{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0C11Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0C11Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0C11Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0C11Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Altivar Process ATV600, ATV6A0C11Q6, Modular version, 110 kW at 690 V normal duty, 118 A line current, STO SIL3, integrated EMC filter category C3.","salesMarkdown":"ATV6A0C11Q6 is a cabinet-mount Altivar Process ATV600 drive delivering 110 kW at 690 V normal duty (90 kW heavy duty). Line current draws 118 A at 690 V normal duty, 100 A heavy duty — those figures govern supply cable sizing and branch protection. The integrated EMC filter meets IEC 61800-3 category C3, which covers most industrial distribution without external add-ons. Safety function STO SIL3 is built in, no external safety relay required for machine stop circuits. Communication flexibility: slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP, or CANopen module; slot A/B can take digital/analog I/O or relay extension. That gives network integration options without changing the base drive SKU. Cabinet mount only (UL type 1 or 12 with cabinet integration). Forced convection cooling — ensure clearance for airflow. Line side connection via screw terminals or M10 bar; motor connection via M10 bars. Control wiring: removable screw terminals, 0.5…1.5 mm². Switching frequency adjustable 2…4.9 kHz with derating factor — higher frequencies reduce motor noise but increase dissipation. The drive's protection suite includes thermal, overcurrent, short-circuit, overvoltage, undervoltage, phase loss, and overspeed. One power module and control unit kit with mechanical mounting parts and fuse set included.","metaTitle":"Schneider ATV6A0C11Q6 Altivar Process 110kW 690V Drive","metaDescription":"Active production ATV6A0C11Q6 110kW 690V drive, STO SIL3, integrated C3 EMC filter. Sourced to order. Compliance IEC 61800-5-1, IEC 61508.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6A0C11Q6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, single 690 V, 110 kW","Line current":"118.0 A 690 V normal duty) 100.0 A 690 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"141 kVA at 690 V normal duty 120 kVA at 690 V heavy duty","Motor power kW":"110.0 kW at 690 V normal duty 90.0 kW at 690 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 2100 W 2.5 kHz normal duty) Forced convection 1770 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"125.0 A at 2.5 kHz normal duty 105.0 A at 2.5 kHz heavy duty","Maximum transient current":"137.5 A 60 s normal duty) 157.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 15...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV6A0C11Q6/variable-speed-drive-altivar-process-atv600-apm-single-690-v-110-kw/"},"ai":{"faq":[{"question":"What is the CE marking on this product?","answer":"ATV6A0C11Q6 carries CE marking per the field records."},{"question":"What variant is the ATV6A0C11Q6?","answer":"It is the Modular version of the Altivar Process ATV600 range."},{"question":"What compliance documentation is available for this drive?","answer":"The drive complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. CE marking is listed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0C11Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0C11Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}