{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630D15N4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630D15N4","canonicalUrl":"https://aoctrl.com/schneider/ATV630D15N4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630D15N4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630, ATV630D15N4, 15 kW normal duty / 11 kW heavy duty, 31.7 A nominal output, 380...480 V, IP21, wall mount, standard version.","salesMarkdown":"## What the 31.7 A continuous output means for your motor load The ATV630D15N4 delivers 31.7 A continuous at 4 kHz carrier in normal duty, enough to run a 15 kW (20 hp) induction motor on a pump or fan curve. In heavy-duty applications — conveyors or positive-displacement loads — the same drive outputs 23.5 A at 4 kHz, matching an 11 kW (15 hp) motor. The carrier frequency is adjustable; raising it above 4 kHz derates the continuous current, so the 31.7 A figure is the ceiling for thermal design. Output frequency spans 0.1 to 500 Hz, covering both standard 50/60 Hz induction motors and high-speed synchronous motors up to 30000 rpm equivalent. The adjustable PID regulator on board means closed-loop process control — pressure, flow, or level — without an external controller. ## Safety and EMC integration — STO SIL 3 and built-in filter This removes the motor torque without disconnecting the power wiring — no external safety relay needed for the stop function. The drive also carries UL 508C listing and overvoltage category III, meaning it withstands distribution-level surges on a 480 V panel. The internal EMC filter supports 50 m shielded motor cable at C2 limits (environment 1, category C2) and 150 m at C3 limits (environment 2, category C3). For most industrial installations, this eliminates the need for an external input filter. Total harmonic current distortion (THDI) stays below 48 % from 80 to 100 % load, compliant with IEC 61000-3-12. ## Fieldbus options and I/O complement Slot A accepts plug-in communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (RJ45 or SUB-D 9 or screw terminals), Ethernet Powerlink, or BACnet MS/TP. The drive ships with Ethernet, Modbus serial, and Modbus TCP onboard — no extra module for basic networked control. Eight discrete inputs are standard, with DI7 and DI8 programmable as pulse inputs up to 30 kHz — usable for encoder or flowmeter feedback. Slot A and slot B also accept digital/analog I/O extension modules and output relay extension modules if the onboard I/O count is insufficient. ## Mounting, cooling, and environmental limits Wall-mount only, vertical within ±10 degrees. Forced convection cooling moves 215 m³/h of air — the heatsink needs clearance on both sides for airflow. IP21 protection means indoor installation only; no washdown rating. Operating altitude up to 1000 m without derating, then 1 % current derating per 100 m up to 4800 m. Vibration resistance is 1.5 mm peak-to-peak at 2–13 Hz and 1 gn at 13–200 Hz per IEC 60068-2-6. Shock resistance 15 gn for 11 ms per IEC 60068-2-27. Ambient humidity 5–95 % non-condensing, pollution degree 2 — typical for a clean industrial control room. ## Lifecycle and sourcing — active production, quoted to order The drive carries CE marking, UL 508C listing, and compliance with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. Documentation for RoHS and REACH is available from Schneider Electric on request.","metaTitle":"Schneider ATV630D15N4 AC Drive, 15 kW, 31.7 A, 380-480 V","metaDescription":"Schneider Electric ATV630D15N4 Altivar Process VFD, 15 kW normal duty, 31.7 A output, 380-480 V, STO SIL 3, integrated EMC filter.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"27 A 380 V normal duty) 23.3 A 480 V normal duty) 20.6 A 380 V heavy duty) 18.1 A 480 V heavy duty)","Frequency":"50...60 Hz - 5...5 %","IP Rating":"UL type 1 UL 508C","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"70 °C","Temp Operating Min":"-40 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive","Ambient Air Temperature Operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,058.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/ATV630D15N4/variable-speed-drive-altivar-process-atv600-atv630-15kw-20hp-380-to-480v-ip21-ul-type-1/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV630D15N4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630D15N4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630D15N4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}