{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630C16N4US","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630C16N4US","canonicalUrl":"https://aoctrl.com/schneider/ATV630C16N4US","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630C16N4US","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630C16N4US variable speed drive, 380–480 V, 160 kW normal duty, 302 A continuous output, IP00, integrated EMC filter C3.","salesMarkdown":"The ATV630C16N4US sits in the Altivar Process ATV600 family, a standard version drive for asynchronous and synchronous motors. It is rated 160 kW normal duty and 132 kW heavy duty at 380–480 VAC – the difference drives your sizing: use the normal duty figure for continuous pump/fan loads and the heavy duty figure when you need 150% overload for 60 seconds. The continuous output current is 302 A at 2.5 kHz (normal duty) and 250 A at 2.5 kHz (heavy duty), so the current rating already builds in the switching frequency derating. The integrated EMC filter meets IEC 61800-3 category C3 and is rated for 150 m of motor cable. That is enough to keep conducted emissions from the drive off your sensor lines if you maintain separation between the motor and control cable trays. If you see noise on a 4–20 mA loop near this drive, check the shield bond at the drive end before swapping the sensor – the filter is usually adequate up to that cable length. Safety function STO (safe torque off) with SIL3 capability is built in without an external module. That means you can wire the drive into a safety circuit without a separate safety relay, but verify the wiring matches the SIL3 logic: two independent paths for the STO request. ## Duty profile comparison: normal vs heavy The drive is rated 160 kW normal duty and 132 kW heavy duty. Line current at 480 V is 262 A for normal duty and 213 A for heavy duty. ## Integration notes – mounting, cooling, wiring Wall-mount only, IP00 (IP21 with an optional kit). Requires forced convection cooling with 600 m3/h airflow – leave clearance above and below the heatsink. Ambient relative humidity allowed 5–95% non-condensing. Vibration: 1.5 mm peak-to-peak at 2–13 Hz, 1 gn at 13–200 Hz. Shock: 15 gn for 11 ms. 8 discrete inputs, two configurable as pulse inputs up to 30 kHz. The base unit includes Modbus serial, Modbus TCP, and Ethernet IP; other fieldbus via option cards. The adjustable PID regulator is built in, so you can run closed-loop pressure or flow control without an external controller on simple loops.","metaTitle":"Schneider ATV630C16N4US Altivar Process Drive, 160 kW","metaDescription":"Altivar Process ATV630C16N4US variable speed drive, 160 kW normal duty at 380–480 V. Current lifecycle stage, sourced to order via RFQ. Integrated EMC filter C3, STO SIL3, Modbus/E","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV630C16N4US","Marking":"CE","Variant":"Standard version","Category":"US1CP4E22206","Standards":"UL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 492.1 ft (150 m) IEC 61800-3 category C3","Noise level":"69.9 dB","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module Slot A communication module, Ethernet IP/Modbus TCP/MD-Link communication module, BACnet MS/TP communication module, Ethernet Powerlink","description":"Variable Speed Drive, Altivar Process ATV600, ATV630, 160kW, 250hp, 380 to 480V, IP00 [TAA, BABA]","Line current":"284 A 380 V normal duty) 262 A 480 V normal duty) 237 A 380 V heavy duty) 213 A 480 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Mounting Mode":"Wall mount","Motor power kW":"160 kW normal duty) 132 kW heavy duty)","Regulation loop":"Adjustable PID regulator","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2","Range of Product":"Altivar Process ATV600","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV630","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Discrete input type":"DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC 1 MOhm 500 V DC for 1 minute to earth","Product destination":"Asynchronous motors Synchronous motors","Overvoltage category":"III","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Compliance/Compliance":"TAA BABA BAA via COTS","Discrete input number":"8","Nbr. of units in pkg.":"1","Volume of cooling air":"158506.07 Gal/hr(US) (600 m3/h)","Nominal Output Current":"302.0 A","IP degree of protection":"IP00IEC 61800-5-1 IP00IEC 60529 IP21 with kit VW3A9704)IEC 61800-5-1 IP21 with kit VW3A9704)IEC 60529","Continuous output current":"302 A 2.5 kHz normal duty 250 A 2.5 kHz heavy duty","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"380...480 V","Maximum Horse Power Rating":"250 hp normal duty 200 hp heavy duty","Communication Port Protocol":"Modbus serial Modbus TCP Ethernet","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-40...158 °F (-40...70 °C)","Ambient Air Temperature for Storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"60 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/ATV630C16N4US/variable-speed-drive-altivar-process-atv600-atv630-160kw-250hp-380-to-480v-ip00-taa-baba/"},"ai":{"faq":[{"question":"What is the CE marking and variant of this drive?","answer":"It carries CE marking and is the Standard version of the ATV630 process drive series."},{"question":"What compliance standards does this drive meet?","answer":"It complies with UL 508C, IEC 61800-3 (environment 1 category C2 and environment 2 category C3), IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and is TAA BABA BAA compliant via COTS."},{"question":"What is the normal duty power rating versus heavy duty?","answer":"Normal duty is 160 kW (250 hp) with 302 A continuous at 2.5 kHz; heavy duty is 132 kW (200 hp) with 250 A continuous at 2.5 kHz."},{"question":"Does it support safe torque off without an external card?","answer":"Yes, STO (safe torque off) with SIL3 capability is integrated into the drive hardware."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630C16N4US","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630C16N4US when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}