{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0M10N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0M10N6","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0M10N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0M10N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 series, ATV6A0M10N6 AC drive, modular version, 710 kW at 500 V normal duty, 560 kW heavy duty, cabinet mount, CE marked.","salesMarkdown":"## Sizing the drive to the load The ATV6A0M10N6: This drive is rated for 710 kW at 500 V in normal duty (110 % overload for 60 s) and 560 kW in heavy duty (150 % overload for 60 s). The line current at 500 V is 954 A for normal duty, 758 A for heavy duty. The apparent power works out to 826 kVA and 656 kVA respectively. That's a big cabinet-mount drive — plan the incoming cable and fuse sizing around the 954 A figure for normal duty applications. It handles both asynchronous and synchronous motors. The output voltage tracks the supply voltage, so no step-up transformer needed if the line is at 500 V. Switching frequency is adjustable from 2 to 4.9 kHz with a derating factor — running at the higher end quiets motor whine but reduces continuous output current. Factor that into the thermal design of the panel. ## Safety and compliance — the integrated STO matters That means you can wire the STO terminals directly into the safety circuit without an external safety relay for many applications — saves panel space and wiring time. The drive also includes thermal protection for both motor and drive, phase loss detection, overcurrent, short-circuit, and DC bus overvoltage monitoring. The integrated EMC filter meets IEC 61800-3 category C3, rated for 300 m of motor cable. That covers most industrial installations without an external filter. The prospective line Isc is 50 kA — the drive can be installed on a supply with up to 50 kA available fault current. CE marked, pollution degree 2 per IEC 61800-5-1. The protection degree is UL type 1 or type 12 when integrated into a cabinet — the drive itself is not rated for standalone wet-area installation. ## Communication and I/O expansion Comes with dual-port Ethernet/IP and Modbus TCP (10/100 Mbit/s, half/full duplex, auto-negotiation) plus a 2-wire RS-485 Modbus serial port running at 4.8 to 38.4 kbit/s. The Modbus serial supports RTU framing and up to 247 slave addresses. Slot A accepts a wide range of fieldbus option cards: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (RJ45, SUB-D 9, or screw terminals). Slot A and slot B also accept digital/analog I/O extension modules and output relay extension modules. That gives flexibility to match whatever network the plant floor runs. Cabinet mount only — the drive is not a standalone enclosure. The kit includes the control unit, mechanical mounting hardware, power connection set, fuses, the 200 kW power module, and a front cover. Forced convection cooling, so leave clearance above and below for airflow. Operates at altitudes up to 2000 m with current derating above 1000 m. Ambient temperature range is not explicitly stated in the spec table, but the 5–95 % non-condensing humidity range (IEC 60068-2-3) gives a sense of the environment it tolerates. Vibration resistance is 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz; shock resistance is 4 gn for 11 ms. Noise level is 74 dB — plan for hearing protection if the drive is in a walk-in panel or near operators. ## Power quality and harmonic performance Total harmonic current distortion (THDi) is less than 48 % at full load per IEC 61000-3-12. That's a standard 6-pulse rectifier figure — if the plant has strict harmonic limits or a weak supply, budget for an external line reactor or active filter. The drive also meets IEC 61800-3 and IEC 61000-3-12 for EMC and harmonic compliance.","metaTitle":"Schneider ATV6A0M10N6 Altivar Process VFD, 710 kW","metaDescription":"Schneider Electric ATV6A0M10N6 Altivar Process ATV600 AC drive. 710 kW at 500 V normal duty, STO SIL 3, integrated EMC filter.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"954.0 A 500 V normal duty) 758.0 A 500 V heavy duty)","Frequency":"50...60 Hz - 5...5 %","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.1 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV6A0M10N6/variable-speed-drive-altivar-process-atv600-apm-single-500-v-710-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6A0M10N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0M10N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0M10N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}