23,200 m³/h (high efficiency), requiring a dedicated ventilation path in the substation or motor control centre room. The drive assembly includes two plinths, a phase-shifting transformer, nine power cells, medium-voltage arrestors, cooling fans, and an HMI. Separate air flows for power and control sections keep the electronics compartment within the 0–90 % humidity envelope (0–95 % optional). Operating altitude derating starts at 1000 m at 0.6 % per 100 m. ## Compliance and sourcing posture CE marked, with standards compliance to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Pollution degree 2 per EN/IEC 61800-5-1 and overvoltage category II. Dielectric strength is 10 kV AC between earth and power terminals. Electrical isolation between power and control circuits is standard. Sourced to order against the BOM quantity through independent distribution. No pin-compatible alternative exists within the Altivar 1200 family — the ATV1200A8603333 is a specific voltage and power configuration.","metaTitle":"Schneider Electric ATV1200A8603333 AC Drive, 860 kVA, 719 kW","metaDescription":"Schneider Electric ATV1200A8603333 medium-voltage AC drive, 860 kVA / 719 kW, 3.3 kV input, 18-pulse rectifier. Active production. CE marked.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1400 mm (standard efficiency) 1500 mm (high efficiency)","Width":"2760 mm (standard efficiency) 3360 mm (high efficiency)","title":"ATV1200A8603333","Height":"2590 mm standard efficiency 2740 mm high efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"18 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 3.3 kV - 860 kVA","Line current":"150 A","Apparent power":"860 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"719 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"10 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer 9 x power cells Medium voltage arrestors Cooling fans Human machine interface","Product destination":"Synchronous motors Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"16600 m3/h (standard efficiency) 23200 m3/h (high efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP42 IP41 IP31","Network number of phases":"3 phases","Continuous output current":"150 A (standard overload) 120 A (high overload)","Maximum transient current":"180 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"3.3 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Closed-loop control with encoder Voltage/frequency ratio (V/f)","Asynchronous motor control profile":"Vector control with sensor, optional Voltage/frequency ratio (V/f) Closed-loop control with encoder Sensorless flux vector control","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"29 kW (standard efficiency) 25 kW (high efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency) 96.5 % (high efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A8603333?filename=Schneider+Electric_Altivar-1200_ATV1200A8603333.pdf', 'path_name': '98ce83eecdb9c3ea5dd943bb628d34a4.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/98ce83eecdb9c3ea5dd943bb628d34a4.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A8603333/medium-voltage-variable-speed-drive-atv1200-3-3-kv-860-kva/"},"ai":{"faq":[{"question":"What are the key power ratings of the ATV1200A8603333?","answer":"The drive is rated for 860 kVA apparent power and 719 kW motor output at a supply voltage of 2970–3630 V. Line current is 150 A with an 18-pulse diode rectifier input."},{"question":"What compliance documentation does Schneider Electric provide for the ATV1200A8603333?","answer":"The drive is CE marked and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Dielectric strength is 10 kV AC between earth and power terminals."},{"question":"How can I order the ATV1200A8603333 or check availability?","answer":"The drive is quoted to order against your BOM quantity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A8603333","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A8603333 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}