{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630U15N4Z","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630U15N4Z","canonicalUrl":"https://aoctrl.com/schneider/ATV630U15N4Z","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630U15N4Z","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630, standard version variable speed drive, ATV630U15N4Z, 1.5 kW normal duty / 0.75 kW heavy duty, 380...480 V, 4 A continuous output, IP20.","salesMarkdown":"The ATV630U15N4Z is a standard-version Altivar Process drive sized for a 1.5 kW normal-duty or 0.75 kW heavy-duty induction or synchronous motor on a 380...480 V three-phase supply. Continuous output current is 4 A at 4 kHz for normal duty; heavy duty drops to 2.2 A at 4 kHz. The integrated EMC filter meets IEC 61800-3 category C2 at cable runs up to 10 m and category C3 up to 50 m, which covers most panel-to-motor distances without an external filter. ## Integration checklist Mount the drive vertically within ±10°; forced-convection cooling draws 38 m³/h of air, so leave clearance above and below the heat sink. The IP20 enclosure is suited for a clean cabinet interior. Eight discrete inputs are provided, with DI7 and DI8 configurable as pulse inputs up to 30 kHz. The onboard PID regulator handles closed-loop process control without an external controller. STO (safe torque off) is rated SIL 3, meeting IEC 61800-5-2 for safe stop applications. ## Communication and options The drive ships with Modbus serial and Modbus TCP/Ethernet as standard. Slot A accepts a range of fieldbus option cards: Profibus DP V1, PROFINET, DeviceNet, CANopen (various terminations), EtherNet/IP, BACnet MS/TP, and Ethernet Powerlink. An I/O extension module or relay output module can also occupy Slot A or Slot B.","metaTitle":"Schneider Electric ATV630U15N4Z Altivar Process Drive, 1.5 k","metaDescription":"ATV630U15N4Z variable speed drive, 1.5 kW normal duty, 4 A output, 380-480 V supply. Active production. STO SIL 3, integrated EMC filter. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV630U15N4Z","Marking":"CE","Variant":"Standard version","Standards":"UL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 32.8 ft (10 m) IEC 61800-3 category C2 Integrated 164.04 ft (50 m) IEC 61800-3 category C3 With EMC plate option","Noise level":"54.5 dB","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module Slot A communication module, Ethernet IP/Modbus TCP/MD-Link communication module, BACnet MS/TP communication module, Ethernet Powerlink","description":"variable speed drive, Altivar Process ATV600, ATV630, cabinet Integration, IP20, 1.5kW, 380 to 480 V","Line current":"3 A 380 V normal duty) 2.6 A 480 V normal duty) 1.7 A 380 V heavy duty) 1.5 A 480 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Mounting Mode":"Cabinet mount","Assembly style":"With heat sink","Motor power kW":"1.5 kW normal duty) 0.75 kW heavy duty)","Regulation loop":"Adjustable PID regulator","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2","Range of Product":"Altivar Process ATV600","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV630","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Discrete input type":"DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC 1 MOhm 500 V DC for 1 minute to earth","Product destination":"Asynchronous motors Synchronous motors","Overvoltage category":"III","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Discrete input number":"8","Nbr. of units in pkg.":"1","Volume of cooling air":"10038.7 Gal/hr(US) (38 m3/h)","Nominal Output Current":"4.0 A","IP degree of protection":"IP20IEC 61800-5-1 IP20IEC 60529","Continuous output current":"4 A 4 kHz normal duty 2.2 A 4 kHz heavy duty","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"380...480 V","Maximum Horse Power Rating":"2 hp normal duty 1 hp heavy duty","Communication Port Protocol":"Modbus TCP Ethernet Modbus serial","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-40...158 °F (-40...70 °C)","Ambient Air Temperature for Storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/77091e1c6736f0d2bf8eb14bb5367137.pdf","sourceUrl":"https://www.se.com/us/en/product/ATV630U15N4Z/variable-speed-drive-altivar-process-atv600-atv630-cabinet-integration-ip20-1-5kw-380-to-480-v/"},"ai":{"faq":[{"question":"What are the key electrical ratings for this drive?","answer":"Rated supply voltage is 380...480 V at 50/60 Hz. Motor power is 1.5 kW normal duty and 0.75 kW heavy duty. Continuous output current is 4 A at 4 kHz for normal duty and 2.2 A at 4 kHz for heavy duty."},{"question":"What safety functions does the ATV630U15N4Z support?","answer":"It includes STO (safe torque off) rated SIL 3, compliant with IEC 61800-5-2."},{"question":"What communication protocols are available on this drive?","answer":"Standard protocols are Modbus serial and Modbus TCP/Ethernet. Optional Slot A cards add Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherNet/IP, BACnet MS/TP, or Ethernet Powerlink."},{"question":"What standards and certifications does the ATV630U15N4Z comply with?","answer":"It is CE marked and complies with UL 508C, IEC 61800-3 (environment categories C2 and C3), IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630U15N4Z","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630U15N4Z when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}