{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV212HD45N4LCD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV212HD45N4LCD","canonicalUrl":"https://aoctrl.com/schneider/ATV212HD45N4LCD","factsUrl":"https://aoctrl.com/api/mcp/products/ATV212HD45N4LCD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 212 ATV212HD45N4LCD AC drive, 45 kW / 60 hp, 380-480 V, 83.8 A / 65.9 A line current, integrated C2 EMC filter, IP20, 550 x 240 x 244 mm.","salesMarkdown":"Rated for 45 kW or 60 hp on standard asynchronous motors, this ATV212HD45N4LCD draws 83.8 A at 380 V and 65.9 A at 480 V line current — the lower figure at 480 V is the one to size the input feeder and upstream protection for in North America. The integrated Class C2 EMC filter means it meets EN 61800-3 Category C2 conducted emissions limits out of the box for industrial environments — no external filter needed for most second-environment (industrial mains) installations. ## Protection coverage and fieldbus — what the drive watches and how it talks The drive monitors itself and the motor for overcurrent, overvoltage on the DC bus, input phase loss, short-circuit between motor phases, earth faults, overheating, and motor thermal protection including PTC probe input — all built in, no add-on module for basic motor protection. Serial communication is 2-wire RS-485 Modbus RTU at 9600 or 19200 bps, with addressing from 1 to 247 — sufficient for most PLC-to-drive links without a fieldbus gateway, though the LonWorks option card is available if the site uses that backbone. ## Mounting and environment — panel fit and site conditions Dimensions are 550 mm high, 240 mm wide, 244 mm deep — a tall, relatively narrow footprint that fits a standard 600 mm deep enclosure with clearance for the top cable entry and heatsink airflow of 429 m³/h. Operating position is vertical within ±10°, altitude derating starts above 1000 m (1 % per 100 m up to 3000 m, with a 2000 m limit for corner-grounded distribution networks), and ambient conditions cover 5–95 % humidity without condensation — standard for indoor industrial panels.","metaTitle":"Schneider ATV212HD45N4LCD AC Drive, 45 kW / 60 hp, 480 V","metaDescription":"Schneider Electric ATV212HD45N4LCD Altivar 212 AC drive, 45 kW / 60 hp at 480 V. Integrated C2 EMC filter, Modbus serial. Mature lifecycle, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"244 mm","Width":"240 mm","Height":"550 mm","Marking":"CE","Air flow":"429 m3/h","Standards":"EN 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C3 EN 61800-3 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-5-1 IEC 61800-3 environments 1 category C3 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C2 UL Type 1 EN 61800-3 environments 2 category C3 EN 61800-3 category C3 IEC 61800-3 environments 1 category C2 EN 55011 class A group 1 EN 61800-3 environments 1 category C2 EN 61800-3 IEC 61800-3 EN 61800-3 environments 1 category C1 EN 61800-5-1 IEC 61800-3 environments 1 category C1 IEC 61800-3 category C2 IEC 61800-3 category C3","EMC filter":"Class C2 EMC filter integrated","Data format":"8 bits, 1 stop, odd even or no configurable parity","Noise level":"64 dB conforming to 86/188/EEC","Option card":"Communication card for LonWorks","Speed range":"1...10","Line current":"83.8 A at 380 V 65.9 A at 480 V","Functionality":"Mid","Apparent power":"61.9 kVA at 380 V","Assembly style":"With heat sink","Connector type":"1 RJ45 1 open style","Motor power hp":"60 hp","Motor power kW":"45 kW","Output voltage":"= 1 mOhm 500 V DC for 1 minute","Speed accuracy":"+/- 10 % of nominal slip 0.2 Tn to Tn","Protection type":"Overheating protection: drive Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor","Regulation loop":"Adjustable PI regulator","Torque accuracy":"+/- 15 %","lifecycle_stage":"mature","Local signalling":"1 LED (red) for DC bus energized","Pollution degree":"3 conforming to IEC 61800-5-1","Range of product":"Altivar 212","Shock resistance":"15 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV212","Network frequency":"47.5...63 Hz","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3 5...95 % without dripping water conforming to IEC 60068-2-3","Transmission rate":"9600 bps or 19200 bps","Operating altitude":"1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 1000 m without derating","Operating position":"Vertical +/- 10 degree","Physical interface":"2-wire RS 485","Transmission frame":"RTU","Analogue input type":"VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits","Number of addresses":"1...247","Product destination":"Asynchronous motors","Switching frequency":"6...16 kHz adjustable 8...16 kHz with derating factor","Frequency resolution":"Display unit: 0.1 Hz Analog input: 0.024/50 Hz","Prospective line Isc":"22 kA","Specific application":"Centrifugal pumps and fans","Transient overtorque":"120 % of nominal motor torque +/- 10 % for 60 s","Type of polarization":"No impedance","Vibration resistance":"1.5 mm (f= 3...13 Hz) conforming to EN/IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8","Analogue input number":"2","Braking to standstill":"By DC injection","Communication service":"Monitoring inhibitable Time out setting from 0.1 to 100 s Read holding registers (03) 2 words maximum Write single register (06) Read device identification (43) Write multiple registers (16) 2 words maximum","Supply voltage limits":"323...528 V","Analogue output number":"1","Discrete output number":"2","Power dissipation in W":"1253 W","IP degree of protection":"IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529","Motor slip compensation":"Adjustable Not available in voltage/frequency ratio motor control Automatic whatever the load","Network number of phases":"3 phases","Continuous output current":"94 A at 380 V 94 A at 460 V","Maximum transient current":"103.4 A for 60 s","Product or component type":"Variable speed drive","[Us] rated supply voltage":"380...480 V - 15...10 %","Communication port protocol":"BACnet LonWorks Modbus APOGEE FLN METASYS N2","Nominal switching frequency":"8 kHz","Environmental characteristic":"Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3","Product specific application":"Pumps and fans in HVAC","Speed drive output frequency":"0.5...200 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11","Asynchronous motor control profile":"Voltage/frequency ratio, 5 points Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio, 2 points Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor, standard","Acceleration and deceleration ramps":"Automatic based on the load Linear adjustable separately from 0.01 to 3200 s","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"-10...40 °C (without derating) 40...50 °C (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/id/en/product/ATV212HD45N4LCD/kit-variable-speed-drive-atv212-45kw-380v-3ph-lcd/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV212HD45N4LCD/alternatives.json"},"ai":{"faq":[{"question":"What is the line current for the ATV212HD45N4LCD at 480 V?","answer":"The line current is 65.9 A at 480 V and 83.8 A at 380 V."},{"question":"What EMC filter class does this drive have?","answer":"An integrated Class C2 EMC filter is built in, meeting EN 61800-3 Category C2 conducted emissions limits for industrial second-environment installations without an external filter."},{"question":"How can I order the ATV212HD45N4LCD or request a quote?","answer":"Submit an RFQ for current pricing and availability confirmation — no stock-holding claim, but the mature lifecycle keeps lead times predictable."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV212HD45N4LCD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV212HD45N4LCD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}