{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630D15M3US","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630D15M3US","canonicalUrl":"https://aoctrl.com/schneider/ATV630D15M3US","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630D15M3US","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630, variable speed drive, 15 kW normal duty / 11 kW heavy duty, 200-240 V, 63.4 A continuous, STO SIL 3, IP21, without EMC filter.","salesMarkdown":"The ATV630D15M3US is a current-production variable speed drive from the Altivar Process ATV600 series, sized for 15 kW normal duty and 11 kW heavy duty on a 200-240 V supply. The continuous output current is 63.4 A at 4 kHz for normal duty; heavy duty drops to 46.8 A at 4 kHz. That derating matters if your application is constant torque or high overload — spec the HD current if the load profile calls for 150 % overload for 60 s. Line current at full normal duty is 52.6 A at 200 V and 45.5 A at 240 V. The drive includes an adjustable PID regulator and is designed for both asynchronous and synchronous motors, making it a fit for process pumps, fans, and compressors where closed-loop control is needed. The unit ships without an integrated EMC filter. For CE-marked installations, plan for an external filter to meet IEC 61800-3 environment 1 category C2 or environment 2 category C3 as listed on the standards list. The IP21 enclosure (UL type 1) suits clean indoor panel or wall-mounted locations. ## Safety, communications, and integration slot options STO (Safe Torque Off) is built in at SIL 3, eliminating the need for an external safety relay for drive shutdown in many machine safety architectures. The drive also complies with IEC 61508 and ISO 13849-1, covering functional safety requirements up to PL e (depending on architecture). Slot A accepts a wide range of communication option cards: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), Ethernet IP/Modbus TCP/MD-Link, BACnet MS/TP, and Ethernet Powerlink. The drive itself includes Ethernet and Modbus serial as standard, so a fieldbus card is only needed for non-native protocols. Slot A and B also accept digital/analog I/O extension and output relay extension modules, giving flexibility for additional feedback or status signals without a remote I/O bank. The eight onboard discrete inputs include two that can be programmed as pulse inputs up to 30 kHz for encoder or flowmeter feedback. ## Mounting, cooling, and derating for altitude and environment Mount vertically with +/- 10 degree tolerance; forced convection cooling moves 240 m3/h (63402.4 Gal/hr(US)). Noise level is 63.5 dB. Operating altitude from 1000 to 4800 m requires current derating of 1 % per 100 m above 1000 m. Ambient temperature range and humidity (5–95 % non-condensing) are per IEC 60068-2-3. Pollution degree 2 (normally non-conductive) covers most industrial panel environments. Vibration resistance: 1.5 mm peak-to-peak at 2–13 Hz, 1 gn at 13–200 Hz. Shock resistance 15 gn for 11 ms. Overvoltage category III means it can be connected directly to the building supply without extra surge suppression in most locations. TAA-compliant (BABA BAA via COTS) for US federal projects.","metaTitle":"Schneider ATV630D15M3US Altivar Process Drive, 15 kW 200-240","metaDescription":"Active production ATV630D15M3US variable speed drive, 200-240V, 15 kW ND, 63.4 A, STO SIL 3, IP21, TAA compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"title":"ATV630D15M3US","Marking":"CE","Variant":"Standard version","Category":"US1CP4E22205","Standards":"UL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Without EMC filter","Noise level":"63.5 dB","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module Slot A communication module, Ethernet IP/Modbus TCP/MD-Link communication module, BACnet MS/TP communication module, Ethernet Powerlink","description":"Variable Speed Drive, Altivar Process ATV600, ATV630, 15kW, 20hp, 200 to 240V, IP21, UL type 1 [TAA, BABA]","Line current":"52.6 A 200 V normal duty) 45.5 A 240 V normal duty) 40.1 A 200 V heavy duty) 34.3 A 240 V heavy duty)","Maximum THDI":"<48 % from 80...100 % of load IEC 61000-3-12","Mounting Mode":"Wall mount","Motor power kW":"15 kW normal duty) 11 kW heavy duty)","Regulation loop":"Adjustable PID regulator","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2","Range of Product":"Altivar Process ATV600","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV630","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Discrete input type":"DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC 1 MOhm 500 V DC for 1 minute to earth","Product destination":"Asynchronous motors Synchronous motors","Degree of protection":"UL type 1 UL 508C","Overvoltage category":"III","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Compliance/Compliance":"TAA BABA BAA via COTS","Discrete input number":"8","Nbr. of units in pkg.":"1","Volume of cooling air":"63402.4 Gal/hr(US) (240 m3/h)","Nominal Output Current":"63.4 A","IP degree of protection":"IP21IEC 61800-5-1 IP21IEC 60529","Continuous output current":"63.4 A 4 kHz normal duty 46.8 A 4 kHz heavy duty","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"200...240 V","Maximum Horse Power Rating":"20 hp normal duty 15 hp heavy duty","Communication Port Protocol":"Ethernet Modbus serial Modbus TCP","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-40...158 °F (-40...70 °C)","Ambient Air Temperature for Storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/ATV630D15M3US/variable-speed-drive-altivar-process-atv600-atv630-15kw-20hp-200-to-240v-ip21-ul-type-1-taa-baba/"},"ai":{"faq":[{"question":"What is its listed marking and variant?","answer":"The marking is CE. The variant is listed as Standard version, meaning it is not a custom or tailored variant."},{"question":"What compliance documentation does it carry?","answer":"The drive is compliant with UL 508C, IEC 61800 series (including environment categories C2 and C3), IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. It is also TAA-compliant (BABA BAA via COTS)."},{"question":"What are the key output ratings for motor sizing?","answer":"Normal duty: 15 kW, 63.4 A continuous at 4 kHz. Heavy duty: 11 kW, 46.8 A at 4 kHz. Maximum THDI is below 48 % from 80 to 100 % load per IEC 61000-3-12."},{"question":"Does this drive include an EMC filter?","answer":"No, it is the 'without EMC filter' variant. An external filter is required for most CE-marked installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630D15M3US","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630D15M3US when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}