{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV21HD30M3X","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV21HD30M3X","canonicalUrl":"https://aoctrl.com/schneider/ATV21HD30M3X","factsUrl":"https://aoctrl.com/api/mcp/products/ATV21HD30M3X","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar 21 ATV21HD30M3X AC drive, 30 kW, 200-240 V three-phase input, 89.5 A line current, 44.6 kVA apparent power, IP20, CE marked.","salesMarkdown":"## Drive fit for a 30 kW, 200-240 V three-phase line The ATV21HD30M3X is a 30 kW Altivar 21 AC drive designed for three-phase 200-240 V input — the line current draws 89.5 A at 240 V and 113.3 A at 200 V, so the upstream feeder and branch protection must be sized for the lower-voltage end of the range. Apparent power is 44.6 kVA at 240 V, which sets the transformer or generator capacity needed for a single drive installation. ## Switching frequency and torque capability Switching frequency is adjustable from 6 to 16 kHz, with derating required above 8 kHz — for a 30 kW motor driving a fan or pump, 6 kHz keeps the IGBT junction temperature within limits while the 16 kHz ceiling quiets motor whine on constant-torque loads. Transient overtorque of 120 % for 60 seconds gives headroom for breakaway torque on conveyors or crushers without oversizing the drive frame. ## Compliance and environmental ratings The drive carries CE marking and complies with IEC 61800-5-1 (safety) and IEC 61800-3 (EMC) for environments 1 and 2, categories C1 through C3 — it ships without an EMC filter, so a line-side filter may be needed for first-environment (residential) installations. Pollution degree 3 per IEC 61800-5-1 means the drive is rated for conductive pollution environments — typical in industrial panels near machining or chemical processes — and the IP20 enclosure requires cabinet mounting.","metaTitle":"Schneider Electric ATV21HD30M3X AC Drive, 30 kW, 200-240 V","metaDescription":"Schneider Electric ATV21HD30M3X Altivar 21 AC drive, 30 kW, 200-240 V three-phase input, 89.5 A line current at 240 V. Mature lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Depth":"11.4 in (290 mm)","Phase":"3 phase","Width":"12.6 in (320 mm)","Height":"24.8 in (630 mm)","Marking":"CE","Category":"22156-ATV212 30 - 40 HP 230 VOLT","Standards":"IEC 61800-5-1 IEC 61800-3 environments 2 category C3 EN 61800-3 environments 2 category C1 IEC 61800-3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 1 category C2 EN 61800-5-1 EN 61800-3 EN 61800-3 environments 2 category C3 EN 61800-3 environments 2 category C2 IEC 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C3 UL Type 1 IEC 61800-3 environments 1 category C3","Diagnostic":"1 LED (red) for DC bus energized","EMC filter":"Without EMC filter","Data format":"8 bits, 1 stop, odd even or no configurable parity","Noise level":"63.7 dB 86/188/EEC","Option card":"Communication card APOGEE FLN Communication card BACnet Communication card LonWorks Communication card METASYS N2","Speed range":"1...10","Line current":"113.3 A 200 V 89.5 A 240 V","Apparent power":"44.6 kVA 240 V","Assembly style":"With heat sink","Component name":"ATV21","Connector Type":"1 RJ45","Motor power kW":"30 kW","Output voltage":"= 1 mOhm 500 V DC for 1 minute","Speed accuracy":"+/- 10 % of nominal slip 0.2 Tn to Tn","Regulation loop":"Adjustable PI regulator","Torque accuracy":"+/- 15 %","lifecycle_stage":"mature","Pollution degree":"3 IEC 61800-5-1","Range of Product":"Altivar 21","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Relative humidity":"5...95 % without condensation IEC 60068-2-3 5...95 % without dripping water IEC 60068-2-3","Transmission Rate":"9600 bps or 19200 bps","Operating altitude":"3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network","Operating position":"Vertical +/- 10 degree","Physical interface":"2-wire RS 485","Transmission frame":"RTU","Dielectric strength":"2830 V DC between earth and power terminals 4230 V DC between control and power terminals","Number of addresses":"1...247","Product destination":"Asynchronous motors","Switching frequency":"6...16 kHz adjustable 8...16 kHz with derating factor","Frequency resolution":"Analog input 0.024/50 Hz Display unit 0.1 Hz","Power Supply Voltage":"200...240 V - 15...10 %","Transient overtorque":"120 % of nominal motor torque +/- 10 % 60 s","Type of polarization":"No impedance","Vibration resistance":"1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8 1.5 mm (f= 3...13 Hz) conforming to EN/IEC 60068-2-6","Communication Service":"Read device identification (43) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Write single register (06) Monitoring inhibitable Write multiple registers (16) 2 words maximum","Power Supply Frequency":"50...60 Hz - 5...5 %","IP degree of protection":"IP20 on upper part without blanking plate on cover EN/IEC 60529 IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1","Motor slip compensation":"Adjustable Not available in voltage/frequency ratio motor control Automatic whatever the load","Maximum transient current":"128.7 A 60 s","Product or Component Type":"Variable speed drive","Maximum Horse Power Rating":"40 hp","Communication Port Protocol":"Modbus","Nominal switching frequency":"8 kHz","Power Supply Voltage Limits":"170...264 V","Environmental characteristic":"Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3","Product Specific Application":"Pumps and fans in HVAC","Speed drive output frequency":"0.5...200 Hz","maximum prospective line Isc":"22 kA","Electromagnetic compatibility":"1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11","Power Supply Frequency Limits":"47.5...63 Hz","Maximum Continuous Output Current":"117 A 230 V","Asynchronous motor control profile":"Energy saving ratio Quadratic voltage/frequency ratio Current flux vector control (FVC) without speed feedback Constant voltage/frequency ratio Constant voltage/frequency ratio with automatic IR compensation","Ambient Air Temperature for Storage":"-13...158 °F (-25...70 °C)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) (without derating) 104...122 °F (40...50 °C) (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/ATV21HD30M3X/variable-speed-drive-atv21-30kw-40hp-240v-ip20/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV21HD30M3X/alternatives.json"},"ai":{"faq":[{"question":"How can I order the ATV21HD30M3X or check availability?","answer":"The ATV21HD30M3X is quoted to order against your BOM quantity through independent distribution. Availability and current pricing are confirmed at RFQ — no stock-holding claim is made on this page."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV21HD30M3X","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV21HD30M3X when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}