{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV1200A97506666","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV1200A97506666","canonicalUrl":"https://aoctrl.com/schneider/ATV1200A97506666","factsUrl":"https://aoctrl.com/api/mcp/products/ATV1200A97506666","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 1200 ATV1200A97506666 AC drive, 8151 kW motor power, 2970-3630 V supply, 36-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## Floor-standing medium-voltage drive, 8151 kW The ATV1200A97506666 is a Schneider Electric Altivar 1200 series AC drive rated for 8151 kW motor power at a supply voltage of 2970-3630 V. It uses a 36-pulse diode rectifier bridge input, which reduces line-side harmonics compared to 6- or 12-pulse topologies — relevant for installations where IEEE 519 compliance or utility-imposed THD limits apply. The drive is assembled in a floor-standing enclosure with separate air flows for the power section and control compartment. The enclosure is grey (RAL 7032) and measures 9770 mm wide by 3340 mm high by 1700 mm deep — this is a large-format drive that requires a dedicated equipment room or outdoor shelter with crane access for positioning. ## 36-pulse topology and overload profile The 36-pulse diode rectifier bridge draws a line current of 850 A and delivers an apparent power rating of 9750 kVA. The prospective line short-circuit current withstand is 31.5 kA for 150 ms — this sets the upstream fault-clearing requirement for the supply transformer and switchgear coordination study. Overload capability is specified in two duty classes: standard overload allows 1.2× In for 60 s or 1.5× In for 3 s; high overload allows 1.5× In for 60 s or 1.85× In for 3 s. The high-overload profile is typically selected for applications with intermittent peak torque demands, such as crushers or extruders, while standard overload suits centrifugal pumps and fans. The drive includes integrated EMC filtering and provides electrical isolation between the power and control circuits. Dielectric strength is rated at 20 kV AC between earth and power terminals — a figure that confirms the drive is designed for ungrounded or high-resistance-grounded medium-voltage distribution systems. ## Product composition and control interface The ATV1200A97506666 ships as a complete assembly comprising two plinths, a phase-shifting transformer, medium-voltage arrestors, cooling fans, a human-machine interface, and 18 power cells. The phase-shifting transformer is the key component that enables the 36-pulse rectification — each power cell receives a phase-shifted secondary winding, cancelling harmonics up to the 35th order. Control wiring connects to four software-configurable analogue inputs (0-20 mA or 4-20 mA, 24 V max, 250 Ohm impedance) and one analogue output of the same type. Discrete I/O includes six digital inputs standard, expandable to ten with an optional module. The control supply requires an external 220 V AC source at 3 kVA; the cooling fans draw 380 V AC from an internal supply. Power connections use M10 screw-type bars with a clamping capacity of 6 × 40 mm² per phase (/R, /S, L3/T), with cable entry from the top or bottom. The drive is designed for vertical installation within ±10° and requires 100,000 m³/h of cooling air at standard efficiency — this airflow demand must be factored into the room HVAC design. ## Standards compliance and environmental limits The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. The pollution degree is 2 per EN/IEC 61800-5-1, and the overvoltage category is II — this means the drive is intended for installation in a clean, controlled environment (typically a dedicated electrical room) rather than directly on a production floor. Relative humidity range is 0-90% (0-95% optional), and the operating position is vertical within ±10°. The noise level is 80 dB — hearing protection is required within the equipment room during operation.","metaTitle":"Schneider ATV1200A97506666 AC Drive, 8151 kW, 2970-3630 V","metaDescription":"Schneider Electric ATV1200A97506666 Altivar 1200 AC drive, 8151 kW motor power, 2970-3630 V supply, 36-pulse rectifier. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1700 mm (standard efficiency)","Width":"9770 mm (standard efficiency)","title":"ATV1200A97506666","Height":"3340 mm standard efficiency","Supply":"External supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)","Marking":"CE","Isolation":"Electrical between power and control","Standards":"EN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1","EMC filter":"Integrated","Input type":"36 pulse diode rectifier bridge","Noise level":"80 dB","Speed range":"20...100","description":"medium voltage variable speed drive ATV1200 - 6.6 kV - 9750 kVA","Line current":"850 A","Apparent power":"9750 kVA","Assembly style":"In floor-standing enclosure with separate air flows","Motor power kW":"8151 kW","Output voltage":"<= power supply voltage","Protection type":"Ground fault protection: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to EN/IEC 61800-5-1","Range of product":"Altivar 1200","Device short name":"ATV1200","Relative humidity":"0...90 % 0...95 % optional","Operating altitude":"1000...2000 m with current derating 0.6 % per 100 m","Operating position":"Vertical +/- 10 degree","Overload withstand":"1.2 In, standard overload, 60 s 1.5 In, standard overload, 3 s 1.5 In, high overload, 60 s 1.85 In, high overload, 3 s","Analogue input type":"software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm","Colour of enclosure":"Grey (RAL 7032)","Dielectric strength":"20 kV AC between earth and power terminals","Product Composition":"2 x plinth Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface 18 x power cells","Product destination":"Asynchronous motors","Analogue output type":"software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm","Overvoltage category":"II conforming to EN/IEC 61800-5-1","Prospective line Isc":"31.5 kA for 150 ms","Vibration resistance":"4.9 m/s² (f= 10...50 Hz)","Analogue input number":"4","Discrete input number":"6 10 (optional)","Electrical connection":"Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from the bottom or from the top","Supply voltage limits":"2970...3630 V","Volume of cooling air":"100000 m3/h (standard efficiency)","Analogue output number":"2 4 (optional)","Discrete output number":"10 14 (optional)","IP degree of protection":"IP41 IP31 IP42","Network number of phases":"3 phases","Continuous output current":"850 A (standard overload) 680 A (high overload)","Maximum transient current":"1020 A for 60 s","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6.6 kV +/- 10 %","Communication port protocol":"Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9","Nominal switching frequency":"600 Hz","Product specific application":"Fan, pump, compressor, conveyor","Speed drive output frequency":"0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback","[Uc] control circuit voltage":"220 V","Synchronous motor control profile":"Closed-loop control with encoder Voltage/frequency ratio (V/f)","Asynchronous motor control profile":"Sensorless flux vector control Voltage/frequency ratio (V/f) Vector control with sensor, optional Closed-loop control with encoder","Acceleration and deceleration ramps":"Linear from 0...3200 s","Ambient air temperature for storage":"-10...60 °C","Ambient air temperature for operation":"0...40 °C 40...50 °C (with current derating of 2 % per °C)","Total Losses At 100 % Load Including Fan Power":"239 kW (standard efficiency)","Drive Efficiency With Transformer (Including Fan Power)":"96 % (standard efficiency)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/vn/en/product/download-pdf/ATV1200A97506666?filename=Schneider+Electric_Altivar-1200_ATV1200A97506666.pdf', 'path_name': '85a7a1b4fb29696d2dcc46b8e7bbe4b7.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/85a7a1b4fb29696d2dcc46b8e7bbe4b7.pdf', 'status': 1}","sourceUrl":"https://www.se.com/vn/en/product/ATV1200A97506666/medium-voltage-variable-speed-drive-atv1200-6-6-kv-9750-kva/"},"ai":{"faq":[{"question":"What is the motor power rating of the ATV1200A97506666?","answer":"The drive is rated for 8151 kW motor power at a supply voltage of 2970-3630 V. This is the continuous output capability at the drive terminals."},{"question":"What input rectifier topology does the ATV1200A97506666 use?","answer":"It uses a 36-pulse diode rectifier bridge. This topology significantly reduces line-side harmonic distortion compared to 6- or 12-pulse drives, which is critical for meeting IEEE 519 or utility-imposed THD limits without external harmonic filters."},{"question":"What overload capabilities does the ATV1200A97506666 offer?","answer":"Standard overload allows 1.2× In for 60 s or 1.5× In for 3 s. High overload allows 1.5× In for 60 s or 1.85× In for 3 s. The high-overload profile is suited for applications with intermittent peak torque demands like crushers or extruders."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV1200A97506666","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV1200A97506666 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}