{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A93006363","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A93006363","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A93006363","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A93006363","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A93006363 medium-voltage AC drive, 7148 kW motor power, 8550 kVA apparent power, 2970-3630 V supply, 36-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## 7148 kW motor power — medium-voltage class The ATV1200A93006363: Rated for 7148 kW motor power with 8550 kVA apparent power, this drive sits in the medium-voltage class — supply voltage limits are 2970 to 3630 V. It is not a 480 V unit; the 36-pulse diode rectifier input keeps line-side harmonics low without an active front end. Overload capability is 1.2 In for 60 seconds (standard duty) and 1.5 In for 3 seconds — enough for normal starting and short-term overloads on large fans, pumps, or compressors. High-overload profile goes to 1.5 In for 60 s and 1.85 In for 3 s for tougher loads. ## Floor-standing enclosure — site prep needed The drive ships in a floor-standing enclosure with separate air flows for power and control sections. Physical footprint is 9770 mm wide by 3340 mm tall by 1700 mm deep — this is a room-sized installation, not a panel-mount unit. Cooling requires 100,000 m³/h of forced-convection air through the enclosure. Operating altitude above 1000 m requires derating the output current by 0.6% per additional 100 m. The enclosure must sit vertical within ±10 degrees, and ambient relative humidity is limited to 90% (95% with optional treatment). ## System composition — transformer and cells included This order code covers the complete drive system: phase-shifting transformer, medium-voltage arrestors, 18 power cells, cooling fans, and a human-machine interface. It is not a bare inverter module — the transformer and cells are integral to the 36-pulse input design. Electrical connection is via M10 screw-type bars accepting up to 6 x 40 mm² cable per phase, entry from top or bottom. The drive includes an integrated EMC filter and provides ground-fault protection on the drive side.","metaTitle":"Schneider ATV1200A93006363 Altivar 1200 VFD, 7148 kW","metaDescription":"Schneider Altivar 1200 ATV1200A93006363 medium-voltage VFD, 7148 kW, 8550 kVA, 36-pulse input, 2970-3630 V supply. Actively produced; quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"1700 mm (standard efficiency)","Width":"9770 mm (standard efficiency)","Height":"3340 mm standard efficiency","Current":"850 A","IP Rating":"IP42 / IP31 / IP41","Input Type":"36 pulse diode rectifier bridge","Coil Voltage":"220 V","Product Status":"Active","Protection Type":"Ground fault protection: drive","Pollution Degree":"Pollution degree 2","Temp Storage Max":"60 °C","Temp Storage Min":"-10 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"50 °C","Temp Operating Min":"0 °C","Temperature Storage":"-10...60 °C","Ambient Air Temperature Operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV1200A93006363/medium-voltage-variable-speed-drive-atv1200-6-3-kv-8550-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV1200A93006363/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A93006363","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A93006363 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}