{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6A0M10Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6A0M10Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6A0M10Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6A0M10Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600, ATV6A0M10Q6, modular version, 1000 kW normal duty at 690 V, 969 A line current, integrated EMC filter C3.","salesMarkdown":"This ATV6A0M10Q6 is a 1000 kW normal duty / 800 kW heavy duty drive at 690 V from the Altivar Process ATV600 series, modular version. Line current sits at 969 A normal duty, 779 A heavy duty. It includes an integrated EMC filter rated for 300 m cable (C3 category), so you can avoid an external filter for most industrial installations with a separate transformer. The drive supports synchronous and asynchronous motors, with 2...4.9 kHz adjustable switching frequency – factor derating above 1 kHz if you need higher output frequency clean. Cooling is forced convection; mount it in a cabinet with UL type 1 or 12 enclosure rating. ## Fieldbus and safety Slot A accepts a range of communication modules: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (RJ45, SUB-D 9, or screw terminal). There are also I/O and relay extension modules for Slot A/B. The drive itself has a Modbus serial port (2-wire RS 485, RTU) and an Ethernet/Modbus TCP port (10/100 Mbit/s, half/full duplex). The Safe Torque Off function protects both motor and drive from unintended restart – no external safety relay needed for the basic stop function. Thermal protection, motor phase break, overcurrent, overvoltage, and earth fault protections are all on-board. ## Wiring and mounting notes Cabinet mount only. Line side screw terminal; motor side uses M10 x 2 bars. Control wiring via removable screw terminals (0.5...1.5 mm² / AWG 20...16). Vibration resistance: 1.5 mm peak-to-peak at 2...13 Hz, 0.5 gn at 13...200 Hz. Shock resistance: 4 gn for 11 ms. Relative humidity 5...95% non-condensing. Allow adequate clearance for forced convection airflow – the fan is integral. The kit includes control unit, mechanical mounting kits, power connection set, fuses, a 200 kW power module (note: this is a multi-module configuration for the full 1000 kW?), and front covers. Verify the exact kit composition for your order.","metaTitle":"Schneider ATV6A0M10Q6, 1000kW 690V Altivar Process","metaDescription":"ATV6A0M10Q6 active production drive, 1000 kW normal duty / 800 kW heavy duty at 690 V, STO SIL 3, modular version. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6A0M10Q6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"74 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, single 690 V, 1000 kW","Line current":"969.0 A 690 V normal duty) 779.0 A 690 V heavy duty)","Maximum THDI":"<48 % full load IEC 61000-3-12","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"1158 kVA at 690 V normal duty 931 kVA at 690 V heavy duty","Motor power kW":"1000.0 kW at 690 V normal duty 800.0 kW at 690 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 5.0 power module 200 kW 4 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 17700 W 2.5 kHz normal duty) Forced convection 14200 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"1030.0 A at 2.5 kHz normal duty 830.0 A at 2.5 kHz heavy duty","Maximum transient current":"1133 A 60 s normal duty) 1245 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 15...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV6A0M10Q6/variable-speed-drive-altivar-process-atv600-apm-single-690-v-1000-kw/"},"ai":{"faq":[{"question":"What is ATV6A0M10Q6's listed marking on this component line?","answer":"The marking is CE, indicating compliance with applicable EU directives."},{"question":"What is ATV6A0M10Q6's listed variant?","answer":"It is the modular version of the Altivar Process ATV600 series."},{"question":"What compliance documentation does this drive provide?","answer":"ATV6A0M10Q6 carries CE marking and complies with IEC 61800-3 (EMC, integrated filter C3), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety with STO SIL 3)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6A0M10Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6A0M10Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}