{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6000D890A6060NA3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6000D890A6060NA3","canonicalUrl":"https://aoctrl.com/schneider/ATV6000D890A6060NA3","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6000D890A6060NA3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV6000, ATV6000D890A6060NA3, medium-voltage drive, 890 kVA, 710 kW normal duty, floor-standing enclosure.","salesMarkdown":"The Schneider Electric ATV6000D890A6060NA3 is a medium-voltage Altivar Process ATV6000 drive rated for 890 kVA apparent power, delivering 710 kW for normal duty and 670 kW for heavy duty induction, synchronous, or permanent magnet motors. The input stage uses a 30-pulse diode rectifier bridge, keeping total harmonic current distortion (THDI) below 3% per IEEE 519-1992 without an external filter. It ships in a floor-standing enclosure (2760 mm wide × 2617 mm high × 1400 mm deep) with integrated phase-shifting transformer, power cells, cooling fans, and a 10-inch LCD touch screen HMI. ## Integration notes Two option card slots (A and B) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, or I/O and relay extensions. The control block includes two RJ45 ports for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial. Eight programmable digital inputs (24 V DC, two configurable as pulse inputs up to 30 kHz) and configurable analog inputs (0–10 V or 0–20 mA, 12-bit) handle the control interface. Three relay outputs (one NO/NC fault, two NO sequence) are standard. Electrical isolation between power and control circuits is maintained. The drive meets IEC 61800-3, IEC 61800-4, IEC 61800-5-1, and IEC 60529; the integrated EMC filter conforms to category C3 (control) and C4 (power). ## Ratings & protection Line current is 85.7 A normal duty / 81 A heavy duty. Power losses are 30.9 kW (normal) and 29.2 kW (heavy). Forced convection cooling keeps the enclosure within ratings; noise level is 80 dB. Protection covers line supply overvoltage/undervoltage/phase loss, DC bus overvoltage, transformer thermal overload, cabinet overheating, overcurrent, overload, short-circuit, motor phase break, motor earth fault, and fan monitoring.","metaTitle":"Schneider ATV6000D890A6060NA3 ATV6000 Drive, 890 kVA, 710 kW","metaDescription":"Schneider Electric Altivar Process ATV6000 medium-voltage drive, 890 kVA apparent power, 710 kW normal duty. Active lifecycle. 30-pulse rectifier, <3% THDI. Floor-standing enclosur","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Depth":"1400.0 mm","Width":"2760.0 mm","Height":"2617.0 mm","Supply":"Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA","Marking":"CE EAC","Isolation":"Electrical between power and control","Standards":"IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076","EMC filter":"Integrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power","Input type":"30 pulse diode rectifier bridge","Cable Entry":"Bottom","Noise level":"80 dB","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A: communication module for EtherCAT Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module Slot B: HTL encoder interface module Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module","Output type":"IGBT inverter cells multilevel PWM","Display type":"10 inch LCD touch screen multi-language","Line current":"85.7 A normal duty 81 A heavy duty","Maximum THDI":"<3 % conforming to IEEE 519-1992","Power factor":"96","Power losses":"30.9 kW normal duty 29.2 kW heavy duty","Apparent power":"890 kVA","Assembly style":"In floor-standing enclosure","Connector type":"2 RJ45 (on the control block) for Ethernet IP/Modbus TCP 1 RJ45 (on the control block) for Modbus serial","Motor power kW":"710 kW for normal duty 670 kW for heavy duty","Output voltage":"<= power supply voltage","Protection type":"Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV6000","Supply frequency":"50 Hz +/- 5 %","Device short name":"ATV6000","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Relay output type":"Configurable relay logic R1: fault relay NO/NC Configurable relay logic R2: sequence relay NO Configurable relay logic R3: sequence relay NO","Operating altitude":"1000...2000 m with derating factor","Provided equipment":"Power cells Plinth Enclosure Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface","Analogue input type":"configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution: 12 bits configurable current: 0...20 mA, impedance: 250 Ohm, resolution: 12 bits","Colour of enclosure":"Light grey (RAL 7035)","Discrete input type":"DI1...DI8 programmable, 24 V DC ( DI7, DI8 programmable as pulse input: 0...30 kHz, 24 V DC ( POEA, POEB PWM output enable, 24 V DC (<= 30 V), impedance: > 2.2 kOhm","Product destination":"Asynchronous motors Synchronous motors Permanent magnet motors","Relay output number":"3","Analogue output type":"Configurable voltage: 0...10 V DC impedance 470 Ohm, resolution 10 bits Configurable current: 0...20 mA impedance 500 Ohm, resolution 10 bits","Discrete output type":"Logic output <= 30 V DC 100 mA","Frequency resolution":"0.01 Hz","Overvoltage category":"II conforming to IEC 61800-5-1 motor side III conforming to IEC 61800-5-1 line side III conforming to IEC 61800-5-1 low voltage connections","Prospective line Isc":"31.5 kA for 150 ms","Discrete input number":"10","Volume of cooling air":"9889 m3/h","Analogue output number":"2","Discrete output number":"2","Energy efficiency ratio":"0.985 inverter 0.96 total drive including transformer","IP degree of protection":"IP31 conforming to IEC 60529","Network number of phases":"3 phases","Continuous output current":"81.7 A normal duty 78 A heavy duty","Maximum transient current":"123 A during 3 s (normal duty) 146 A during 3 s (heavy duty)","Product or component type":"Medium voltage variable speed drive","[Us] rated supply voltage":"6 kV +/- 10 %","Communication port protocol":"Ethernet IP/Modbus TCP","Environmental characteristic":"3K3 conforming to IEC 60721-3-3 3B1 conforming to IEC 60721-3-3 3C2 conforming to IEC 60721-3-3 3S1 conforming to IEC 60721-3-3 3M1 conforming to IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0.1...120 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor","Asynchronous motor control profile":"Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop","Ambient air temperature for storage":"0...50 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 3 s (normal duty) 1.5 x In during 60 s (heavy duty) 1.8 x In during 3 s (heavy duty)","Ambient air temperature for operation":"0...40 °C 40...50 °C with derating factor -25...70 °C during transport"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/ATV6000D890A6060NA3/medium-voltage-variable-speed-drive-atv6000-6-kv-890-kva/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6000D890A6060NA3/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the ATV6000D890A6060NA3?","answer":"Apparent power is 890 kVA, motor power is 710 kW for normal duty and 670 kW for heavy duty. Line current is 85.7 A normal / 81 A heavy."},{"question":"What compliance standards does the ATV6000D890A6060NA3 meet?","answer":"It is marked CE and EAC, and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, and IEEE 519:1992."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6000D890A6060NA3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6000D890A6060NA3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}