{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000C190A3333NA3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000C190A3333NA3","canonicalUrl":"https://aoctrl.com/schneider/ATV6000C190A3333NA3","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000C190A3333NA3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000, 333 A line current (normal duty), 1520 kW motor power, 18-pulse diode rectifier, floor-standing enclosure, CE EAC.","salesMarkdown":"The Schneider Electric ATV6000C190A3333NA3 is a medium-voltage drive from the Altivar Process ATV6000 range, built around an 18-pulse diode rectifier input and IGBT inverter cells with multilevel PWM output. It is sized for a 1520 kW motor in normal duty or 1220 kW in heavy duty, drawing 333 A or 266 A line current respectively. The drive is supplied in a floor-standing enclosure measuring 4460 mm wide by 2687 mm high by 1500 mm deep. ## Supply and input architecture The 18-pulse diode rectifier keeps input current THDI below 3% per IEEE 519-1992, so no external harmonic filter is needed for most utility compliance. The control circuit accepts 100–240 V AC 47–63 Hz or 120–370 V DC, with a separate 400 V AC supply for the cooling fans. An integrated EMC filter meets IEC 61800-3 category C3 on the control side and C4 on the power side. ## Motor and output ratings Output voltage is limited to the supply voltage level. The drive handles asynchronous, synchronous, and permanent magnet motors. Power losses run 66.1 kW at normal duty and 53.1 kW at heavy duty, so forced convection cooling is mandatory — the enclosure includes dedicated fan supply. ## Control and connectivity A 10-inch LCD touchscreen provides local control in multiple languages. The control block carries two RJ45 ports for Ethernet IP or Modbus TCP, plus one RJ45 for Modbus serial. Slot A accepts fieldbus option cards for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Slot B takes encoder interface modules (5/12 V digital, analog, resolver, or HTL). Eight programmable digital inputs (DI1–DI8, 24 V DC) include two configurable as pulse inputs up to 30 kHz. Analog inputs are configurable for 0–10 V DC or 0–20 mA, 12-bit resolution. Three relay outputs (one NO/NC fault, two NO sequence) and configurable analog outputs (0–10 V DC or 0–20 mA, 10-bit) round out the I/O.","metaTitle":"Schneider ATV6000C190A3333NA3 ATV6000, 333 A line, 1520 kW","metaDescription":"Schneider Electric Altivar Process ATV6000 medium voltage drive, 333 A line current (normal duty), 1520 kW motor power, 18-pulse rectifier, floor-standing enclosure. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1500.0 mm","Width":"4460.0 mm","title":"ATV6000C190A3333NA3","Height":"2687.0 mm","Supply":"Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 6 kVA","Marking":"CE EAC","Isolation":"Electrical between power and control","Standards":"IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076","EMC filter":"Integrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power","Input type":"18 pulse diode rectifier bridge","Cable Entry":"Bottom","Noise level":"80 dB","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A: communication module for EtherCAT Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module Slot B: HTL encoder interface module Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module","Output type":"IGBT inverter cells multilevel PWM","description":"Medium Voltage Variable Speed Drive ATV6000 - 3.3 kV - 1900 kVA","Display type":"10 inch LCD touch screen multi-language","Line current":"333 A normal duty 266 A heavy duty","Maximum THDI":"<3 % conforming to IEEE 519-1992","Power factor":"96","Power losses":"66.1 kW normal duty 53.1 kW heavy duty","Apparent power":"1900 kVA","Assembly style":"In floor-standing enclosure","Connector type":"2 RJ45 (on the control block) for Ethernet IP/Modbus TCP 1 RJ45 (on the control block) for Modbus serial","Motor power kW":"1520 kW for normal duty 1220 kW for heavy duty","Output voltage":"<= power supply voltage","Protection type":"Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV6000","Supply frequency":"50 Hz +/- 5 %","Device short name":"ATV6000","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Relay output type":"Configurable relay logic R1: fault relay NO/NC Configurable relay logic R2: sequence relay NO Configurable relay logic R3: sequence relay NO","Operating altitude":"1000...2000 m with derating factor","Provided equipment":"Power cells Phase-shifting transformer Cooling fans Human machine interface Medium voltage arrestors Enclosure Plinth","Analogue input type":"configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution: 12 bits configurable current: 0...20 mA, impedance: 250 Ohm, resolution: 12 bits","Colour of enclosure":"Light grey (RAL 7035)","Discrete input type":"DI1...DI8 programmable, 24 V DC ( DI7, DI8 programmable as pulse input: 0...30 kHz, 24 V DC ( POEA, POEB PWM output enable, 24 V DC (<= 30 V), impedance: > 2.2 kOhm","Product destination":"Permanent magnet motors Asynchronous motors Synchronous motors","Relay output number":"3","Analogue output type":"Configurable voltage: 0...10 V DC impedance 470 Ohm, resolution 10 bits Configurable current: 0...20 mA impedance 500 Ohm, resolution 10 bits","Discrete output type":"Logic output <= 30 V DC 100 mA","Frequency resolution":"0.01 Hz","Overvoltage category":"II conforming to IEC 61800-5-1 motor side III conforming to IEC 61800-5-1 line side III conforming to IEC 61800-5-1 low voltage connections","Prospective line Isc":"31.5 kA for 150 ms","Discrete input number":"10","Volume of cooling air":"15564 m3/h","Analogue output number":"2","Discrete output number":"2","Energy efficiency ratio":"0.985 inverter 0.96 total drive including transformer","IP degree of protection":"IP31 conforming to IEC 60529","Network number of phases":"3 phases","Continuous output current":"320 A normal duty 256 A heavy duty","Maximum transient current":"480 A during 3 s (normal duty) 480 A during 3 s (heavy duty)","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"3.3 kV +/- 10 %","Communication port protocol":"Ethernet IP/Modbus TCP Modbus serial","Environmental characteristic":"3K3 conforming to IEC 60721-3-3 3B1 conforming to IEC 60721-3-3 3C2 conforming to IEC 60721-3-3 3S1 conforming to IEC 60721-3-3 3M1 conforming to IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0.1...120 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor","Asynchronous motor control profile":"Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop","Ambient air temperature for storage":"0...50 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 3 s (normal duty) 1.5 x In during 60 s (heavy duty) 1.8 x In during 3 s (heavy duty)","Ambient air temperature for operation":"0...40 °C 40...50 °C with derating factor -25...70 °C during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/ca/en/product/download-pdf/ATV6000C190A3333NA3?filename=Schneider+Electric_Altivar-Process-ATV6000_ATV6000C190A3333NA3.pdf', 'path_name': '67269a47b808d62080ad3c6ea4bffc5d.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/67269a47b808d62080ad3c6ea4bffc5d.pdf', 'status': 1}","sourceUrl":"https://www.se.com/be/en/product/ATV6000C190A3333NA3/medium-voltage-variable-speed-drive-atv6000-3-3-kv-1900-kva/"},"ai":{"faq":[{"question":"What are the key electrical ratings?","answer":"Line current is 333 A normal duty / 266 A heavy duty. Motor power is 1520 kW normal duty / 1220 kW heavy duty. Apparent power is 1900 kVA. Input THDI is below 3%."},{"question":"What compliance documentation is available?","answer":"The drive carries CE and EAC marking and conforms to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076."},{"question":"What is the physical size of the enclosure?","answer":"The floor-standing enclosure measures 4460 mm wide, 2687 mm high, and 1500 mm deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000C190A3333NA3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000C190A3333NA3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}