{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV12H075M2X","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV12H075M2X","canonicalUrl":"https://aoctrl.com/schneider/ATV12H075M2X","factsUrl":"https://aoctrl.com/api/mcp/products/ATV12H075M2X","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 12, ATV12H075M2X, 0.75 kW / 1 hp, 100-120 V single-phase, 10.2 A line current (heavy duty), Modbus RS-485, cabinet mount.","salesMarkdown":"The ATV12H075M2X is a current-production Altivar 12 drive sized for a 0.75 kW (1 hp) motor on 100-120 V single-phase input. Line current at heavy-duty rating is 10.2 A at 100 V and 8.5 A at 120 V, which sets the supply-side wire and fuse sizing. Switching frequency is adjustable 2-16 kHz; running above 4 kHz applies a derating factor, so for continuous full-load operation at higher carrier frequencies the drive must be oversized or the load reduced. ## Fieldbus and control note Communication is Modbus serial over a 2-wire RS-485 physical interface, RTU frame, with selectable baud rates of 9.6, 19.2, or 38.4 kbit/s. The single RJ45 connector handles the bus connection. Addressing supports 1 to 247 nodes. The drive includes an adjustable PID regulator for closed-loop process control, and the analog input linearity error is ±0.3% of maximum value.","metaTitle":"Schneider ATV12H075M2X Altivar 12 VFD, 0.75 kW, 1 hp, 100-12","metaDescription":"Schneider ATV12H075M2X Altivar 12 drive, 0.75 kW / 1 hp, 100-120 V single-phase, current production. Modbus RS-485, 2-16 kHz switching frequency. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Depth":"131.2 mm","Width":"72 mm","title":"ATV12H075M2X","Height":"143 mm","Marking":"CE","Standards":"UL 508C UL 618000-5-1 IEC 61800-5-1 IEC 61800-3","EMC filter":"Without EMC filter","Insulation":"Electrical between power and control","Data format":"8 bits, configurable odd, even or no parity","Noise level":"0 dB","Speed range":"1...20","description":"variable speed drive, Altivar 12, 0.75kW, 240V, 1 phase","Line current":"10.2 A at 100 V (heavy duty) 8.5 A at 120 V (heavy duty)","Mounting mode":"Cabinet mount","Time constant":"20 ms +/- 1 ms for reference change","Apparent power":"at 240 V (heavy duty)","Assembly style":"With heat sink","Connector type":"1 RJ45","Motor power hp":"1 hp","Motor power kW":"0.75 kW","Linearity error":"+/- 0.3 % of maximum value for analogue input","Protection type":"Line supply overvoltage Line supply undervoltage Overcurrent between output phases and earth Overheating protection Short-circuit between motor phases Against input phase loss in three-phase Thermal motor protection via the drive by continuous calculation of I²t","Regulation loop":"Adjustable PID regulator","lifecycle_stage":"current","Method of access":"Server Modbus serial","Pollution degree":"2","Quantity per set":"Set of 1","Range of product":"Altivar 12","Shock resistance":"15 gn conforming to IEC 60068-2-27 for 11 ms","Supply frequency":"50/60 Hz +/- 5 %","Network frequency":"50...60 Hz","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3 5...95 % without dripping water conforming to IEC 60068-2-3","Sampling duration":"20 ms, tolerance +/- 1 ms for logic input 10 ms for analogue input","Tightening Torque":"0.8 N.m","Transmission rate":"9.6 kbit/s 19.2 kbit/s 38.4 kbit/s","Operating altitude":"> 1000...2000 m with current derating 1 % per 100 m <= 1000 m without derating","Operating position":"Vertical +/- 10 degree","Physical interface":"2-wire RS 485","Transmission frame":"RTU","Number of addresses":"1...247","Relay output number":"1","Switching frequency":"2...16 kHz adjustable 4...16 kHz with derating factor","Frequency resolution":"Analog input: converter A/D, 10 bits Display unit: 0.1 Hz","Overvoltage category":"Class III","Prospective line Isc":"1 kA","Transient overtorque":"150...170 % of nominal motor torque depending on drive rating and type of motor","Type of polarization":"No impedance","Vibration resistance":"1 gn (f = 13...200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f = 3...13 Hz) - drive unmounted on symmetrical DIN rail - conforming to IEC 60068-2-6","Analogue input number":"1","Braking to standstill":"By DC injection","Communication service":"Read holding registers (03) 29 words Write single register (06) 29 words Write multiple registers (16) 27 words Read/write multiple registers (23) 4/4 words Read device identification (43)","Discrete input number":"4","Maximum input current":"8.5 A","Analogue output number":"1","Discrete output number":"2","Maximum output voltage":"240 V","Nominal Output Current":"4.2 A","IP degree of protection":"IP20","Motor slip compensation":"Preset in factory Adjustable","Brake chopper integrated":"False","Electromagnetic emission":"Radiated emissions environment 1 category C2 conforming to IEC 61800-3 2...16 kHz shielded motor cable Conducted emissions with integrated EMC filter environment 1 category C1 conforming to IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable Conducted emissions with integrated EMC filter environment 1 category C2 conforming to IEC 61800-3 2...12 kHz shielded motor cable Conducted emissions with integrated EMC filter environment 1 category C2 conforming to IEC 61800-3 2, 4 and 16 kHz shielded motor cable Conducted emissions with additional EMC filter environment 1 category C1 conforming to IEC 61800-3 4...12 kHz shielded motor cable Conducted emissions with additional EMC filter environment 1 category C2 conforming to IEC 61800-3 4...12 kHz shielded motor cable Conducted emissions with additional EMC filter environment 2 category C3 conforming to IEC 61800-3 4...12 kHz shielded motor cable <50 m","Maximum output frequency":"4 kHz","Continuous output current":"4.2 A at 4 kHz","Product or component type":"Variable speed drive","[Us] rated supply voltage":"200...240 V - 15...10 %","Communication port protocol":"Modbus","Nominal switching frequency":"4 kHz","Product specific application":"Simple machine","Speed drive output frequency":"0.5...400 Hz","4 Quadrant Operation Possible":"False","Electromagnetic compatibility":"Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Immunity to conducted disturbances level 3 conforming to IEC 61000-4-6 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Surge immunity test level 3 conforming to IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11","With sft fct Safe Stop 2 (SS2)":"False","Ambient air transport temperature":"-25...70 °C","Asynchronous motor control profile":"Quadratic voltage/frequency ratio Sensorless flux vector control Voltage/frequency ratio (V/f)","Acceleration and deceleration ramps":"U Linear from 0 to 999.9 s S","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"-10...40 °C without derating 40...60 °C with current derating 2.2 % per °C","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3","With safety function Safe Stop 1 (SS1)":"False","With safety function Safe Position (SP)":"False","With safety function Safe Direction (SDI)":"False","With safety function Safe torque off (STO)":"False","With safety function Safe programmable logic":"False","With safety function Safe Speed Monitor (SSM)":"False","Relative symmetric network frequency tolerance":"5 %","With safety function Safe Operating Stop (SOS)":"False","With safety function Safely Limited Speed (SLS)":"False","With safety function Safely Limited Position (SLP)":"False","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/384da3173eb7a1a1268934c4f757572d.pdf","sourceUrl":"https://www.se.com/vn/en/product/ATV12H075M2X/variable-speed-drive-altivar-12-0-75kw-240v-1-phase/"},"ai":{"faq":[{"question":"What communication protocols does it support?","answer":"Modbus serial over 2-wire RS-485, RTU frame, at baud rates of 9.6, 19.2, or 38.4 kbit/s. Addressing supports 1 to 247 nodes via a single RJ45 connector."},{"question":"Does this drive include an internal EMC filter?","answer":"No, this variant is supplied without an internal EMC filter. External filtering is required for installations that must meet conducted emission limits."},{"question":"What compliance standards does it meet?","answer":"CE marked and certified to UL 508C, UL 61800-5-1, IEC 61800-5-1, and IEC 61800-3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV12H075M2X","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV12H075M2X when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}