{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630C25N4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630C25N4","canonicalUrl":"https://aoctrl.com/schneider/ATV630C25N4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630C25N4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630, ATV630C25N4 variable speed drive, 481 A continuous output, 380...480 V, 250 kW normal duty, IP00, wall mount.","salesMarkdown":"## What the 481 A continuous output means for your motor load The ATV630C25N4 is a 481 A continuous output drive in the Altivar Process ATV600 family, sized for 250 kW normal duty / 220 kW heavy duty on asynchronous or synchronous motors. That 481 A figure is at 2.5 kHz switching — if you push the carrier frequency higher, the output current derates, so the 481 A is the ceiling for a standard pump or fan application. The line current at 380 V normal duty pulls 451 A; at 480 V normal duty it's 366 A. That spread tells you the drive is current-limited, not voltage-limited — the motor kW rating shifts with the supply voltage. ## Safety and compliance: STO SIL 3 and the standards stack Built-in Safe Torque Off (STO) rated SIL 3 means this drive can serve in a safety circuit without an external safety relay for the torque removal function — it removes rotational energy from the motor shaft per IEC 61508 and ISO 13849-1. That simplifies the panel wiring for a guarding application. The drive carries CE marking and complies with UL 508C, IEC 61800-3 (environment 1 category C2 and environment 2 category C3), plus IEC 61000-3-12 for harmonic limits. The integrated EMC filter is rated for 50 m cable at category C3 — enough for most industrial installations without an external filter. That matters for the site electrical engineer coordinating the SCCR upstream. ## Mounting, cooling, and physical integration Wall-mount chassis, IP00 as shipped — you need the VW3A9113 kit to reach IP21. The drive moves 1260 m³/h of forced-convection cooling air, so the enclosure must have intake and exhaust vents sized for that volume. Operating position is vertical ±10°, which is standard for a wall-mount VFD. Vibration resistance is 1.5 mm peak-to-peak at 2-13 Hz and 1 gn at 13-200 Hz per IEC 60068-2-6; shock is 15 gn for 11 ms per IEC 60068-2-27. That's typical for a drive that goes on a machine frame, not just a control-room floor. ## Fieldbus and I/O: what you can plug into Slot A The drive has a Slot A for communication modules — Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), Ethernet Powerlink, and BACnet MS/TP. The base unit already has Modbus serial and Ethernet, so for a simple Modbus TCP line you don't need an option card. Eight discrete inputs, two of which (DI7, DI8) are programmable as pulse inputs up to 30 kHz. That's enough for a basic encoder feedback or flowmeter input without an extra card. There's also an adjustable PID regulator built in — set it for pressure or flow control and the drive closes the loop itself. Quoted to order against the BOM quantity. No stock-holding claim; sourced per RFQ.","metaTitle":"Schneider Electric ATV630C25N4 Altivar Process VFD, 481 A","metaDescription":"Schneider Electric ATV630C25N4 variable speed drive, 481 A continuous output, 250 kW normal duty. In active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV630C25N4","Marking":"CE","Variant":"Standard version","Category":"US1CP4E22207","Standards":"UL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 164.04 ft (50 m) IEC 61800-3 category C3","Noise level":"76 dB","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module Slot A communication module, Ethernet IP/Modbus TCP/MD-Link communication module, BACnet MS/TP communication module, Ethernet Powerlink","description":"Variable Speed Drive, Altivar Process ATV600, ATV630, 250kW, 400hp, 380 to 480V, IP00","Line current":"451 A 380 V normal duty) 366 A 480 V normal duty) 365 A 380 V heavy duty) 301 A 480 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Mounting Mode":"Wall mount","Motor power kW":"250 kW normal duty) 220 kW heavy duty)","Regulation loop":"Adjustable PID regulator","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2","Range of Product":"Altivar Process ATV600","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV630","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Operating altitude":"3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Discrete input type":"DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC 1 MOhm 500 V DC for 1 minute to earth","Product destination":"Asynchronous motors Synchronous motors","Overvoltage category":"III","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Discrete input number":"8","Nbr. of units in pkg.":"1","Volume of cooling air":"332862.7 Gal/hr(US) (1260 m3/h)","Nominal Output Current":"481.0 A","IP degree of protection":"IP00IEC 61800-5-1 IP00IEC 60529 IP21 with kit VW3A9113)IEC 61800-5-1 IP21 with kit VW3A9113)IEC 60529","Continuous output current":"481 A 2.5 kHz normal duty 387 A 2.5 kHz heavy duty","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"380...480 V","Maximum Horse Power Rating":"400 hp normal duty 300 hp heavy duty","Communication Port Protocol":"Modbus TCP Modbus serial Ethernet","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-40...158 °F (-40...70 °C)","Ambient Air Temperature for Storage":"-13...158 °F (-25...70 °C)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) (without derating) 104...140 °F (40...60 °C) (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"60 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$11,310.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/ATV630C25N4/variable-speed-drive-altivar-process-atv600-atv630-250kw-400hp-380-to-480v-ip00/"},"ai":{"faq":[{"question":"What is ATV630C25N4's listed marking (CE) on this component line?","answer":"The ATV630C25N4 carries CE marking, confirming compliance with applicable European directives for the low-voltage and EMC requirements."},{"question":"What compliance documentation does this brand provide for ATV630C25N4?","answer":"The drive is CE marked and complies with UL 508C, IEC 61800-3 (environments 1 and 2), IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. The integrated EMC filter is rated for 50 m cable at category C3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630C25N4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630C25N4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}