{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV630U40M3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV630U40M3","canonicalUrl":"https://aoctrl.com/schneider/ATV630U40M3","factsUrl":"https://aoctrl.com/api/mcp/products/ATV630U40M3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV630, variable speed drive, 200-240 V supply, 4 kW normal duty / 3 kW heavy duty motor power, IP21, integral STO SIL 3.","salesMarkdown":"The ATV630U40M3 is an active-production Altivar Process ATV600 drive sized for 200-240 V three-phase supply, delivering 18.7 A continuous at 4 kHz (normal duty) or 13.7 A (heavy duty), corresponding to 4 kW and 3 kW motor power respectively. It ships without an internal EMC filter, so plan for an external filter or cabling mitigation if the installation must meet IEC 61800-3 Category C2 or C3 limits — the drive is certified to both environments, meaning the EMC performance depends on the filter you add. Wall-mount only, IP21 enclosure (UL Type 1), forced convection cooling drawing 38 m³/h of air. Mount vertical ±10°. Ambient humidity 5-95% non-condensing; altitude derating starts at 1000m, 1% per 100m up to 4800m. These bounds define where the drive can be panel-mounted without additional conditioning. Safety function STO (Safe Torque Off) integrated, SIL 3 capable. That eliminates a separate safety relay on many packaging lines with E-stops or guard interlocks. Discrete I/O includes 8 inputs, two programmable as 0-30 kHz pulse inputs, plus Modbus serial and Modbus TCP/Ethernet as standard communication ports. The drive carries CE marking and is listed under UL 508C. It complies with IEC 61800-3 for both environment 1 category C2 and environment 2 category C3 — note that the as-shipped unit has no EMC filter, so achieving the lower emission limits will require an external filter. Additional standards covered: IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic current limits), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety). The variant is standard version. ## Integration Notes Wall-mount vertical ±10°, forced convection cooling at 38 m3/h; output frequency 0.1-500 Hz. Slots A and B accept communication modules (Profibus, PROFINET, DeviceNet, Modbus TCP, CANopen, Ethernet IP, BACnet MS/TP, Powerlink) or I/O/relay extensions.","metaTitle":"Schneider ATV630U40M3 Altivar Process VSD, 200-240V, 4kW/3kW","metaDescription":"Active-production Altivar Process ATV630 variable speed drive, 200-240V supply, 4kW normal duty / 3kW heavy duty, IP21, STO SIL3, multiple IEC/UL standards. CE marked. Source via R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Marking":"CE","Variant":"Standard version","Category":"US1CP4E22205","Standards":"UL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Without EMC filter","Noise level":"54.5 dB","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module Slot A communication module, Ethernet IP/Modbus TCP/MD-Link communication module, BACnet MS/TP communication module, Ethernet Powerlink","Line current":"15.1 A 200 V normal duty) 12.9 A 240 V normal duty) 11.7 A 200 V heavy duty) 10.2 A 240 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Mounting Mode":"Wall mount","Motor power kW":"4 kW normal duty) 3 kW heavy duty)","Regulation loop":"Adjustable PID regulator","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Pollution degree":"2","Range of Product":"Altivar Process ATV600","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV630","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Discrete input type":"DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC 1 MOhm 500 V DC for 1 minute to earth","Product destination":"Asynchronous motors Synchronous motors","Degree of protection":"UL type 1 UL 508C","Overvoltage category":"III","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Discrete input number":"8","Nbr. of units in pkg.":"1","Volume of cooling air":"10038.7 Gal/hr(US) (38 m3/h)","Nominal Output Current":"18.7 A","IP degree of protection":"IP21IEC 61800-5-1 IP21IEC 60529","Continuous output current":"18.7 A 4 kHz normal duty 13.7 A 4 kHz heavy duty","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"200...240 V","Maximum Horse Power Rating":"5 hp normal duty 4 hp heavy duty","Communication Port Protocol":"Modbus TCP Ethernet Modbus serial","Product Specific Application":"Process and utilities","Speed drive output frequency":"0.1...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-40...158 °F (-40...70 °C)","Ambient Air Temperature for Storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$642.62","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c5f4be581b3bc3b98ae02e77b539bb79.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV630U40M3/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does the ATV630U40M3 carry?","answer":"It is CE marked, UL 508C listed, and complies with IEC 61800-3 (environments 1 category C2 and 2 category C3), IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1."},{"question":"What is the ATV630U40M3's listed marking and variant?","answer":"Marking is CE; variant is Standard version."},{"question":"Can the ATV630U40M3 be used for synchronous motors?","answer":"Yes, the product destination lists both asynchronous and synchronous motors."},{"question":"What is the maximum output frequency of the ATV630U40M3?","answer":"The speed drive output frequency range is 0.1 to 500 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV630U40M3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV630U40M3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}