{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV212WD22N4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV212WD22N4","canonicalUrl":"https://aoctrl.com/schneider/ATV212WD22N4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV212WD22N4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 212 ATV212WD22N4 AC Drive (VFD) 480V, 22 kW, 33.1 A at 480 V, 3-phase, 28.3 x 11.2 x 12.4 in, integrated C2 EMC filter.","salesMarkdown":"## 22 kW Altivar 212 drive — panel fit and load match The ATV212WD22N4 is a 22 kW AC drive from the Altivar 212 series, designed for asynchronous motors in 3-phase 480 V installations. It draws 33.1 A at 480 V and 41.6 A at 380 V line current, so the upstream protection and cable sizing should be specced for the higher 380 V figure if the supply could land there. The drive carries an integrated Class C2 EMC filter, which covers most industrial environments (IEC 61800-3 environments 1 and 2, category C2) without an external filter box. That saves a DIN-rail slot and a wiring step. Physical footprint is 28.3 in high by 11.2 in wide by 12.4 in deep — a tall, narrow enclosure that fits a standard 800 mm cabinet depth. Mount it vertically within ±10° for the heatsink to work as designed. ## Mature lifecycle — sourcing posture Sourced to order against the BOM quantity through independent distribution. ## Compliance and approvals stack The drive carries CE, UL, CSA, C-Tick, and GOST markings, and meets IEC 61800-5-1 for safety and IEC 61800-3 for EMC across environments 1 and 2, categories C1 through C3. Pollution degree 3 per IEC 61800-5-1 means it tolerates conductive dust and humidity in industrial panels. Protection includes thermal power stage monitoring, short-circuit between motor phases, overcurrent between output phases and earth, DC bus overvoltage, input phase loss, and motor thermal protection with PTC probe support.","metaTitle":"Schneider ATV212WD22N4 AC Drive (VFD) 480V, 22 kW","metaDescription":"Schneider Electric ATV212WD22N4 Altivar 212 AC Drive, 22 kW, 33.1 A at 480 V, 3-phase. Mature lifecycle. Integrated C2 EMC filter. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"12.4 in (315 mm)","Phase":"3 phase","Width":"11.2 in (284 mm)","title":"ATV212WD22N4","Height":"28.3 in (720 mm)","Marking":"CE","Category":"US1CP4D22158","Standards":"IEC 61800-5-1 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 CE UL CSA C-Tick N1831 GOST","EMC filter":"Class C2 EMC filter integrated","Data format":"8 bits, 1 stop, odd even or no configurable parity","Noise level":"59.9 dB 86/188/EEC","Option card":"Communication card LonWorks","Speed range":"1...10","description":"variable speed drive, Altivar 212, 22kW, 30hp, 480V, 3 phases, with EMC class C2, IP55","Line current":"33.1 A 480 V 41.6 A 380 V","Functionality":"Mid","Apparent power":"33.2 kVA 380 V","Assembly style":"With heat sink","Connector Type":"1 open style 1 RJ45","Motor power kW":"22 kW","Output voltage":"= 1 mOhm 500 V DC for 1 minute","Speed accuracy":"+/- 10 % of nominal slip 0.2 Tn to Tn","Protection type":"Overheating protection drive Thermal power stage drive Short-circuit between motor phases drive Input phase breaks drive Overcurrent between output phases and earth drive Overvoltages on the DC bus drive Break on the control circuit drive Against exceeding limit speed drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Against input phase loss drive Thermal protection motor Motor phase break motor With PTC probes motor","Regulation loop":"Adjustable PI regulator","Torque accuracy":"+/- 15 %","lifecycle_stage":"mature","Local signalling":"1 LED (red) for DC bus energized","Pollution degree":"3 IEC 61800-5-1","Range of Product":"Altivar 212","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV212","Network Frequency":"47.5...63 Hz","Relative humidity":"5...95 % without condensation IEC 60068-2-3 5...95 % without dripping water IEC 60068-2-3","Transmission Rate":"9600 bps or 19200 bps","Operating altitude":"3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating","Operating position":"Vertical +/- 10 degree","Physical interface":"2-wire RS 485","Transmission frame":"RTU","Analogue input type":"VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable PTC probe 0...6 probes 1500 Ohm VIA switch-configurable current 0...20 mA 250 Ohm 10 bits","Number of addresses":"1...247","Product destination":"Asynchronous motors","Switching frequency":"6...16 kHz adjustable 8...16 kHz with derating factor","Frequency resolution":"Display unit 0.1 Hz Analog input 0.024/50 Hz","Prospective line Isc":"22 kA","Specific application":"HVAC","Transient overtorque":"120 % of nominal motor torque +/- 10 % 60 s","Type of polarization":"No impedance","Vibration resistance":"1.5 mm (f= 3...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8","Analogue input number":"2","Braking to standstill":"By DC injection","Communication Service":"Write multiple registers (16) 2 words maximum Read device identification (43) Write single register (06) Monitoring inhibitable Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s","Nbr. of units in pkg.":"1","Supply voltage limits":"323...528 V","Analogue output number":"1","Discrete output number":"2","IP degree of protection":"IP55","Motor slip compensation":"Not available in voltage/frequency ratio motor control Automatic whatever the load Adjustable","Continuous output current":"43.5 A 380 V 43.5 A 460 V","Maximum transient current":"47.9 A 60 s","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"380...480 V - 15...10 %","Maximum Horse Power Rating":"30 hp","Communication Port Protocol":"METASYS N2 LonWorks BACnet APOGEE FLN Modbus","Nominal switching frequency":"8 kHz","Environmental characteristic":"Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3","Product Specific Application":"Pumps and fans in HVAC","Speed drive output frequency":"0.5...200 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11","Asynchronous motor control profile":"Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio, 2 points","Acceleration and deceleration ramps":"Automatic based on the load Linear adjustable separately from 0.01 to 3200 s","Ambient Air Temperature for Storage":"-13...158 °F (-25...70 °C)","Environment/IP degree of protection":"IP55 IEC 61800-5-1 IP55 IEC 60529","Ambient air temperature for operation":"14...104 °F (-10...40 °C) (without derating) 104...122 °F (40...50 °C) (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,174.24 – $6,192.16","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/ATV212WD22N4/variable-speed-drive-altivar-212-22kw-30hp-480v-3-phases-with-emc-class-c2-ip55/"},"ai":{"faq":[{"question":"What is ATV212WD22N4's line current rating?","answer":"The drive draws 33.1 A at 480 V and 41.6 A at 380 V line current. Size upstream protection for the higher 380 V figure."},{"question":"What compliance documentation does Schneider provide for ATV212WD22N4?","answer":"The drive is CE, UL, CSA, C-Tick, and GOST certified, meeting IEC 61800-5-1 safety and IEC 61800-3 EMC standards across environments 1 and 2, categories C1 through C3."},{"question":"How can I order ATV212WD22N4 or check availability?","answer":"This drive is sourced to order against the BOM quantity through independent distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV212WD22N4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV212WD22N4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}