{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000C375A1111NA3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000C375A1111NA3","canonicalUrl":"https://aoctrl.com/schneider/ATV6000C375A1111NA3","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000C375A1111NA3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000, ATV6000C375A1111NA3, medium voltage drive, 3000 kW normal duty, 3750 kVA, 54-pulse diode rectifier, IGBT multilevel PWM.","salesMarkdown":"The Schneider Electric ATV6000C375A1111NA3 is a medium voltage drive from the Altivar Process ATV6000 range, rated for 3000 kW normal duty and 2540 kW heavy duty, with an apparent power of 3750 kVA. It uses a 54-pulse diode rectifier bridge on the input and IGBT inverter cells with multilevel PWM on the output, keeping input current THDI below 3% per IEEE 519-1992. The 3750 kVA apparent power tells you the transformer and cable sizing upstream need to handle that full-load kVA, not just the motor kW. Line current is 197 A normal duty, 166 A heavy duty, so the incoming feeder and fusing should be specced for at least the normal-duty figure. ## Installation and compliance Cable entry is at the bottom. The drive includes an integrated EMC filter: category C3 on the control side, C4 on the power side. Standards compliance covers IEC 61800-3 (EMC), IEC 61800-5-1 (safety), and IEEE 519-1992 (harmonic distortion). Marked CE and EAC. The 10-inch LCD touch screen is the local HMI; the control block has two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial. Option card slots A and B accept communication modules (PROFIBUS, PROFINET, EtherCAT, DeviceNet, CANopen) and encoder interfaces (digital 5/12 V, analog, resolver, HTL).","metaTitle":"Schneider ATV6000C375A1111NA3 ATV6000, 3000 kW MV Drive","metaDescription":"Schneider Electric ATV6000C375A1111NA3 medium voltage drive, 3000 kW normal duty, 3750 kVA. 54-pulse rectifier, THDI <3%. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1700.0 mm","Width":"6660.0 mm","Height":"2751.0 mm","Supply":"Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 8 kVA","Marking":"CE EAC","Isolation":"Electrical between power and control","Standards":"IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076","EMC filter":"Integrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power","Input type":"54 pulse diode rectifier bridge","Cable Entry":"Bottom","Noise level":"83 dB","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A: communication module for EtherCAT Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module Slot B: HTL encoder interface module Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module","Output type":"IGBT inverter cells multilevel PWM","Display type":"10 inch LCD touch screen multi-language","Line current":"166 A heavy duty 197 A normal duty","Maximum THDI":"<3 % conforming to IEEE 519-1992","Power factor":"96","Power losses":"130.4 kW normal duty 110.5 kW heavy duty","Apparent power":"3750 kVA","Assembly style":"In floor-standing enclosure","Connector type":"2 RJ45 (on the control block) for Ethernet IP/Modbus TCP 1 RJ45 (on the control block) for Modbus serial","Motor power kW":"3000 kW for normal duty 2540 kW for heavy duty","Output voltage":"<= power supply voltage","Protection type":"Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV6000","Supply frequency":"50 Hz +/- 5 %","Device short name":"ATV6000","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Relay output type":"Configurable relay logic R1: fault relay NO/NC Configurable relay logic R2: sequence relay NO Configurable relay logic R3: sequence relay NO","Operating altitude":"1000...2000 m with derating factor","Provided equipment":"Power cells Phase-shifting transformer Cooling fans Human machine interface Medium voltage arrestors Enclosure Plinth","Analogue input type":"configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution: 12 bits configurable current: 0...20 mA, impedance: 250 Ohm, resolution: 12 bits","Colour of enclosure":"Light grey (RAL 7035)","Discrete input type":"DI1...DI8 programmable, 24 V DC ( DI7, DI8 programmable as pulse input: 0...30 kHz, 24 V DC ( POEA, POEB PWM output enable, 24 V DC (<= 30 V), impedance: > 2.2 kOhm","Product destination":"Permanent magnet motors Asynchronous motors Synchronous motors","Relay output number":"3","Analogue output type":"Configurable voltage: 0...10 V DC impedance 470 Ohm, resolution 10 bits Configurable current: 0...20 mA impedance 500 Ohm, resolution 10 bits","Discrete output type":"Logic output <= 30 V DC 100 mA","Frequency resolution":"0.01 Hz","Overvoltage category":"II conforming to IEC 61800-5-1 motor side III conforming to IEC 61800-5-1 line side III conforming to IEC 61800-5-1 low voltage connections","Prospective line Isc":"31.5 kA for 150 ms","Discrete input number":"10","Volume of cooling air":"25848 m3/h","Analogue output number":"2","Discrete output number":"2","Energy efficiency ratio":"0.985 inverter 0.96 total drive including transformer","IP degree of protection":"IP31 conforming to IEC 60529","Network number of phases":"3 phases","Continuous output current":"160 A heavy duty 188 A normal duty","Maximum transient current":"300 A during 3 s (heavy duty) 282 A during 3 s (normal duty)","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"11 kV +/- 10 %","Communication port protocol":"Ethernet IP/Modbus TCP","Environmental characteristic":"3K3 conforming to IEC 60721-3-3 3B1 conforming to IEC 60721-3-3 3C2 conforming to IEC 60721-3-3 3S1 conforming to IEC 60721-3-3 3M1 conforming to IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0.1...120 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor","Asynchronous motor control profile":"Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop","Ambient air temperature for storage":"0...50 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 3 s (normal duty) 1.5 x In during 60 s (heavy duty) 1.8 x In during 3 s (heavy duty)","Ambient air temperature for operation":"0...40 °C 40...50 °C with derating factor -25...70 °C during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/ATV6000C375A1111NA3/medium-voltage-variable-speed-drive-atv6000-11-kv-3750-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6000C375A1111NA3/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Motor power is 3000 kW normal duty, 2540 kW heavy duty. Apparent power is 3750 kVA. Line current is 197 A normal duty, 166 A heavy duty. Input THDI is below 3%."},{"question":"What compliance documentation does the ATV6000C375A1111NA3 carry?","answer":"It is marked CE and EAC, and conforms to IEC 61800-3, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076."},{"question":"What are the physical dimensions of this drive?","answer":"Height 2751 mm, depth 1700 mm, width 6660 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000C375A1111NA3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000C375A1111NA3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}