{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000D750A4242ND","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000D750A4242ND","canonicalUrl":"https://aoctrl.com/schneider/ATV6000D750A4242ND","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000D750A4242ND","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000, model ATV6000D750A4242ND, 750 kVA apparent power, 3-phase input, 24-pulse diode rectifier, 600 kW normal duty / 480 kW heavy duty, floor-standing enclosure.","salesMarkdown":"The Schneider Electric ATV6000D750A4242ND is a current-production Altivar Process ATV6000 medium-voltage drive, delivering 750 kVA apparent power with a 24-pulse diode rectifier input that keeps line THDI below 3% per IEEE 519-1992 — no external filter needed for that spec. It's rated 600 kW normal duty, 480 kW heavy duty, with a 96% power factor and an integrated EMC filter (C3 control side, C4 power). The enclosure sits at 104.7 x 99.9 x 55.1 inches and includes the phase-shifting transformer, power cells, cooling fans, HMI, and cabinet cooling. The 600 kW normal duty / 480 kW heavy duty rating sets the continuous and overload capability — heavy duty for constant-torque loads (conveyors, extruders) and normal duty for variable-torque (pumps, fans). The 24-pulse input, combined with the phase-shifting transformer, suppresses the 5th and 7th harmonics to meet IEEE 519 without an active front end. Protection covers line over/undervoltage, phase loss, DC bus overvoltage, thermal overload on the transformer, cabinet overtemperature, output overcurrent/short-circuit, IGBT faults, motor phase/earth faults, and fan monitoring. The 10-inch LCD touchscreen provides multi-language access to diagnostics and commissioning. Marked CULus, CE, UKCA — suitable for North American and European installations. Standards include IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEEE 519, and UL 347A. The isolation between power and control is electrical. Pollution degree 2 per IEC 61800-5-1.","metaTitle":"Schneider ATV6000D750A4242ND Altivar Process drive, 750 kVA","metaDescription":"Schneider Electric ATV6000D750A4242ND Altivar Process drive, 750 kVA apparent power, 600 kW normal duty / 480 kW heavy duty, 24-pulse input, <3% THDI, CULus CE UKCA. Current produc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"55.1 in (1400.0 mm)","Phase":"3 phase","Width":"104.7 in (2660.0 mm)","title":"ATV6000D750A4242ND","Height":"99.9 in (2537.0 mm)","Supply":"Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for cooling fan 400 V AC +/- 10 % 3 kVA External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 %","Marking":"CULus CE UKCA","Isolation":"Electrical between power and control","Standards":"IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076 UL 347A","EMC filter":"Integrated IEC 61800-3 category C3 control Integrated IEC 61800-3 category C4 Power","Input type":"24 pulse diode rectifier bridge","Cable Entry":"Bottom","Noise level":"80 dB","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A communication module EtherCAT Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module Slot B HTL encoder interface module Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","Output type":"IGBT inverter cells multilevel PWM","description":"Medium Voltage Variable Speed Drive ATV6000, 4.16 kV, 804 hp, UL certification","Display type":"10 inch LCD touch screen multi-language","Line current":"83 A heavy duty 104 A normal duty","Maximum THDI":"<3 % IEEE 519-1992","Power factor":"96","Power losses":"26.2 kW normal duty 20.9 kW heavy duty","Apparent power":"750 kVA","Assembly style":"In floor-standing enclosure","Connector type":"2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial","Motor power kW":"600 kW normal duty 480 kW heavy duty","Output voltage":"<= power supply voltage","Protection type":"Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overvoltages on the DC bus drive Thermal overload for transformer drive Cabinet overheating drive Overcurrent drive Overload drive Short-circuit protection drive IGBT for each cell drive Thermal protection motor Motor phase break motor Motor earth fault motor Break on the control circuit drive Fan monitoring drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 IEC 61800-5-1","Range of Product":"Altivar Process ATV6000","Supply frequency":"50 Hz +/- 5 %","Device short name":"ATV6000","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Relay output type":"Configurable relay logic R1 fault relay NO/NC Configurable relay logic R2 sequence relay NO Configurable relay logic R3 sequence relay NO","Operating altitude":"3280.84...6561.68 ft (1000...2000 m) with derating factor","Provided Equipment":"Plinth Phase-shifting transformer Medium voltage arrestors Power cells Cooling fans Enclosure Human machine interface","Analogue input type":"configurable voltage 0...10 V DC 30 kOhm 12 bits configurable current 0...20 mA 250 Ohm 12 bits","Colour of enclosure":"Light grey RAL 7035)","Discrete input type":"DI1...DI8 programmable, 24 V DC DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC POEA, POEB PWM output enable, 24 V DC 2.2 kOhm","Product destination":"Permanent magnet motors Asynchronous motors Synchronous motors","Relay output number":"3","Analogue output type":"Configurable voltage 0...10 V DC 470 Ohm 10 bits Configurable current 0...20 mA 500 Ohm 10 bits","Discrete output type":"Logic output <= 30 V DC 100 mA","Frequency resolution":"0.01 Hz","Overvoltage category":"II IEC 61800-5-1 motor side III IEC 61800-5-1 line side III IEC 61800-5-1 low voltage connections","Prospective line Isc":"31.5 kA 150 ms","Discrete input number":"10","Volume of cooling air":"1948039.6 Gal/hr(US) (7374 m3/h)","Analogue output number":"2","Discrete output number":"2","Energy efficiency ratio":"0.985 inverter 0.96 total drive including transformer","IP degree of protection":"IP31 conforming to IEC 60529","Continuous output current":"80 A heavy duty 100 A normal duty","Maximum transient current":"150 A 3 s heavy duty) 150 A 3 s normal duty)","Product or Component Type":"Medium voltage variable speed drive","[Us] rated supply voltage":"4.16 kV +/- 10 %","Maximum Horse Power Rating":"643.0 hp heavy duty 804.0 hp normal duty","Communication Port Protocol":"Ethernet IP/Modbus TCP","Environmental characteristic":"3K3 conforming to IEC 60721-3-3 3B1 conforming to IEC 60721-3-3 3C2 conforming to IEC 60721-3-3 3S1 conforming to IEC 60721-3-3 3M1 conforming to IEC 60721-3-3","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...120 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor","Asynchronous motor control profile":"Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop","Ambient Air Temperature for Storage":"32...122 °F (0...50 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 3 s normal duty) 1.5 x In 60 s heavy duty) 1.8 x In 3 s heavy duty)","Ambient air temperature for operation":"32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/us/en/product/download-pdf/ATV6000D750A4242ND?filename=Schneider+Electric_Altivar-Process-ATV6000_ATV6000D750A4242ND.pdf', 'path_name': '532eb68dc67cf748e378b9a941107610.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/532eb68dc67cf748e378b9a941107610.pdf', 'status': 1}","sourceUrl":"https://www.se.com/us/en/product/ATV6000D750A4242ND/medium-voltage-variable-speed-drive-atv6000-4-16-kv-804-hp-ul-certification/"},"ai":{"faq":[{"question":"What compliance markings does the ATV6000D750A4242ND carry?","answer":"It carries CULus, CE, and UKCA markings, plus conformance with IEC 61800-3, IEC 61800-5-1, IEEE 519, and UL 347A."},{"question":"What is the line THDI of the ATV6000D750A4242ND?","answer":"Less than 3% at rated load, meeting IEEE 519-1992 limits, thanks to the 24-pulse rectifier."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000D750A4242ND","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000D750A4242ND when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}