{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A9406060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A9406060","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A9406060","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A9406060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A9406060 medium-voltage AC drive, 940 kVA, 786 kW motor power, 2970-3630 V supply, 30-pulse rectifier, floor-standing enclosure.","salesMarkdown":"## 940 kVA at 3 kV — what the rating means for the load The ATV1200A9406060 is rated for 940 kVA apparent power and 786 kW motor power, fed from a 2970-3630 V supply — this is a medium-voltage drive sized for large induction or synchronous motors in the 800 kW class. The 30-pulse diode rectifier bridge at the input keeps line-side harmonics low enough to skip a separate filter in most utility grids — the integrated EMC filter handles the drive-side emissions. Overload capability is 1.2× rated current for 60 seconds standard duty, or 1.5× for 3 seconds; high-overload profile pushes to 1.5× for 60 seconds and 1.85× for 3 seconds — match this to your load cycle before committing the BOM line. ## Floor-standing enclosure — physical integration constraints This drive ships in a floor-standing enclosure with separate air flows — the standard-efficiency variant measures 2860 mm wide × 2590 mm high × 1400 mm deep; the high-efficiency variant is wider at 3460 mm and taller at 2740 mm, with depth increasing to 1500 mm (-). Forced-convection cooling moves 16600 m³/h on the standard build and 23200 m³/h on the high-efficiency build — the room's ventilation must handle that airflow without recirculating hot exhaust into the intake. Operating altitude derates current 0.6 % per 100 m above 1000 m; the drive must sit vertical within ±10°. No pin-compatible alternative exists in the Altivar 1200 family — the footprint and voltage class are unique to this order code.","metaTitle":"Schneider ATV1200A9406060 AC Drive, 940 kVA, 786 kW, 3 kV","metaDescription":"Schneider Electric Altivar 1200 ATV1200A9406060 medium-voltage VFD, 940 kVA apparent power, 786 kW motor power, 2970-3630 V supply.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1400 mm (standard efficiency) 1500 mm (high efficiency)","Width":"2860 mm (standard efficiency) 3460 mm (high efficiency)","title":"ATV1200A9406060","Height":"2590 mm standard efficiency 2740 mm high efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"30 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6 kV - 940 kVA","Line current":"100 A","Apparent power":"940 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"786 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 15 x power cells","Product destination":"Synchronous motors Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"16600 m3/h (standard efficiency) 23200 m3/h (high efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP31 IP41 IP42","Network number of phases":"3 phases","Continuous output current":"90 A (standard overload) 72 A (high overload)","Maximum transient current":"108 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Voltage/frequency ratio (V/f) Closed-loop control with encoder","Asynchronous motor control profile":"Voltage/frequency ratio (V/f) Sensorless flux vector control Vector control with sensor, optional Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"31 kW (standard efficiency) 28 kW (high efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency) 96.5 % (high efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A9406060?filename=Schneider+Electric_Altivar-1200_ATV1200A9406060.pdf', 'path_name': '0b4a759d3df3666b57d5a488843d2c0f.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/0b4a759d3df3666b57d5a488843d2c0f.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A9406060/medium-voltage-variable-speed-drive-atv1200-6-kv-940-kva/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A9406060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A9406060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}