{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0M10N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0M10N6","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0M10N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0M10N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 series, ATV6A0M10N6 AC drive, modular version, 710 kW at 500 V normal duty, 560 kW heavy duty, cabinet mount, CE marked.","salesMarkdown":"## Sizing the drive to the load The ATV6A0M10N6: This drive is rated for 710 kW at 500 V in normal duty (110 % overload for 60 s) and 560 kW in heavy duty (150 % overload for 60 s). The line current at 500 V is 954 A for normal duty, 758 A for heavy duty. The apparent power works out to 826 kVA and 656 kVA respectively. That's a big cabinet-mount drive — plan the incoming cable and fuse sizing around the 954 A figure for normal duty applications. It handles both asynchronous and synchronous motors. The output voltage tracks the supply voltage, so no step-up transformer needed if the line is at 500 V. Switching frequency is adjustable from 2 to 4.9 kHz with a derating factor — running at the higher end quiets motor whine but reduces continuous output current. Factor that into the thermal design of the panel. ## Safety and compliance — the integrated STO matters That means you can wire the STO terminals directly into the safety circuit without an external safety relay for many applications — saves panel space and wiring time. The drive also includes thermal protection for both motor and drive, phase loss detection, overcurrent, short-circuit, and DC bus overvoltage monitoring. The integrated EMC filter meets IEC 61800-3 category C3, rated for 300 m of motor cable. That covers most industrial installations without an external filter. The prospective line Isc is 50 kA — the drive can be installed on a supply with up to 50 kA available fault current. CE marked, pollution degree 2 per IEC 61800-5-1. The protection degree is UL type 1 or type 12 when integrated into a cabinet — the drive itself is not rated for standalone wet-area installation. ## Communication and I/O expansion Comes with dual-port Ethernet/IP and Modbus TCP (10/100 Mbit/s, half/full duplex, auto-negotiation) plus a 2-wire RS-485 Modbus serial port running at 4.8 to 38.4 kbit/s. The Modbus serial supports RTU framing and up to 247 slave addresses. Slot A accepts a wide range of fieldbus option cards: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (RJ45, SUB-D 9, or screw terminals). Slot A and slot B also accept digital/analog I/O extension modules and output relay extension modules. That gives flexibility to match whatever network the plant floor runs. Cabinet mount only — the drive is not a standalone enclosure. The kit includes the control unit, mechanical mounting hardware, power connection set, fuses, the 200 kW power module, and a front cover. Forced convection cooling, so leave clearance above and below for airflow. Operates at altitudes up to 2000 m with current derating above 1000 m. Ambient temperature range is not explicitly stated in the spec table, but the 5–95 % non-condensing humidity range (IEC 60068-2-3) gives a sense of the environment it tolerates. Vibration resistance is 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz; shock resistance is 4 gn for 11 ms. Noise level is 74 dB — plan for hearing protection if the drive is in a walk-in panel or near operators. ## Power quality and harmonic performance Total harmonic current distortion (THDi) is less than 48 % at full load per IEC 61000-3-12. That's a standard 6-pulse rectifier figure — if the plant has strict harmonic limits or a weak supply, budget for an external line reactor or active filter. The drive also meets IEC 61800-3 and IEC 61000-3-12 for EMC and harmonic compliance.","metaTitle":"Schneider ATV6A0M10N6 Altivar Process VFD, 710 kW","metaDescription":"Schneider Electric ATV6A0M10N6 Altivar Process ATV600 AC drive. 710 kW at 500 V normal duty, STO SIL 3, integrated EMC filter.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"title":"ATV6A0M10N6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"74 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, single 500 V, 710 kW","Line current":"954.0 A 500 V normal duty) 758.0 A 500 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"826 kVA at 500 V normal duty 656 kVA at 500 V heavy duty","Motor power kW":"710.0 kW at 500 V normal duty 560.0 kW at 500 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 5.0 power module 200 kW 4 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 17500 W 2.5 kHz normal duty) Forced convection 14100 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"1030.0 A at 2.5 kHz normal duty 830.0 A at 2.5 kHz heavy duty","Maximum transient current":"1133 A 60 s normal duty) 1245 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"500 V - 10...15 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV6A0M10N6/variable-speed-drive-altivar-process-atv600-apm-single-500-v-710-kw/"},"ai":{"faq":[{"question":"What motor types does ATV6A0M10N6 support?","answer":"It is designed for both asynchronous (induction) and synchronous motors. The drive's control algorithm handles both types without hardware changes."},{"question":"What safety functions are built into ATV6A0M10N6?","answer":"The drive also includes thermal protection for motor and drive, phase loss, overcurrent, short-circuit, and DC bus overvoltage protection."},{"question":"What communication protocols does ATV6A0M10N6 support?","answer":"Built-in dual-port Ethernet/IP and Modbus TCP (10/100 Mbit/s) plus a 2-wire RS-485 Modbus serial port (RTU, 4.8–38.4 kbit/s). Slot A accepts option cards for Profibus DP V1, PROFINET, DeviceNet, CANopen, and additional I/O or relay modules."},{"question":"What is the THDi of ATV6A0M10N6?","answer":"Total harmonic current distortion is less than 48 % at full load, measured per IEC 61000-3-12. This is typical for a 6-pulse drive; for stricter harmonic limits, an external line reactor or active filter may be needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0M10N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0M10N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}