{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0C11S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0C11S6","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0C11S6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0C11S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 series, ATV6A0C11S6 modular AC drive, 125 hp normal duty at 600 V, 112 A line current, STO SIL 3, cabinet mount.","salesMarkdown":"## 125 hp at 600 V — normal and heavy duty ratings The ATV6A0C11S6 delivers 125 hp in normal duty and 100 hp in heavy duty at 600 V, with corresponding line currents of 112 A and 92 A. The apparent power at normal duty is 116 kVA, dropping to 96 kVA under heavy duty — this difference matters when sizing the upstream transformer and feeder cables for the actual load profile. The drive accepts synchronous and asynchronous motors, with an adjustable switching frequency between 2 and 4.9 kHz that carries a derating factor — raising the carrier to quiet motor whine reduces the continuous output current, so the heavy-duty current rating is the safer starting point for a fan or pump load. ## STO SIL 3 and integrated EMC filter The drive also integrates an EMC filter compliant with IEC 61800-3 category C3, supporting motor cable runs up to 300 m without an external output filter — a practical saving on long conveyor or pump runs. The drive carries CE marking and complies with UL 61800-5-1, IEC 61800-5-1, and IEC 61000-3-12 for harmonic current emissions, with a maximum THDI below 48% at full load. This covers both European and North American installation requirements from a single unit. ## Modular architecture and fieldbus options The modular variant includes a control unit, power module, mechanical mounting kits, and a set of fuses — the power module is rated 200 kW. Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (with RJ45, SUB-D 9, or screw terminal variants), plus digital/analog I/O and relay extension modules. Native Modbus serial (2-wire RS 485, RTU frame, 1–247 addresses) and Modbus TCP over Ethernet IP (10/100 Mbit/s) are on board, so the drive can join a mixed-fieldbus line without an extra gateway for the primary control network. ## Protection coverage and environmental limits The drive protects against motor thermal overload, phase loss, short circuit, earth faults, DC bus overvoltage, line supply undervoltage/overvoltage, phase loss, overspeed, and control circuit break. The prospective line short-circuit current rating is 50 kA — this sets the SCCR floor for the panel label. Operating altitude is limited to 2000 m with derating above 1000 m; ambient relative humidity range is 5–95% without condensation. Vibration resistance is 1.5 mm peak-to-peak at 2–13 Hz and 0.5 gn at 13–200 Hz per IEC 60068-2-6, with shock resistance of 4 gn at 11 ms per IEC 60068-2-27.","metaTitle":"Schneider Electric ATV6A0C11S6 AC Drive, 125 HP, 600 V","metaDescription":"Schneider Electric ATV6A0C11S6 Altivar Process ATV600 drive, 125 HP normal duty at 600 V, 112 A line current, integrated EMC filter, STO SIL 3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6A0C11S6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, single 600 V, 125 hp","Line current":"112.0 A 600 V normal duty) 92.0 A 600 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"116 kVA at 600 V normal duty 96 kVA at 600 V heavy duty","Motor power hp":"125.0 hp at 600 V normal duty 100.0 hp at 600 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 2190 W 2.5 kHz normal duty) Forced convection 1880 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"125.0 A at 2.5 kHz normal duty 105.0 A at 2.5 kHz heavy duty","Maximum transient current":"137.5 A 60 s normal duty) 157.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"600 V - 15...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ca/en/product/ATV6A0C11S6/variable-speed-drive-altivar-process-atv600-apm-single-600-v-125-hp/"},"ai":{"faq":[{"question":"Where can I buy ATV6A0C11S6 and how do I get a price?","answer":"The ATV6A0C11S6 is sourced to order against your BOM quantity through independent distribution."},{"question":"What fieldbus options are available for ATV6A0C11S6?","answer":"Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen (RJ45, SUB-D 9, or screw terminal). Native Modbus serial and Modbus TCP are onboard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0C11S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0C11S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}