{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV21HD22M3X","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV21HD22M3X","canonicalUrl":"https://aoctrl.com/schneider/ATV21HD22M3X","factsUrl":"https://aoctrl.com/api/mcp/products/ATV21HD22M3X","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 21 ATV21HD22M3X AC drive (VFD), 22 kW, 200-240 V 3-phase, 66.4 A line current, 33.5 kVA, IP20, without EMC filter.","salesMarkdown":"## 22 kW, 200-240 V — what it handles The ATV21HD22M3X is a 22 kW Altivar 21 variable-frequency drive for three-phase asynchronous motors on a 200-240 V supply — the line current at 240 V is 66.4 A, and at 200 V it draws 80.4 A, so the feeder and branch protection need to be sized for the lower-voltage end of the range. Apparent power is 33.5 kVA at 240 V, and the drive delivers a transient overtorque of 120 % for 60 s — enough to break a stalled pump or conveyor start without tripping, as long as the upstream circuit is coordinated for the inrush. ## Switching frequency and derating Switching frequency is adjustable from 6 to 16 kHz, with a derating factor required above 8 kHz — running at 16 kHz quiets the motor whine but cuts the continuous output current, so if you need full rated torque at the shaft, keep the carrier at 8 kHz or below. The drive includes an adjustable PI regulator for closed-loop process control (pressure, flow, level) and the speed accuracy is ±10 % of nominal slip from 0.2 Tn to Tn — adequate for most fan and pump applications that don't need encoder feedback. ## Standards and compliance package The ATV21HD22M3X carries CE marking and meets EN/IEC 61800-3 for EMC environments 1 and 2, categories C1 through C3, plus EN/IEC 61800-5-1 for safety — so it's accepted across most industrial installations in Europe and markets that harmonise with IEC standards. It is quoted to order against the BOM; availability and current pricing confirmed at RFQ. ## Mounting and environment Dimensions are 16.5 x 9.4 x 4.8 inches (H x W x D) — the heatsink is integral, so panel cut-out and clearance for airflow need to account for the full depth plus a bend radius for the power cables. Operating altitude is limited to 2000 m for corner-grounded distribution networks; above that, derate per the manual. Pollution degree 3 per IEC 61800-5-1 means it's suited for industrial environments with conductive dust or humidity, but not for direct washdown — IP20, no EMC filter fitted.","metaTitle":"Schneider Electric ATV21HD22M3X AC Drive (VFD) 240V, 22 kW","metaDescription":"Schneider Electric ATV21HD22M3X Altivar 21 VFD, 22 kW, 200-240 V 3-phase, 66.4 A line current. Mature lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Depth":"4.8 in (122 mm)","Phase":"3 phase","Width":"9.4 in (240 mm)","title":"ATV21HD22M3X","Height":"16.5 in (420 mm)","Marking":"CE","Category":"22156-ATV212 30 - 40 HP 230 VOLT","Standards":"EN 61800-3 environments 1 category C3 EN 61800-3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 UL Type 1 EN 61800-3 environments 1 category C2 IEC 61800-5-1 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 IEC 61800-3 environments 2 category C3 EN 61800-3 environments 1 category C1 EN 61800-5-1 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 1 category C2","Diagnostic":"1 LED (red) for DC bus energized","EMC filter":"Without EMC filter","Data format":"8 bits, 1 stop, odd even or no configurable parity","Noise level":"59.9 dB 86/188/EEC","Option card":"Communication card APOGEE FLN Communication card BACnet Communication card LonWorks Communication card METASYS N2","Speed range":"1...10","description":"variable speed drive ATV21 - 22kW, 30HP - 240V - IP20","Line current":"66.4 A 240 V 80.4 A 200 V","Apparent power":"33.5 kVA 240 V","Assembly style":"With heat sink","Component name":"ATV21","Connector Type":"1 RJ45","Motor power kW":"22 kW","Output voltage":"= 1 mOhm 500 V DC for 1 minute","Speed accuracy":"+/- 10 % of nominal slip 0.2 Tn to Tn","Regulation loop":"Adjustable PI regulator","Torque accuracy":"+/- 15 %","lifecycle_stage":"mature","Pollution degree":"3 IEC 61800-5-1","Range of Product":"Altivar 21","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Relative humidity":"5...95 % without condensation IEC 60068-2-3 5...95 % without dripping water IEC 60068-2-3","Transmission Rate":"9600 bps or 19200 bps","Operating altitude":"3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network","Operating position":"Vertical +/- 10 degree","Physical interface":"2-wire RS 485","Transmission frame":"RTU","Dielectric strength":"2830 V DC between earth and power terminals 4230 V DC between control and power terminals","Number of addresses":"1...247","Product destination":"Asynchronous motors","Switching frequency":"6...16 kHz adjustable 8...16 kHz with derating factor","Frequency resolution":"Analog input 0.024/50 Hz Display unit 0.1 Hz","Power Supply Voltage":"200...240 V - 15...10 %","Transient overtorque":"120 % of nominal motor torque +/- 10 % 60 s","Type of polarization":"No impedance","Vibration resistance":"1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8 1.5 mm (f= 3...13 Hz) conforming to EN/IEC 60068-2-6","Communication Service":"Write multiple registers (16) 2 words maximum Read device identification (43) Write single register (06) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Monitoring inhibitable","Power Supply Frequency":"50...60 Hz - 5...5 %","IP degree of protection":"IP20 on upper part without blanking plate on cover EN/IEC 60529 IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1","Motor slip compensation":"Automatic whatever the load Not available in voltage/frequency ratio motor control Adjustable","Maximum transient current":"96.8 A 60 s","Product or Component Type":"Variable speed drive","Maximum Horse Power Rating":"30 hp","Communication Port Protocol":"Modbus","Nominal switching frequency":"8 kHz","Power Supply Voltage Limits":"170...264 V","Environmental characteristic":"Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3","Product Specific Application":"Pumps and fans in HVAC","Speed drive output frequency":"0.5...200 Hz","maximum prospective line Isc":"22 kA","Electromagnetic compatibility":"1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11","Power Supply Frequency Limits":"47.5...63 Hz","Maximum Continuous Output Current":"88 A 230 V","Asynchronous motor control profile":"Constant voltage/frequency ratio Constant voltage/frequency ratio with automatic IR compensation Quadratic voltage/frequency ratio Current flux vector control (FVC) without speed feedback Energy saving ratio","Ambient Air Temperature for Storage":"-13...158 °F (-25...70 °C)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) (without derating) 104...122 °F (40...50 °C) (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/ATV21HD22M3X/variable-speed-drive-atv21-22kw-30hp-240v-ip20/"},"ai":{"faq":[{"question":"How can I order the ATV21HD22M3X or get a quote?","answer":"This drive is quoted to order through independent distribution."},{"question":"What is the ATV21HD22M3X's line current at 240 V?","answer":"At 240 V the line current is 66.4 A; at 200 V it is 80.4 A. Size the branch circuit for the higher current at the lower voltage end of the range."},{"question":"What compliance documentation does Schneider provide for the ATV21HD22M3X?","answer":"The drive is CE marked and complies with EN/IEC 61800-3 (EMC environments 1 and 2, categories C1-C3) and EN/IEC 61800-5-1 (safety). Standards documentation is available from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV21HD22M3X","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV21HD22M3X when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}