{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0C35T4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0C35T4","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0C35T4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0C35T4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600, modular drive, ATV6A0C35T4, 550 hp normal duty at 480 V, integrated EMC filter, STO SIL 3, open-protocol communication slots.","salesMarkdown":"## Integration brief The Schneider ATV6A0C35T4 is a modular Altivar Process ATV600 drive rated for 550 hp at 480 V normal duty (450 hp heavy duty), drawing 586 A normal duty line current. It speaks native Modbus serial (RS-485 RTU) and 10/100 Ethernet IP/Modbus TCP via the embedded port, and accepts slot-A option cards for Profibus, PROFINET, DeviceNet, CANopen, or Modbus TCP/EtherNet/IP — so it folds into any BMS without a gateway hack. Safety is built in: Safe Torque Off (STO) rated SIL 3 per IEC 61508, using dedicated 24 V DC inputs on STOA/STOB. That saves an external safety relay for basic stop functions. Cabinet-mounted with forced convection cooling. Digital inputs are 24 V DC (19–30 V), the analog inputs are software-configurable 0–10 V or 0/4–20 mA with 12-bit resolution. Internal supplies include a 10.5 V DC reference for a 1–10 kΩ potentiometer and a separate 24 V DC supply for digital inputs and STO, all short-circuit protected under 200 mA. It operates over 50/60 Hz ±5% supply, at altitudes up to 4800 m with derating (1% per 100 m above 1000 m). Pollution degree 2 per IEC 61800-5-1.","metaTitle":"Schneider ATV6A0C35T4 Altivar Process 600, 550 HP","metaDescription":"Schneider ATV6A0C35T4 Altivar Process ATV600 drive, 550 hp at 480 V normal duty, integrated EMC filter, STO SIL3, open-protocol slots. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV6A0C35T4","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), <200 mA overload and short-circuit protection","Marking":"CE","Variant":"Modular version","Accuracy":"+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"71 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, single 480 V, 550 hp","Line current":"586.0 A 480 V normal duty) 486.0 A 480 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Refresh time":"Relay output R1, R2, R3)5 ms +/- 0.5 ms)","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"487 kVA at 480 V normal duty 404 kVA at 480 V heavy duty","Motor power hp":"550.0 hp at 480 V normal duty 450.0 hp at 480 V heavy duty","Motor power kW":"355.0 kW at 480 V normal duty 280.0 kW at 480 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 3 power module 160 kW 2 front cover","Linearity error":"AI1, AI2, AI3 +/- 0.15 % of maximum value analog input AO1, AO2 +/- 0.2 % analog output","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Local signalling":"3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"7 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Relay output type":"Configurable relay logic R1 fault relay NO/NC 100000 cycles Configurable relay logic R2 sequence relay NO 100000 cycles Configurable relay logic R3 sequence relay NO 100000 cycles","Sampling duration":"2 ms +/- 0.5 ms DI1...DI4) - discrete input 5 ms +/- 1 ms DI5, DI6) - discrete input 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input 10 ms +/- 1 ms AO1) - analog output","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Analogue input type":"AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits","Discrete input type":"DI1...DI6 programmable, 24 V DC DI5, DI6 programmable as pulse input 0...30 kHz, 24 V DC STOA, STOB safe torque off, 24 V DC 2.2 kOhm","Input compatibility":"DI1...DI6 discrete input level 1 PLC IEC 61131-2 DI5, DI6 discrete input level 1 PLC IEC 65A-68 STOA, STOB discrete input level 1 PLC IEC 61131-2","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz with derating factor 2...8 kHz adjustable","Analogue output type":"Software-configurable voltage AO1, AO2 0...10 V DC 470 Ohm 10 bits Software-configurable current AO1, AO2 0...20 mA 10 bits","Discrete input logic":"Positive logic (source) DI1...DI6), < 5 V, > 11 V Negative logic (sink) DI1...DI6), > 16 V, < 10 V Positive logic (source) DI5, DI6), < 0.6 V, > 2.5 V Positive logic (source) STOA, STOB), < 5 V, > 11 V","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 8970 W 2.5 kHz normal duty) Forced convection 6770 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"660.0 A at 2.5 kHz normal duty 520.0 A at 2.5 kHz heavy duty","Maximum switching current":"Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC","Maximum transient current":"726 A 60 s normal duty) 780 A 60 s heavy duty)","Minimum switching current":"Relay output R1, R2, R3 5 mA 24 V DC","Product or component type":"Variable speed drive","[Us] rated supply voltage":"480 V - 15...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV6A0C35T4?filename=Schneider+Electric_Altivar-Process-ATV600_ATV6A0C35T4.pdf', 'path_name': '94507340c4a704963711608ae5e43e52.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/94507340c4a704963711608ae5e43e52.pdf', 'status': 1}","sourceUrl":"https://www.se.com/in/en/product/ATV6A0C35T4/variable-speed-drive-altivar-process-atv600-apm-single-480-v-550-hp/"},"ai":{"faq":[{"question":"What communication protocols does the ATV6A0C35T4 support?","answer":"It includes built-in Modbus serial (RS-485 RTU) and Ethernet IP/Modbus TCP with half/full duplex and auto-negotiation. Option cards for slot A add Profibus, PROFINET, DeviceNet, CANopen, or Modbus TCP/EtherNet/IP."},{"question":"What are the supply voltage requirements?","answer":"Digital inputs and STO require a 24 V DC supply (19–30 V for inputs, 21–27 V for STO). Internal supplies also provide 10.5 V DC ±5% for a potentiometer. All are short-circuit protected under 200 mA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0C35T4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0C35T4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}