{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000D630A6666ND","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000D630A6666ND","canonicalUrl":"https://aoctrl.com/schneider/ATV6000D630A6666ND","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000D630A6666ND","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000 AC drive, ATV6000D630A6666ND, 500 kW normal duty / 470 kW heavy duty, 630 kVA, 3-phase, floor-standing enclosure, 10-inch LCD touch screen.","salesMarkdown":"## 630 kVA drive for medium-voltage motor control The ATV6000D630A6666ND is a 630 kVA Altivar Process ATV6000 drive rated 500 kW normal duty and 470 kW heavy duty, using a 30-pulse diode rectifier front end and IGBT inverter cells with multilevel PWM output. Total harmonic current distortion is below 3% per IEEE 519-1992, and the power factor is 0.96 — the multi-pulse topology cleans the line without an external filter for most installations. ## Floor-standing enclosure with integrated transformer The drive ships in a floor-standing enclosure measuring 103.03 in high by 108.7 in wide by 55.1 in deep, with bottom cable entry and forced-convection cooling. Provided equipment includes the phase-shifting transformer, power cells, cooling fans, plinth, medium-voltage arrestors, and the HMI — the enclosure is a complete assembly, not a bare drive chassis. ## 10-inch touch screen and multi-protocol comms The HMI is a 10-inch LCD multi-language touch screen; the control block carries two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial, plus slot A supports Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT option cards. Slot B accepts encoder interface modules (digital 5/12 V, analog, resolver, HTL) and I/O or relay extension modules — the drive can be configured for closed-loop speed or position control without an external controller. ## Protection coverage and compliance Protection includes line supply overvoltage/undervoltage/phase loss, DC bus overvoltage, cabinet overheating, overcurrent, overload, short-circuit, motor thermal, motor phase break, motor earth fault, and fan monitoring. Marked CULus, CE, and UKCA; designed to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A. Pollution degree 2 per IEC 61800-5-1.","metaTitle":"Schneider ATV6000D630A6666ND AC Drive, 500 kW, 630 kVA, 480V","metaDescription":"Schneider Electric ATV6000D630A6666ND Altivar Process ATV6000 AC drive. 500 kW normal duty, 630 kVA, 3-phase, floor-standing enclosure. CULus CE UKCA.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"55.1 in (1400.0 mm)","Phase":"3 phase","Width":"108.7 in (2760.0 mm)","title":"ATV6000D630A6666ND","Height":"103.03 in (2617.0 mm)","Supply":"Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA","Marking":"CULus CE UKCA","Isolation":"Electrical between power and control","Standards":"IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076 UL 347A","EMC filter":"Integrated IEC 61800-3 category C3 control Integrated IEC 61800-3 category C4 Power","Input type":"30 pulse diode rectifier bridge","Cable Entry":"Bottom","Noise level":"80 dB","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A communication module EtherCAT Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module Slot B HTL encoder interface module Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","Output type":"IGBT inverter cells multilevel PWM","description":"Medium Voltage Variable Speed Drive ATV6000, 6.6 kV, 670 hp, UL certification","Display type":"10 inch LCD touch screen multi-language","Line current":"55.2 A normal duty 52 A heavy duty","Maximum THDI":"<3 % IEEE 519-1992","Power factor":"96","Power losses":"21.9 kW normal duty 20.5 kW heavy duty","Apparent power":"630 kVA","Assembly style":"In floor-standing enclosure","Connector type":"2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial","Motor power kW":"500 kW normal duty 470 kW heavy duty","Output voltage":"<= power supply voltage","Protection type":"Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overvoltages on the DC bus drive Thermal overload for transformer drive Cabinet overheating drive Overcurrent drive Overload drive Short-circuit protection drive IGBT for each cell drive Thermal protection motor Motor phase break motor Motor earth fault motor Break on the control circuit drive Fan monitoring drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 IEC 61800-5-1","Range of Product":"Altivar Process ATV6000","Supply frequency":"50 Hz +/- 5 %","Device short name":"ATV6000","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Relay output type":"Configurable relay logic R1 fault relay NO/NC Configurable relay logic R2 sequence relay NO Configurable relay logic R3 sequence relay NO","Operating altitude":"3280.84...6561.68 ft (1000...2000 m) with derating factor","Provided Equipment":"Power cells Medium voltage arrestors Enclosure Plinth Cooling fans Phase-shifting transformer Human machine interface","Analogue input type":"configurable voltage 0...10 V DC 30 kOhm 12 bits configurable current 0...20 mA 250 Ohm 12 bits","Colour of enclosure":"Light grey RAL 7035)","Discrete input type":"DI1...DI8 programmable, 24 V DC DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC POEA, POEB PWM output enable, 24 V DC 2.2 kOhm","Product destination":"Asynchronous motors Synchronous motors Permanent magnet motors","Relay output number":"3","Analogue output type":"Configurable voltage 0...10 V DC 470 Ohm 10 bits Configurable current 0...20 mA 500 Ohm 10 bits","Discrete output type":"Logic output <= 30 V DC 100 mA","Frequency resolution":"0.01 Hz","Overvoltage category":"II IEC 61800-5-1 motor side III IEC 61800-5-1 line side III IEC 61800-5-1 low voltage connections","Prospective line Isc":"31.5 kA 150 ms","Discrete input number":"10","Volume of cooling air":"2705064.6 Gal/hr(US) (10239.6 m3/h)","Analogue output number":"2","Discrete output number":"2","Energy efficiency ratio":"0.985 inverter 0.96 total drive including transformer","IP degree of protection":"IP31 conforming to IEC 60529","Continuous output current":"52.3 A normal duty 50 A heavy duty","Maximum transient current":"78.4 A 3 s normal duty) 93.8 A 3 s heavy duty)","Product or Component Type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6.6 kV +/- 10 %","Maximum Horse Power Rating":"630.0 hp heavy duty 670.0 hp normal duty","Communication Port Protocol":"Ethernet IP/Modbus TCP","Environmental characteristic":"3K3 conforming to IEC 60721-3-3 3B1 conforming to IEC 60721-3-3 3C2 conforming to IEC 60721-3-3 3S1 conforming to IEC 60721-3-3 3M1 conforming to IEC 60721-3-3","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...120 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor","Asynchronous motor control profile":"Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop","Ambient Air Temperature for Storage":"32...122 °F (0...50 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 3 s normal duty) 1.5 x In 60 s heavy duty) 1.8 x In 3 s heavy duty)","Ambient air temperature for operation":"32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/us/en/product/download-pdf/ATV6000D630A6666ND?filename=Schneider+Electric_Altivar-Process-ATV6000_ATV6000D630A6666ND.pdf', 'path_name': 'd37b2ca6389bd99d957f8efe92279885.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/d37b2ca6389bd99d957f8efe92279885.pdf', 'status': 1}","sourceUrl":"https://www.se.com/us/en/product/ATV6000D630A6666ND/medium-voltage-variable-speed-drive-atv6000-6-6-kv-670-hp-ul-certification/"},"ai":{"faq":[{"question":"What is the ATV6000D630A6666ND used for?","answer":"It is a medium-voltage AC drive for asynchronous, synchronous, and permanent magnet motors up to 500 kW normal duty or 470 kW heavy duty, typically installed in pump, fan, compressor, and conveyor applications requiring low line harmonics."},{"question":"What compliance documentation does Schneider provide for this drive?","answer":"The drive carries CULus, CE, and UKCA markings and is designed to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000D630A6666ND","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000D630A6666ND when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}