{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630C16N4F","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630C16N4F","canonicalUrl":"https://aoctrl.com/schneider/ATV630C16N4F","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630C16N4F","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630, ATV630C16N4F, variable speed drive, 160 kW normal duty / 132 kW heavy duty, 302 A continuous output, 380-440 V, IP21, floor-standing.","salesMarkdown":"## 160 kW VFD for process and utilities The Schneider Electric ATV630C16N4F is a 160 kW normal-duty variable speed drive from the Altivar Process ATV600 series, designed for asynchronous and synchronous motors in process and utility applications. It delivers 302 A continuous output at 2.5 kHz for normal duty and 250 A for heavy duty, fed from a 380-440 V supply at 50/60 Hz. The drive includes integrated STO (Safe Torque Off) rated SIL 3 per IEC 61800-5-2, meeting the safety circuit requirements for machinery guarding and hazard zone isolation without external contactors. ## Ratings and real-world fit The 302 A continuous output at 2.5 kHz switching frequency sets the thermal ceiling for normal-duty applications like pumps and fans; for heavy-duty loads such as conveyors or compressors, the drive is rated 250 A at the same switching frequency. Line current draw is 251 A at 400 V for normal duty and 210 A for heavy duty — these figures govern the upstream cable and breaker sizing, not the motor nameplate. The integrated EMC filter supports motor cable runs up to 150 m while maintaining Category C3 compliance per IEC 61800-3, which is typical for industrial environments with a dedicated transformer or separate building supply. Output frequency range is 0.1 to 500 Hz, covering standard induction motor speed control as well as high-speed spindle or centrifuge applications. Floor-standing enclosure with IP21 protection per IEC 60529 — suitable for indoor, clean industrial environments where drips and falling dirt are the main ingress risks, but not for washdown or outdoor placement. Forced-convection cooling moves 720 m³/h of air; the drive must be mounted vertically within ±10° and have clear space around the ventilation grilles to avoid recirculating hot exhaust air. Ambient operating range is -15 to 40 °C without derating, extending to 50 °C with a derating factor applied. Above 1000 m altitude, derate 1 % per 100 m up to 4800 m. ## Communication and I/O flexibility Slot A accepts fieldbus option cards for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen, or Ethernet Powerlink, while the base unit includes Ethernet Modbus TCP and Modbus serial ports. Eight digital inputs are standard, with DI7 and DI8 programmable as 0-30 kHz pulse inputs for encoder or flowmeter feedback. An adjustable PID regulator is built in, allowing closed-loop control of pressure, level, or flow without an external controller. Compliance documentation includes CE marking and standards IEC 60204-1, IEC 61800-2, IEC 61800-3, and IEC 61800-5-1.","metaTitle":"Schneider Electric ATV630C16N4F Altivar Process 160 kW VFD","metaDescription":"Schneider Electric ATV630C16N4F variable speed drive, 160 kW normal duty, 302 A continuous output, 380-440 V, IP21, STO SIL 3. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV630C16N4F","Marking":"CE","Variant":"Standard version","Standards":"IEC 60204-1 IEC 61800-2 IEC 61800-3 IEC 61800-5-1","EMC filter":"Integrated with 150 m conforming to IEC 61800-3 category C3","Noise level":"69 dB","Option card":"Slot A: communication module, Profibus DP V1 Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink","description":"variable speed drive, Altivar Process ATV600, ATV630, 160kW, 380 to 440V, IP21","Line current":"251 A at 400 V (normal duty) 210 A at 400 V (heavy duty) 291 A at 380 V (normal duty) 244 A at 380 V (heavy duty)","Maximum THDI":"<48 % full load conforming to IEC 61000-3-12","Mounting mode":"Floor-standing","Motor power kW":"160 kW (normal duty) 132 kW (heavy duty)","Regulation loop":"Adjustable PID regulator","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2","Range of product":"Altivar Process ATV600","Shock resistance":"15 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV630","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Discrete input type":"DI7, DI8 programmable as pulse input: 0...30 kHz, 24 V DC ( 1 MOhm 500 V DC for 1 minute to earth","Product destination":"Asynchronous motors Synchronous motors","Overvoltage category":"III","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Discrete input number":"8","Volume of cooling air":"720 m3/h","Nominal Output Current":"302.0 A","IP degree of protection":"IP21 conforming to IEC 61800-5-1 IP21 conforming to IEC 60529","Continuous output current":"302 A at 2.5 kHz for normal duty 250 A at 2.5 kHz for heavy duty","Product or component type":"Variable speed drive","[Us] rated supply voltage":"380...440 V","Communication port protocol":"Ethernet Modbus TCP Modbus serial","Product specific application":"Process and utilities","Speed drive output frequency":"0.1...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-25...70 °C","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-15...40 °C (without derating) 40...50 °C (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"40 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"6 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$20,202.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV630C16N4F/variable-speed-drive-altivar-process-atv600-atv630-160kw-380-to-440v-ip21/"},"ai":{"faq":[{"question":"What is the ATV630C16N4F used for?","answer":"It is a variable speed drive for asynchronous and synchronous motors in process and utility applications such as pumps, fans, conveyors, and compressors, rated 160 kW normal duty."},{"question":"What safety functions does the ATV630C16N4F include?","answer":"It includes Safe Torque Off (STO) rated SIL 3, which removes torque-producing power from the motor without external contactors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630C16N4F","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630C16N4F when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}