{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000C288A6666ND","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000C288A6666ND","canonicalUrl":"https://aoctrl.com/schneider/ATV6000C288A6666ND","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000C288A6666ND","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000, AC Drive (VFD) 480V, 3-phase, 2300 kW normal duty / 2140 kW heavy duty, 30-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## 30-pulse rectifier and harmonic compliance The ATV6000C288A6666ND: The 30-pulse diode rectifier front end keeps input current THDI below 3% per IEEE 519-1992, so you can skip the external harmonic filter on most utility feeds. Line current draw is 234 A in heavy-duty profile, 252 A in normal duty — size the upstream transformer and cabling for the higher figure plus the transformer's own magnetizing inrush. ## Motor power and duty cycling Rated 2300 kW normal duty, 2140 kW heavy duty — the heavy-duty ceiling is the one that governs continuous process loads like pumps or compressors where the drive must ride through a 150% overload for 60 seconds. The IGBT inverter cells use multilevel PWM, which gives a cleaner output waveform and reduces motor bearing stress compared to a two-level topology. ## Physical footprint and installation planning This is a floor-standing enclosure, 108.3 inches tall, 183.5 inches wide, 63.0 inches deep. That footprint plus the 83 dB noise level and 100 kW heat rejection at normal duty means the drive needs its own room with forced ventilation or a dedicated HVAC zone — it will not share a cabinet with PLCs or low-voltage controls. ## Lifecycle and procurement posture No direct drop-in substitute exists from Schneider; the ATV6000 family is the active platform for this power class.","metaTitle":"Schneider ATV6000C288A6666ND AC Drive 480V, 2300 kW","metaDescription":"Schneider Electric ATV6000C288A6666ND Altivar Process AC Drive, 480V 3-phase, 2300 kW normal duty, 30-pulse rectifier, THDI <3%, CULus/CE/UKCA. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"63.0 in (1600.0 mm)","Width":"183.5 in (4660.0 mm)","Height":"108.3 in (2751.0 mm)","Phases":"3-phase","Current":"234 A heavy duty 252 A normal duty","Frequency":"50 Hz +/- 5 %","IP Rating":"IP31","Input Type":"30 pulse diode rectifier bridge","Display Type":"10 inch LCD touch screen multi-language","Connector Type":"2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"50 °C","Temp Storage Min":"0 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"32...122 °F (0...50 °C)","Ambient Air Temperature Operation":"32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/ATV6000C288A6666ND/medium-voltage-variable-speed-drive-atv6000-6-6-kv-3084-hp-ul-certification/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6000C288A6666ND/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000C288A6666ND","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000C288A6666ND when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}