{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0C11T4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0C11T4","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0C11T4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0C11T4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Altivar Process ATV600, ATV6A0C11T4, modular drive, 110 kW normal duty (150 hp) at 480 V, STO SIL3, integrated EMC filter category C3.","salesMarkdown":"## What this drive delivers The Schneider Altivar Process ATV6A0C11T4 is an active-production modular drive rated 110 kW normal duty (150 hp) at 480 V, with heavy-duty 90 kW (125 hp) capability. It integrates STO SIL3 and a C3 EMC filter for 300 m cable runs. Line current pulls 168 A at 480 V normal duty, 145 A heavy duty, so panel feed and branch protection follow those numbers. Apparent power sits at 140 kVA normal duty. ## Mounting and supply requirements Cabinet mount, forced-convection cooled. The control section needs a 24 V DC external supply for digital inputs (19...30 V), plus internal 24 V for STO and digital inputs (21...27 V) with <200 mA short-circuit protection. An internal 10.5 V DC reference supply handles a 1 to 10 kOhm potentiometer. Analog inputs are software-configurable for 0-10 V or 0/4-20 mA with 12-bit resolution; accuracy holds ±0.6% over a 60 °C temperature variation. Six discrete inputs are programmable, with two capable of pulse inputs up to 30 kHz. Relay outputs R1 (fault) and R2, R3 (sequence) are configurable, rated 5 ms ±0.5 ms refresh. Slot A accepts communication modules for Profibus, PROFINET, DeviceNet, Modbus TCP, or CANopen.","metaTitle":"Schneider ATV6A0C11T4 Process Drive, 110 kW, STO SIL3","metaDescription":"Active production drive for 110 kW/150 hp motors. Normal/heavy duty, STO SIL3, integrated EMC filter C3. Quoted to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV6A0C11T4","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), <200 mA overload and short-circuit protection","Marking":"CE","Variant":"Modular version","Accuracy":"+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, single 480 V, 150 hp","Line current":"168.0 A 480 V normal duty) 145.0 A 480 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Refresh time":"Relay output R1, R2, R3)5 ms +/- 0.5 ms)","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"140 kVA at 480 V normal duty 121 kVA at 480 V heavy duty","Motor power hp":"150.0 hp at 480 V normal duty 125.0 hp at 480 V heavy duty","Motor power kW":"110.0 kW at 480 V normal duty 90.0 kW at 480 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 power module 160 kW 1 control unit mechanical mounting kits power connection set of fuses","Linearity error":"AI1, AI2, AI3 +/- 0.15 % of maximum value analog input AO1, AO2 +/- 0.2 % analog output","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Local signalling":"3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"7 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Relay output type":"Configurable relay logic R1 fault relay NO/NC 100000 cycles Configurable relay logic R2 sequence relay NO 100000 cycles Configurable relay logic R3 sequence relay NO 100000 cycles","Sampling duration":"2 ms +/- 0.5 ms DI1...DI4) - discrete input 5 ms +/- 1 ms DI5, DI6) - discrete input 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input 10 ms +/- 1 ms AO1) - analog output","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Analogue input type":"AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits","Discrete input type":"DI1...DI6 programmable, 24 V DC DI5, DI6 programmable as pulse input 0...30 kHz, 24 V DC STOA, STOB safe torque off, 24 V DC 2.2 kOhm","Input compatibility":"DI1...DI6 discrete input level 1 PLC IEC 61131-2 DI5, DI6 discrete input level 1 PLC IEC 65A-68 STOA, STOB discrete input level 1 PLC IEC 61131-2","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz with derating factor 2...8 kHz adjustable","Analogue output type":"Software-configurable voltage AO1, AO2 0...10 V DC 470 Ohm 10 bits Software-configurable current AO1, AO2 0...20 mA 10 bits","Discrete input logic":"Positive logic (source) DI1...DI6), < 5 V, > 11 V Negative logic (sink) DI1...DI6), > 16 V, < 10 V Positive logic (source) DI5, DI6), < 0.6 V, > 2.5 V Positive logic (source) STOA, STOB), < 5 V, > 11 V","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 2730 W 2.5 kHz normal duty) Forced convection 2180 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"211.0 A at 2.5 kHz normal duty 173.0 A at 2.5 kHz heavy duty","Maximum switching current":"Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC","Maximum transient current":"232.1 A 60 s normal duty) 259.5 A 60 s heavy duty)","Minimum switching current":"Relay output R1, R2, R3 5 mA 24 V DC","Product or component type":"Variable speed drive","[Us] rated supply voltage":"480 V - 15...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/ca/en/product/download-pdf/ATV6A0C11T4?filename=Schneider+Electric_Altivar-Process-ATV600_ATV6A0C11T4.pdf', 'path_name': '414ee4c6cdacc3e1dd87540d7fa611e2.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/414ee4c6cdacc3e1dd87540d7fa611e2.pdf', 'status': 1}","sourceUrl":"https://www.se.com/ca/en/product/ATV6A0C11T4/variable-speed-drive-altivar-process-atv600-apm-single-480-v-150-hp/"},"ai":{"faq":[{"question":"What supply voltages are required for the control section?","answer":"Digital inputs need an external 24 V DC supply (19...30 V). STO and internal digital input supply is also 24 V DC (21...27 V) with <200 mA short-circuit protection. A separate 10.5 V DC reference is provided for a potentiometer (1 to 10 kOhm)."},{"question":"What safety function does this drive support?","answer":"Safe Torque Off (STO) rated SIL 3, integrated into the drive."},{"question":"Which compliance standards does it meet?","answer":"CE marked, conforms to IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508 (functional safety), and IEC 13849-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0C11T4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0C11T4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}