{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000C138A6666ND","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000C138A6666ND","canonicalUrl":"https://aoctrl.com/schneider/ATV6000C138A6666ND","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000C138A6666ND","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000, ATV6000C138A6666ND, 1100 kW normal duty / 1050 kW heavy duty, 3-phase, 30-pulse diode rectifier, 1380 kVA apparent power.","salesMarkdown":"## Ratings that define the fit The ATV6000C138A6666ND: Line current is 121 A at normal duty and 115 A at heavy duty, with an apparent power rating of 1380 kVA. Power losses run 47.9 kW normal duty, 45.7 kW heavy duty — that heat lands in the enclosure, so forced convection cooling is integrated. The drive carries IEC 61800-3 category C3 (integrated) and C4 (power) EMC filters, covering conducted emissions for industrial second-environment installations. ## Fieldbus and I/O architecture Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), and EtherCAT. Slot B takes encoder interfaces (digital 5/12 V, analog, resolver, HTL) plus digital/analog I/O and relay extension modules. The control block includes two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial. Eight programmable digital inputs (24 V DC) are on board. ## Physical scale and enclosure Floor-standing enclosure measures 103.03 in high by 144.09 in wide by 55.1 in deep. Cable entry is at the bottom. The enclosure is light grey RAL 7035 and includes the plinth, power cells, medium-voltage arrestors, phase-shifting transformer, HMI, and cooling fans as provided equipment.","metaTitle":"Schneider ATV6000C138A6666ND Altivar Process VFD, 1100 kW","metaDescription":"Schneider Altivar Process ATV6000C138A6666ND medium-voltage drive, 1100 kW normal duty, 3-phase, 30-pulse input, <3% THDI. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"55.1 in (1400.0 mm)","Width":"144.09 in (3660.0 mm)","Height":"103.03 in (2617.0 mm)","Phases":"3-phase","Current":"121 A normal duty 115 A heavy duty","Frequency":"50 Hz +/- 5 %","IP Rating":"IP31","Input Type":"30 pulse diode rectifier bridge","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"50 °C","Temp Storage Min":"0 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"32...122 °F (0...50 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/ATV6000C138A6666ND/medium-voltage-variable-speed-drive-atv6000-6-6-kv-1475-hp-ul-certification/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6000C138A6666ND/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000C138A6666ND","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000C138A6666ND when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}