{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000C328A3333NA3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000C328A3333NA3","canonicalUrl":"https://aoctrl.com/schneider/ATV6000C328A3333NA3","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000C328A3333NA3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000 AC Drive, ATV6000C328A3333NA3, 2620 kW normal duty / 2100 kW heavy duty, 3280 kVA, 480 V class, 18-pulse diode rectifier, floor-standing enclosure.","salesMarkdown":"## Power stage and motor ratings The ATV6000C328A3333NA3: Rated 2620 kW for normal duty and 2100 kW for heavy duty, with an apparent power of 3280 kVA. The line current draw is 574 A at normal duty, 458 A at heavy duty — these numbers govern the incoming cable and transformer sizing, not the motor FLA alone. The 18-pulse diode rectifier input keeps total harmonic current distortion below 3 % per IEEE 519-1992, which means you can often skip an external harmonic filter on a dedicated transformer. Power factor is 0.96. ## Physical footprint and enclosure This is a floor-standing enclosure, not a wall-mount drive. Dimensions: 5760 mm wide, 1700 mm deep, 2791 mm high. Plan for a dedicated electrical room bay with front and rear access for cable entry from the bottom and forced-convection cooling airflow. Sound pressure level is 85 dB — hearing protection zones apply around the drive during operation. ## Controls, communications, and I/O The standard HMI is a 10-inch LCD colour touchscreen with multi-language support. Communication slots accept Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT on Slot A; encoder feedback modules (digital, analog, resolver, HTL) on Slot B. Built-in Ethernet IP/Modbus TCP on two RJ45 ports plus one dedicated Modbus serial RJ45. The 8 digital inputs include two programmable as pulse inputs up to 30 kHz; analogue inputs are configurable 0–10 V or 0–20 mA. Three configurable relay outputs (one NO/NC fault relay, two NO sequence relays) plus configurable analogue outputs (0–10 V / 0–20 mA). ## Protection suite and compliance The drive monitors line overvoltage, undervoltage, phase loss, DC bus overvoltage, transformer thermal overload, cabinet overtemperature, overcurrent, overload, short-circuit, and motor earth fault. Each IGBT power cell has its own thermal protection. Marked EAC and CE. Designed to IEC 61800-3 (EMC), IEC 61800-4, IEC 61800-5-1 (safety), and IEC 60529 (enclosure). Pollution degree 2 per IEC 61800-5-1. Integrated EMC filter meets category C3 on the control side and C4 on the power side.","metaTitle":"Schneider ATV6000C328A3333NA3 VFD, 2620 kW, 3280 kVA, 480V","metaDescription":"Schneider Electric ATV6000C328A3333NA3 Altivar Process ATV6000 AC Drive. 2620 kW normal duty, 3280 kVA apparent power, 18-pulse input. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1700.0 mm","Width":"5760.0 mm","title":"ATV6000C328A3333NA3","Height":"2791.0 mm","Supply":"Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 26 kVA","Marking":"EAC CE","Isolation":"Electrical between power and control","Standards":"IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076","EMC filter":"Integrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power","Input type":"18 pulse diode rectifier bridge","Cable Entry":"Bottom","Noise level":"85 dB","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A: communication module for EtherCAT Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module Slot B: HTL encoder interface module Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module","Output type":"IGBT inverter cells multilevel PWM","description":"Medium Voltage Variable Speed Drive ATV6000 - 3.3 kV - 3280 kVA","Display type":"10 inch LCD touch screen multi-language","Line current":"574 A normal duty 458 A heavy duty","Maximum THDI":"<3 % conforming to IEEE 519-1992","Power factor":"96","Power losses":"113.8 kW normal duty 91.3 kW heavy duty","Apparent power":"3280 kVA","Assembly style":"In floor-standing enclosure","Connector type":"2 RJ45 (on the control block) for Ethernet IP/Modbus TCP 1 RJ45 (on the control block) for Modbus serial","Motor power kW":"2620 kW for normal duty 2100 kW for heavy duty","Output voltage":"<= power supply voltage","Protection type":"Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV6000","Supply frequency":"50 Hz +/- 5 %","Device short name":"ATV6000","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Relay output type":"Configurable relay logic R1: fault relay NO/NC Configurable relay logic R2: sequence relay NO Configurable relay logic R3: sequence relay NO","Operating altitude":"1000...2000 m with derating factor","Provided equipment":"Power cells Phase-shifting transformer Cooling fans Human machine interface Medium voltage arrestors Enclosure Plinth","Analogue input type":"configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution: 12 bits configurable current: 0...20 mA, impedance: 250 Ohm, resolution: 12 bits","Colour of enclosure":"Light grey (RAL 7035)","Discrete input type":"DI1...DI8 programmable, 24 V DC ( DI7, DI8 programmable as pulse input: 0...30 kHz, 24 V DC ( POEA, POEB PWM output enable, 24 V DC (<= 30 V), impedance: > 2.2 kOhm","Product destination":"Asynchronous motors Permanent magnet motors Synchronous motors","Relay output number":"3","Analogue output type":"Configurable voltage: 0...10 V DC impedance 470 Ohm, resolution 10 bits Configurable current: 0...20 mA impedance 500 Ohm, resolution 10 bits","Discrete output type":"Logic output <= 30 V DC 100 mA","Frequency resolution":"0.01 Hz","Overvoltage category":"II conforming to IEC 61800-5-1 motor side III conforming to IEC 61800-5-1 line side III conforming to IEC 61800-5-1 low voltage connections","Prospective line Isc":"31.5 kA for 150 ms","Discrete input number":"10","Volume of cooling air":"30600 m3/h","Analogue output number":"2","Discrete output number":"2","Energy efficiency ratio":"0.985 inverter 0.96 total drive including transformer","IP degree of protection":"IP31 conforming to IEC 60529","Network number of phases":"3 phases","Continuous output current":"550 A normal duty 440 A heavy duty","Maximum transient current":"825 A during 3 s (normal duty) 825 A during 3 s (heavy duty)","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"3.3 kV +/- 10 %","Communication port protocol":"Ethernet IP/Modbus TCP Modbus serial","Environmental characteristic":"3K3 conforming to IEC 60721-3-3 3B1 conforming to IEC 60721-3-3 3C2 conforming to IEC 60721-3-3 3S1 conforming to IEC 60721-3-3 3M1 conforming to IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0.1...120 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor","Asynchronous motor control profile":"Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop","Ambient air temperature for storage":"0...50 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 3 s (normal duty) 1.5 x In during 60 s (heavy duty) 1.8 x In during 3 s (heavy duty)","Ambient air temperature for operation":"0...40 °C 40...50 °C with derating factor -25...70 °C during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/ca/en/product/download-pdf/ATV6000C328A3333NA3?filename=Schneider+Electric_Altivar-Process-ATV6000_ATV6000C328A3333NA3.pdf', 'path_name': '48fae3c411976ac167d2a4e14b1a97c0.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/48fae3c411976ac167d2a4e14b1a97c0.pdf', 'status': 1}","sourceUrl":"https://www.se.com/be/en/product/ATV6000C328A3333NA3/medium-voltage-variable-speed-drive-atv6000-3-3-kv-3280-kva/"},"ai":{"faq":[{"question":"What is the physical size of this drive?","answer":"The floor-standing enclosure measures 5760 mm wide by 1700 mm deep by 2791 mm high. Cable entry is from the bottom. Plan for a dedicated electrical room footprint with front and rear access."},{"question":"What fieldbus options are available?","answer":"Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Two RJ45 ports on the control block support Ethernet IP/Modbus TCP, plus one dedicated Modbus serial RJ45 port."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000C328A3333NA3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000C328A3333NA3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}